Series IB-IL-AI

IB IL AI 2/SF-230-PAC - Analog module

Inline, Analog input terminal, Analog inputs: 2, 0 V ... 10 V, -10 V ... 10 V, 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA, connection technology: 2-conductor, transmission speed in the local bus: 500 kbps, 3 dB base frequency at 230 Hz, degree of protection: IP20, including Inline connector and labeling field

  • 2 analog single-ended signal inputs for the connection of either voltage or current signals
  • Connection of sensors in 2-conductor technology
  • Current ranges: 0 mA ... 20 mA, 4 mA ... 20 mA, ±20 mA
  • Voltage ranges: 0 V ... 10 V, ±10 V
  • The channels are parameterized independently of one another via the bus system
  • Measured values can be represented in four different formats
  • Resolution depends on the representation format and the measuring range
  • Process data update of both channels within a max. of 1.5 ms
Technical Specifications

Dimensions

Width12.2 mm
Height136.8 mm
Depth71.5 mm
Note on dimensionsHousing dimensions

Inline local bus

Number of interfaces2
Connection MethodInline data jumper
Transmission Speed500 kbps

Module

ID code (dec.)127
ID code (hex)7F
Length code (hex)02
Length code (dec)02
Process data channel32 bit
Input address area4 Byte
Output address area4 Byte
Register length32 bit
Required parameter data 6 Byte
Required configuration data 4 Byte

Analog: General

Input nameAnalog inputs
Description of the inputSingle-ended inputs, voltage or current
Number of Inputs2
A/D conversion timetyp. 120 µs (per channel)
Connection MethodInline shield connector
Connection technology2-conductor
Note regarding the connection technologyshielded
Current Input Signal0 mA ... 20 mA
Current Input Signal4 mA ... 20 mA
Current Input Signal-20 mA ... 20 mA
Input resistance current input50 Ω (Shunt)
Voltage input signal0 V ... 10 V
Voltage input signal-10 V ... 10 V
Input resistance of voltage input> 220 kΩ
Data formatsIB IL, IB ST, IB RT, standardized representation
Limit frequency (3 dB)230 Hz
Common mode voltage range signal - ground40 V (Between current input and functional ground)
Common mode voltage range signal - ground40 V (between voltage input and functional ground)
Measuring PrincipleSuccessive approximation
Measured value resolution16 bits (15 bits + sign bit)
Measured value representation16 bit two's complement
Protective circuitSurge protection; Suppressor diodes in the analog inputs

Product properties

Product familyInline
Typemodular
Scope of deliveryincluding Inline connector and labeling field
Operating modeProcess data operation with 2 words
Special Properties3 dB base frequency at 230 Hz
Diagnostics messagesFailure of the internal I/O supply yes
Diagnostics messagesI/O error Error message in the process data
Diagnostics messagesUser error Error message in the process data

Insulation characteristics

Overvoltage categoryII (IEC 60664-1, EN 60664-1)
Pollution degree2 (IEC 60664-1, EN 60664-1)

Potentials

Power consumptiontyp. 662 mW
Power consumptionmax. 882 mW

Potentials: Communications power (UL)

Supply Voltage7.5 V DC (via voltage jumper)
Current drawmax. 60 mA
Current drawtyp. 45 mA

Potentials: Supply of analog modules (UANA)

Supply Voltage24 V DC (via voltage jumper)
Supply Voltage Range19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current drawmax. 18 mA
Current drawtyp. 13 mA

Electrical isolation/isolation of the voltage ranges

Test voltage: 7.5 V supply (bus logic), 24 V supply UANA / I/O500 V AC, 50 Hz, 1 min.
Test voltage: 7.5 V supply (bus logic), 24 V supply UANA / functional ground500 V AC, 50 Hz, 1 min.
Test voltage: I/O/functional ground500 V AC, 50 Hz, 1 min.

Connection technology

Connection nameInline connector

Conductor connection

Connection MethodSpring-cage connection
Conductor cross section rigid0.08 mm² ... 1.5 mm²
Conductor cross section flexible0.08 mm² ... 1.5 mm²
Conductor cross section AWG28 ... 16
Stripping length8 mm

Inline connector

Connection MethodSpring-cage connection
Conductor cross section, rigid0.08 mm² ... 1.5 mm²
Conductor cross section, flexible0.08 mm² ... 1.5 mm²
Conductor cross section AWG28 ... 16
Stripping length8 mm

Ambient conditions

Ambient Temperature (Operation)-25 °C ... 55 °C
Degree of ProtectionIP20
Air pressure (operation)70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)70 kPa ... 106 kPa (up to 3000 m above sea level)
Ambient temperature (storage/transport)-25 °C ... 85 °C
Permissible humidity (operation)10 % ... 95 % (non-condensing)
Permissible humidity (storage/transport)10 % ... 95 % (non-condensing)

Standards and Regulations

Protection classIII (IEC 61140, EN 61140, VDE 0140-1)

Mounting

Mounting TypeDIN rail mounting
Accessories

Why Proax for Phoenix Contact 2861577?

Proax is an authorized distributor of Phoenix Contact 2861577 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information

Pack Size1
Recommended

Not in stock

Request lead time or order—we'll ensure quick delivery

Phoenix Contact Availability