MINI MCR-SL-PT100-LP-NC - Temperature measuring transducer
Configurable loop-powered temperature transducer for Pt 100 temperature sensors, configured via DIP switches, with screw connection, not preconfigured
- 2-, 3-, 4-conductor Pt 100 sensors
- Highly-compact loop-powered temperature transducer for electrical isolation, conversion, amplification, and filtering of Pt 100 signals to create standard signals
- Does not require additional auxiliary voltage
- Error indication via diagnostic LED and analog signal
- 2-way isolation
- Input signals can be configured via DIP switches
- Supplied by an output loop
- Temperature measuring range of -150 °C ... 300 °C
Technical Specifications
Utilization restriction
EMC note | EMC: class A product, see manufacturer's declaration in the download area |
Product properties
Product family | MINI Analog |
Configuration | DIP switches |
Insulation characteristics
Overvoltage category | II |
Pollution degree | 2 |
Electrical properties
Linearity error | < 0.05 % (for full measuring range) |
Maximum power dissipation for nominal condition | < 42 mW |
Step response (0–99%) | < 200 ms |
Maximum temperature coefficient | < 0.02 %/K |
Transmission error in the set measuring range | ((90 K / set measuring range [K]) + 0.05)% |
Transmission error in the full measuring range | ≤ 0.25 % |
Electrical isolation Input/output/power supply
Rated Insulation Voltage | 30 V AC |
Rated Insulation Voltage | 50 V DC |
Test voltage | 1.5 kV AC (50 Hz, 60 s) |
Insulation | Basic insulation in accordance with IEC/EN 61010 |
Supply
Designation | Loop-powered |
Supply Voltage Range | 12 V DC ... 30 V DC |
Max. current consumption | < 4.5 mA (without signal current) |
Power consumption | < 150 mW (without signal current) |
Signal
Number of Inputs | 1 |
Measurement
Configurable/programmable | Yes, unconfigured |
Sensor types (RTD) that can be used | Pt 100 (IEC 60751/EN 60751) |
Temperature measuring range | min. 50 K |
Sensor type: | -150 °C ... 300 °C (configurable) |
Sensor input current | 1 mA (constant) |
Max. permissible overall conductor resistance | 10 Ω (Per cable) |
Connection technology | 2-, 3-, 4-conductor |
Error detection limit (short-circuit) | < 30 Ω |
Error detection limit (underrange) | 30 Ω ≤ (start span - 2.5% span) |
Error detection limit (overrange) | (end span + 2.5% span) ≤ approx. 254 Ω |
Error detection limit (wire break) | > approx. 254 Ω |
Signal: Current
Number of Outputs | 1 |
Configurable/programmable | Yes, unconfigured |
Current Output Signal | 4 mA ... 20 mA |
Current Output Signal | 20 mA ... 4 mA |
Max. current output signal | 23 mA (output limit) |
Load/Output Load Current Output | (Usupply - 12 V) / 22 mA |
Ripple | < 20 mVPP (at 500 Ω) |
Connection data
Connection Method | Screw connection |
Stripping length | 12 mm |
Screw thread | M3 |
Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section AWG | 26 ... 12 |
Dimensions
Width | 6.2 mm |
Height | 93.1 mm |
Depth | 101.2 mm |
Material specifications
Color | green (RAL 6021) |
Housing Material | PBT |
Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 2 |
Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 2 |
Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 2 |
Ambient conditions
Degree of Protection | IP20 |
Ambient Temperature (Operation) | -20 °C ... 65 °C |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Altitude | ≤ 2000 m |
Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
CE
Certificate | CE-compliant |
UKCA
Certificate | UKCA-compliant |
UL, USA/Canada
Identification | UL 508 Recognized |
Identification | Class I, Div. 2, Groups A, B, C, D T4 |
EMC data
Noise immunity | EN 61000-6-2 |
Note | When being exposed to interference, there may be minimal deviations. |
Electromagnetic compatibility | Conformance with EMC directive |
Noise emission | EN 61000-6-4 |
Electrostatic discharge
Standards/regulations | EN 61000-4-2 |
Comments | Safety measures must be taken to prevent electrostatic discharge. |
Electromagnetic HF field
Designation | Electromagnetic RF field |
Standards/regulations | EN 61000-4-3 |
Typical deviation from the measuring range final value | 5 % |
Fast transients (burst)
Designation | Fast transients (burst) |
Standards/regulations | EN 61000-4-4 |
Typical deviation from the measuring range final value | 5 % |
Surge current load (surge)
Standards/regulations | EN 61000-4-5 |
Comments | Criterion B |
Conducted interference
Designation | Conducted interferences |
Standards/regulations | EN 61000-4-6 |
Typical deviation from the measuring range final value | 5 % |
Mounting
Mounting Type | DIN rail mounting |
Mounting Position | any |
Accessories
Why Proax for Phoenix Contact 2810308?
Proax is an authorized distributor of Phoenix Contact 2810308 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended