MINI MCR-SL-2CP-I-I - Loop-powered isolators
MCR passive isolator, 2-channel, for the electrical isolation of current signals without auxiliary power, with screw connection
- Voltage drop at isolating amplifier of just 1.7 V
- Does not require additional auxiliary voltage
- Two channels on a design width of just 6.2 mm
- Highly compact 2-conductor passive isolators for the electrical isolation and filtering of standard analog signals
- Supplied by an input loop
Technical Specifications
Dimensions
Width | 6.2 mm |
Height | 93.1 mm |
Depth | 101.2 mm |
Ambient conditions
Ambient Temperature (Operation) | -20 °C ... 65 °C |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Maximum altitude | ≤ 2000 m |
Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
Degree of Protection | IP20 |
Noise immunity | EN 61000-6-2 When being exposed to interference, there may be minimal deviations. |
Input data
Designation | Current input |
Number of Inputs | 2 |
Configurable/programmable | no |
Current Input Signal | 0 mA ... 20 mA |
Current Input Signal | 4 mA ... 20 mA |
Max. input voltage | 18 V |
Max. input current | 40 mA |
Response current | approx. 190 µA |
Input voltage limitation | < 2 V (20 mA) |
Voltage dissipation | 1.9 V (I = 20 mA) |
Output data
Output name | Current output |
Number of Outputs | 2 |
Configurable/programmable | no |
Current Output Signal | 0 mA ... 20 mA |
Current Output Signal | 4 mA ... 20 mA |
Load/Output Load Current Output | < 600 Ω (at I = 20 mA output signal) |
Ripple | < 10 mVrms (at 600 Ω) |
Transmission Behavior | 1:1 to input signal |
Power supply
Supply Voltage Range | no separate supply voltage necessary |
Power consumption | 34 mW (per channel) |
Connection data
Connection Method | Screw connection |
Stripping length | 12 mm |
Screw thread | M3 |
Conductor cross section solid | 0.2 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section AWG | 26 ... 12 |
General
No. of channels | 2 |
Maximum transmission error | ≤ 0.1 % (of final value) |
Maximum temperature coefficient | ≤ 0.002 %/K (of measured value / 100 Ω load) |
Temperature coefficient, typical | < 0.002 %/K (of measured value / 100 Ω load) |
Additional error, load-dependent | < 0.03 % (of measured value / 100 Ω load) |
Limit frequency (3 dB) | 75 Hz |
Step response (10-90%) | 5 ms (at 600 Ω load) |
Signal transmission behavior | In = Out |
Electrical isolation | Basic insulation according to EN 61010 |
Overvoltage category | II |
Degree of pollution | 2 |
Rated Insulation Voltage | 50 V AC/DC |
Test voltage input/output | 1.5 kV (50 Hz, 1 min.) |
Test voltage channel/channel | 1.5 kV (50 Hz, 1 min.) |
Electromagnetic compatibility | Conformance with EMC directive |
Noise emission | EN 61000-6-4 |
Noise immunity | EN 61000-6-2 When being exposed to interference, there may be minimal deviations. |
Housing Material | PBT |
Mounting Position | any |
Assembly instructions | The T connector can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715. |
Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 2 |
Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 2 |
Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 2 |
EMC data
Designation | Electromagnetic RF field |
Standards/regulations | EN 61000-4-3 |
Evaluation criterion | A |
Designation | Fast transients (burst) |
Standards/regulations | EN 61000-4-4 |
Evaluation criterion | B |
Designation | Conducted interferences |
Standards/regulations | EN 61000-4-6 |
Evaluation criterion | A |
Standards and Regulations
Electromagnetic compatibility | Conformance with EMC directive |
Noise emission | EN 61000-6-4 |
Standards/regulations | EN 61000-4-2 |
Designation | Electromagnetic RF field |
Standards/regulations | EN 61000-4-3 |
Evaluation criterion | A |
Standards/regulations | EN 61000-4-4 |
Standards/regulations | EN 61000-4-5 |
Designation | Conducted interferences |
Standards/regulations | EN 61000-4-6 |
Evaluation criterion | A |
Electrical isolation | Basic insulation according to EN 61010 |
Conformance/approvals
Designation | CE |
Certificate | CE-compliant |
Designation | UKCA |
Certificate | UKCA-compliant |
Designation | UL, USA / Canada |
Identification | UL 508 Recognized |
Identification | Class I, Div. 2, Groups A, B, C, D |
Designation | Shipbuilding approval |
Certificate | DNV GL TAA00000BW |
Temperature | B |
Humidity | B |
Vibration | B |
EMC | B |
Enclosure | A |
Environmental Product Compliance
China RoHS | Environmentally Friendly Use Period = 50 years |
China RoHS | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
Accessories
Why Proax for Phoenix Contact 2864655?
Proax is an authorized distributor of Phoenix Contact 2864655 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended