Proax

Currency
0 Items
proax logo
Cart
Phoenix ContactOfficial Distributor

By Phoenix Contact

SKU
MPN
MINI MCR-SL-I-U-4
Weight
0.087 kg
This product is Not Cancellable/Not Returnable

MINI MCR-SL-I-U-4 - Signal conditioner

MCR 3-way isolating amplifier, for electrical isolation of analog signals, with screw connection, input signal: 4 mA ... 20 mA, output signal: 0 A ... 10 V

  • Power supply possible via the foot element (TBUS)
  • Low power consumption
  • Entry-level alternative to configurable signal conditioners
  • Highly-compact isolating amplifier for electrical isolation, conversion, amplification, and filtering of standard analog signals
  • 3-way isolation
  • Fixed signal combinations
Technical Specifications

Utilization restriction

EMC noteEMC: class A product, see manufacturer's declaration in the download area

Product properties

Product familyMINI Analog
No. of channels1

Insulation characteristics

Overvoltage categoryII
Pollution degree2

Electrical properties

Electrical isolationBasic insulation in accordance with EN 61010
Electrical isolation between input and outputyes
Limit frequency (3 dB)approx. 100 Hz
Maximum power dissipation for nominal condition434.3 mW
Step response (10-90%) 3.5 ms
Maximum temperature coefficient< 0.01 %/K
Temperature coefficient, typical< 0.002 %/K
Maximum transmission error≤ 0.1 % (of final value)

Electrical isolation Input/output/power supply

Rated Insulation Voltage30 V AC
Rated Insulation Voltage50 V DC
Test voltage1.5 kV AC (50 Hz, 60 s)

Supply

Nominal Supply Voltage24 V DC
Supply Voltage Range19.2 V DC ... 30 V DC (The DIN rail connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, item no. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail in accordance with EN 60715)
Max. current consumption< 9 mA
Power consumption< 200 mW

Signal: Current

Number of Inputs1
Configurable/programmableno
Current Input Signal4 mA ... 20 mA
Max. current input signal50 mA
Input resistance current inputapprox. 50 Ω

Signal: Voltage

Number of Outputs1
Configurable/programmableno
Voltage output signal0 V ... 10 V
Max. voltage output signal12.5 V
Short-circuit currentapprox. 2 mA
Load/output load voltage output≥ 10 kΩ
Ripple< 20 mVPP
Ripple< 20 mVPP (at 10 kΩ)

Connection data

Connection MethodScrew connection
Stripping length12 mm
Screw threadM3
Conductor cross section rigid0.2 mm² ... 2.5 mm²
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section AWG26 ... 12

Dimensions

Width6.2 mm
Height93.1 mm
Depth101.2 mm

Material specifications

Colorgreen (RAL 6021)
Housing MaterialPBT
Fire protection for rail vehicles (DIN EN 45545-2) R22HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24HL 1 - HL 2

Ambient conditions

Degree of ProtectionIP20
Ambient Temperature (Operation)-20 °C ... 65 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Altitude≤ 2000 m
Permissible humidity (operation)5 % ... 95 % (non-condensing)

CE

CertificateCE-compliant

UKCA

CertificateUKCA-compliant

UL, USA/Canada

IdentificationUL 508 Recognized
IdentificationClass I, Div. 2, Groups A, B, C, D T4

Shipbuilding approval

CertificateDNV GL TAA000020N

DNV GL data

TemperatureB
HumidityB
VibrationB
EMCA
EnclosureRequired protection according to the Rules shall be provided upon installation on board

EMC data

Noise immunityEN 61000-6-2
NoteWhen being exposed to interference, there may be minimal deviations.
Electromagnetic compatibilityConformance with EMC directive
Noise emissionEN 61000-6-4

Electrostatic discharge

Standards/regulationsEN 61000-4-2
CommentsSafety measures must be taken to prevent electrostatic discharge.

Electromagnetic HF field

DesignationElectromagnetic RF field
Standards/regulationsEN 61000-4-3
Typical deviation from the measuring range final value5 %

Fast transients (burst)

DesignationFast transients (burst)
Standards/regulationsEN 61000-4-4
Typical deviation from the measuring range final value5 %

Surge current load (surge)

Standards/regulationsEN 61000-4-5
CommentsCriterion B

Conducted interference

DesignationConducted interferences
Standards/regulationsEN 61000-4-6
Typical deviation from the measuring range final value5 %

Standards and Regulations

Electrical isolationBasic insulation in accordance with EN 61010

Mounting

Mounting TypeDIN rail mounting
Assembly instructionsThe DIN rail connector can be used for bridging the supply voltage. It can be snapped onto a 35 mm EN 60715 DIN rail.
Mounting Positionany
Accessories

Why Proax for Phoenix Contact 2813538?

Proax is an authorized distributor of Phoenix Contact 2813538 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information

Pack Size1
Recommended

Not in stock

Request lead time or order—we'll ensure quick delivery

Phoenix Contact Availability