2864095
SKU
PHX2864095
MPN
MINI MCR-SL-R-UI
Weight
0.098 kg
MINI MCR-SL-R-UI - Resistance/potiposition transducer
MCR potiposition transducer for conversion of potentiometer positions into a standard analog signal, 0 Ω input... 100 Ω to 0 kΩ ... 100 kΩ
- Power supply possible via the foot element (TBUS)
- Automatic potentiometer detection without manual adjustment
- Error indication via diagnostic LED and analog signal
- For 100 Ω to 100 kΩ potentiometers
- potentiometer signals to create standard signals
- Configurable measuring range and output signals
- Highly-compact potentiometer transducer for electrical isolation, conversion, amplification, and filtering of
- Input and output signals can be configured via DIP switches
- 3-way isolation
- A potentiometer sub-range can be linearized via the "teach-in" switch on the device
Technical Specifications
Utilization restriction
| EMC note | EMC: class A product, see manufacturer's declaration in the download area |
Product properties
| Product family | MINI Analog |
| No. of channels | 1 |
| Configuration | DIP switches |
Insulation characteristics
| Overvoltage category | II |
| Pollution degree | 2 |
Functionality
| Configuration | DIP switches |
Electrical properties
| Maximum power dissipation for nominal condition | 235.5 mW |
| Step response (0–99%) | < 30 ms |
| Maximum temperature coefficient | < 0.02 %/K |
| Temperature coefficient, typical | < 0.02 %/K |
| Maximum transmission error | < 0.2 % |
Electrical isolation Input/output/power supply
| Rated Insulation Voltage | 30 V AC |
| Rated Insulation Voltage | 50 V DC |
| Test voltage | 1.5 kV AC (50 Hz, 60 s) |
| Insulation | Basic insulation in accordance with IEC/EN 61010 |
Supply
| Nominal Supply Voltage | 24 V DC |
| Supply Voltage Range | 19.2 V DC ... 30 V DC (The DIN rail connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, item no. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail in accordance with EN 60715) |
| Typical current consumption | < 25 mA (at 24 V DC) |
| Power consumption | < 500 mW |
Signal: Resistance
| Number of Inputs | 1 |
| Resistance range | 100 Ω ... 100 kΩ |
| Reference voltage source | < 3.6 V |
Signal: Voltage/current
| Number of Outputs | 1 |
| Voltage output signal | 0 V ... 5 V |
| Voltage output signal | 1 V ... 5 V |
| Voltage output signal | 0 V ... 10 V |
| Voltage output signal | 10 V ... 0 V |
| Max. voltage output signal | 12.5 V |
| Non-load voltage | 12.5 V |
| Current Output Signal | 0 mA ... 20 mA |
| Current Output Signal | 4 mA ... 20 mA |
| Current Output Signal | 20 mA ... 0 mA |
| Current Output Signal | 20 mA ... 4 mA |
| Max. current output signal | 23 mA |
| Short-circuit current | 10 mA |
| Load/output load voltage output | > 10 kΩ |
| Load/Output Load Current Output | < 500 Ω (20 mA) |
| Ripple | < 20 mVPP (500 Ω) |
| Ripple | < 20 mVPP (10 kΩ) |
| Behavior in the event of a sensor error | 0 % ... 105 % (configurable) |
Connection data
| Connection Method | Screw connection |
| Stripping length | 12 mm |
| Screw thread | M3 |
| Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section AWG | 26 ... 12 |
Signaling
| Error indication | Red LED |
Dimensions
| Width | 6.2 mm |
| Height | 93.1 mm |
| Depth | 101.2 mm |
Material specifications
| Color | green (RAL 6021) |
| Housing Material | PBT |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 2 |
Ambient conditions
| Degree of Protection | IP20 |
| Ambient Temperature (Operation) | -20 °C ... 65 °C |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Altitude | ≤ 2000 m |
| Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
CE
| Certificate | CE-compliant |
UKCA
| Certificate | UKCA-compliant |
UL, USA/Canada
| Identification | UL 508 Recognized |
| Identification | Class I, Div. 2, Groups A, B, C, D T4 |
Shipbuilding approval
| Certificate | DNV GL TAA000020N |
DNV GL data
| Temperature | B |
| Humidity | B |
| Vibration | B |
| EMC | A |
| Enclosure | Required protection according to the Rules shall be provided upon installation on board |
EMC data
| Noise immunity | EN 61000-6-2 |
| Note | When being exposed to interference, there may be minimal deviations. |
| Electromagnetic compatibility | Conformance with EMC directive |
| Noise emission | EN 61000-6-4 |
Electromagnetic HF field
| Designation | Electromagnetic RF field |
| Standards/regulations | EN 61000-4-3 |
| Typical deviation from the measuring range final value | 5 % |
Fast transients (burst)
| Designation | Fast transients (burst) |
| Standards/regulations | EN 61000-4-4 |
| Typical deviation from the measuring range final value | 5 % |
Conducted interference
| Designation | Conducted interferences |
| Standards/regulations | EN 61000-4-6 |
| Typical deviation from the measuring range final value | 5 % |
Mounting
| Mounting Type | DIN rail mounting |
| Mounting Position | any |
Accessories
Why Proax for Phoenix Contact 2864095?
Proax is an authorized distributor of Phoenix Contact 2864095 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
| Pack Size | 1 |
Recommended