2905577
SKU
PHX2905577
MPN
MINI MCR-SL-IDS-I-I
Weight
0.088 kg
MINI MCR-SL-IDS-I-I - Output signal conditioner
3-way output signal conditioner for transmitting 0/4 ... 20 mA signals from the controller to a load located in the field with simultaneous 3-way electrical isolation between the input, output, and supply, with screw connection
Technical Specifications
Utilization restriction
| EMC note | EMC: class A product, see manufacturer's declaration in the download area |
Product properties
| Product family | MINI Analog |
| No. of channels | 1 |
Insulation characteristics
| Overvoltage category | II |
| Pollution degree | 2 |
Electrical properties
| Electrical isolation | 3-way isolation |
| Limit frequency (3 dB) | > 175 Hz |
| Protective circuit | Transient protection |
| Signal transmission behavior | In = Out |
| Step response (10-90%) | < 2 ms |
| Maximum temperature coefficient | < 0.01 %/K |
| Temperature coefficient, typical | < 0.01 %/K |
| Maximum transmission error | ≤ 0.1 % (of final value) |
Electrical isolation Input/output/power supply
| Rated Insulation Voltage | 50 V AC/DC |
| Test voltage | 1.5 kV AC (50 Hz, 60 s) |
| Insulation | Basic insulation in accordance with IEC/EN 61010 |
Supply
| Nominal Supply Voltage | 24 V DC |
| Supply Voltage Range | 19.2 V DC ... 30 V DC (The DIN rail connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, item no. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail in accordance with EN 60715) |
| Power consumption | < 600 mW (at 24 V DC) |
Signal
| Number of Inputs | 1 |
| Current Input Signal | 0 mA ... 20 mA |
| Current Input Signal | 4 mA ... 20 mA |
| Max. current input signal | 20 mA |
| Input voltage limitation | < 2 V (20 mA) |
Signal: Current
| Number of Outputs | 1 |
| Current Output Signal | 0 mA ... 20 mA |
| Current Output Signal | 4 mA ... 20 mA |
| Load/Output Load Current Output | ≤ 800 Ω (at 20 mA) |
| Ripple | < 20 mVrms |
Connection data
| Connection Method | Screw connection |
| Stripping length | 12 mm |
| Screw thread | M3 |
| Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section AWG | 26 ... 12 |
Data communication (bypass)
| HART Function | Yes |
| Limit frequency (3 dB) | 2.5 Hz |
Dimensions
| Width | 6.2 mm |
| Height | 93.1 mm |
| Depth | 101.2 mm |
Material specifications
| Color | green (RAL 6021) |
| Housing Material | PBT |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 2 |
Ambient conditions
| Degree of Protection | IP20 |
| Ambient Temperature (Operation) | -20 °C ... 60 °C |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Altitude | ≤ 2000 m |
| Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
CE
| Certificate | CE-compliant |
UKCA
| Certificate | UKCA-compliant |
UL, USA/Canada
| Identification | UL 508 Listed |
| Identification | Class I, Div. 2, Groups A, B, C, D T4 |
| Identification | Class I, Zone 2, Group IIC |
Shipbuilding approval
| Certificate | DNV GL TAA000020N |
DNV GL data
| Temperature | B |
| Humidity | B |
| Vibration | B |
| EMC | A |
| Enclosure | Required protection according to the Rules shall be provided upon installation on board |
EMC data
| Noise immunity | EN 61000-6-2 |
| Note | When being exposed to interference, there may be minimal deviations. |
| Electromagnetic compatibility | Conformance with EMC directive |
| Noise emission | EN 61000-6-4 |
Electrostatic discharge
| Standards/regulations | EN 61000-4-2 |
| Comments | Safety measures must be taken to prevent electrostatic discharge. |
Electromagnetic HF field
| Designation | Electromagnetic RF field |
| Standards/regulations | EN 61000-4-3 |
| Typical deviation from the measuring range final value | 3 % |
Fast transients (burst)
| Designation | Fast transients (burst) |
| Standards/regulations | EN 61000-4-4 |
| Typical deviation from the measuring range final value | 3 % |
Surge current load (surge)
| Standards/regulations | EN 61000-4-5 |
| Comments | Criterion B |
Conducted interference
| Designation | Conducted interferences |
| Standards/regulations | EN 61000-4-6 |
| Typical deviation from the measuring range final value | 3 % |
Standards and Regulations
| Electrical isolation | 3-way isolation |
Mounting
| Mounting Type | DIN rail mounting |
| Assembly instructions | The DIN rail connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, item no. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail in accordance with EN 60715. |
| Mounting Position | any |
Accessories
Why Proax for Phoenix Contact 2905577?
Proax is an authorized distributor of Phoenix Contact 2905577 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
| Pack Size | 1 |
Recommended
MINI MCR-SL-CVS-24-5-10-SP-NC - Constant voltage source, input voltage: 9.6 V DC ... 30 V DC, output voltage: 10 V, 7.5 V, 5 V, 2.5 V DC, electrically isolated, can be configured via DIP switches, spring-cage connection technology, standard configuration. Replacement part: 2902065 MINI MCR-2-CVCS-PT.