SKU
MPN
UM-2KS50/16DI/RS/SO225
Weight
0.636 kg
Series UM
UM-2KS50/16DI/RS/SO225 - Input module
16-channel digital input module with screw connection and redundant voltage supply. Suitable for Yokogawa SDV 144 card.
Technical Specifications
Product properties
No. of channels | 16 |
Insulation characteristics
Insulation | Functional insulation |
Insulation characteristics: Air clearances and creepage distances
Insulation | Functional insulation |
Overvoltage category | II |
Pollution degree | 2 |
Electrical properties
Nominal voltage UN | 30 V DC |
Max. current carrying capacity per branch | 100 mA |
Max. total current of all branches | 2 A |
Air clearances and creepage distances
Rated Insulation Voltage | 50 V |
Rated surge voltage | 0.5 kV (1.2/50 μs) |
Supported controller YOKOGAWA ProSafe-RS
Suitable I/O card | SDV144 |
Field level
Connection Method | Screw connection |
Number of Positions | 48 |
Conductor cross section rigid | 0.2 mm² ... 4 mm² |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section AWG | 24 ... 12 |
Controller level
Connection Method | Yokogawa KS-compatible |
Number of Connections | 2 |
Number of Positions | 50 |
Tightening torque | 0.5 Nm |
Supply
Connection Method | Screw connection |
Number of Connections | 1 |
Number of Positions | 6 |
Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section AWG | 24 ... 12 |
Signaling
Status display present | Yes |
Item dimensions
Width | 250 mm |
Height | 125.4 mm |
Depth | 75.6 mm |
Material specifications
Color | green (RAL 6021) |
Housing insulation material | PVC |
Ambient conditions
Degree of Protection | IP00 |
Degree of protection (Installation location) | ≥ IP54 (Installation location) |
Ambient Temperature (Operation) | -20 °C ... 55 °C |
Altitude | < 2000 m |
Air clearances and creepage distances
Standards/regulations | DIN EN 50178: 1998-04 |
Mounting
Mounting Type | DIN rail mounting |
Mounting Position | any |
Notes
Notes on operation | Voltage monitoring on the module does not work in combination with upstream HESILED fuse terminal blocks with integrated LED display. |
Notes on operation | For proper use, the specifications of the installation directive (see Downloads) must be observed. For applications or use with third-party products, the specifications, and the safety and warning instructions of the respective third-party manufacturer must also be met. |
Accessories
Why Proax for Phoenix Contact 2319812?
Proax is an authorized distributor of Phoenix Contact 2319812 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended