2864781
SKU
PHX2864781
MPN
MINI MCR-SL-2CP-I-I-SP
Weight
0.081 kg
This product is Not Cancellable/Not Returnable
Series MINI-MCR-SL
MINI MCR-SL-2CP-I-I-SP - Loop-powered isolators
MCR passive isolator, two-channel, for electrical isolation of current signals without supply voltage, with spring-cage connection.Replacement item: 2864655 MINI MCR-SL-2CP-I-I
- Voltage drop at isolating amplifier of just 1.7 V
- Does not require additional auxiliary voltage
- Two channels on a design width of just 6.2 mm
- Highly compact 2-conductor passive isolators for the electrical isolation and filtering of standard analog signals
- Supplied by an input loop
Technical Specifications
Product properties
| Product family | MINI Analog |
| No. of channels | 2 |
Insulation characteristics
| Overvoltage category | II |
| Pollution degree | 2 |
Electrical properties
| Rated Insulation Voltage | 50 V AC/DC |
| Electrical isolation | Basic insulation in accordance with EN 61010 |
| Electrical isolation between input and output | yes |
| Limit frequency (3 dB) | 75 Hz |
| Test voltage input/output | 1.5 kV AC (50 Hz, 60 s) |
| Test voltage channel/channel | 1.5 kV AC (50 Hz, 60 s) |
| Signal transmission behavior | In = Out |
| Step response (10-90%) | 5 ms (at 600 Ω load) |
| Maximum temperature coefficient | ≤ 0.002 %/K (of measured value / 100 Ω load) |
| Temperature coefficient, typical | < 0.002 %/K (of measured value / 100 Ω load) |
| Maximum transmission error | ≤ 0.1 % (of final value) |
| Additional error, load-dependent | < 0.03 % (of measured value / 100 Ω load) |
Supply
| Supply Voltage Range | loop-powered, no external supply necessary |
| Power consumption | 34 mW (per channel) |
Signal
| Description of the input | Current input |
| Number of Inputs | 2 |
| Configurable/programmable | no |
| Max. voltage input signal | 18 V |
| Current Input Signal | 0 mA ... 20 mA |
| Current Input Signal | 4 mA ... 20 mA |
| Max. current input signal | 40 mA |
| Response current | approx. 190 µA |
| Input voltage limitation | < 2 V (20 mA) |
| Voltage dissipation | 1.9 V (I = 20 mA) |
Signal: Current
| Number of Outputs | 2 |
| Configurable/programmable | no |
| Current Output Signal | 0 mA ... 20 mA |
| Current Output Signal | 4 mA ... 20 mA |
| Load/Output Load Current Output | < 600 Ω (at I = 20 mA output signal) |
| Ripple | < 10 mVrms (at 600 Ω) |
Connection data
| Connection Method | Spring-cage connection |
| Stripping length | 8 mm |
| Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section AWG | 24 ... 12 |
Dimensions
| Width | 6.2 mm |
| Height | 93.1 mm |
| Depth | 102.5 mm |
Material specifications
| Color | green (RAL 6021) |
| Housing Material | PBT |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 2 |
Ambient conditions
| Degree of Protection | IP20 |
| Ambient Temperature (Operation) | -20 °C ... 65 °C |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
CE
| Certificate | CE-compliant |
ATEX
| Identification | II 3 G Ex nA II T6 X |
UL, USA/Canada
| Identification | UL 508 Recognized |
| Identification | Class I, Div. 2, Groups A, B, C, D |
GL
| Identification | GL EMC 2 D |
EMC data
| Noise immunity | EN 61000-6-2 |
| Note | When being exposed to interference, there may be minimal deviations. |
| Electromagnetic compatibility | Conformance with EMC directive |
| Noise emission | EN 61000-6-4 |
Electrostatic discharge
| Standards/regulations | EN 61000-4-2 |
| Comments | Criterion B |
Electromagnetic HF field
| Designation | Electromagnetic RF field |
| Standards/regulations | EN 61000-4-3 |
| Evaluation criterion | A |
Fast transients (burst)
| Designation | Fast transients (burst) |
| Standards/regulations | EN 61000-4-4 |
| Evaluation criterion | B |
Surge current load (surge)
| Standards/regulations | EN 61000-4-5 |
| Comments | Criterion B |
Conducted interference
| Designation | Conducted interferences |
| Standards/regulations | EN 61000-4-6 |
| Evaluation criterion | A |
Standards and Regulations
| Electrical isolation | Basic insulation in accordance with EN 61010 |
Mounting
| Mounting Type | DIN rail mounting |
| Assembly instructions | The DIN rail connector can be used for bridging the supply voltage. It can be snapped onto a 35 mm EN 60715 DIN rail. |
| Mounting Position | any |
Accessories
Why Proax for Phoenix Contact 2864781?
Proax is an authorized distributor of Phoenix Contact 2864781 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
| Pack Size | 1 |
Recommended
MINI MCR-SL-CVS-24-5-10-SP-NC - Constant voltage source, input voltage: 9.6 V DC ... 30 V DC, output voltage: 10 V, 7.5 V, 5 V, 2.5 V DC, electrically isolated, can be configured via DIP switches, spring-cage connection technology, standard configuration. Replacement part: 2902065 MINI MCR-2-CVCS-PT.