IB IL AI 8/SF-PAC - Analog module
Inline, Analog input terminal, Analog inputs: 8, 0 V ... 5 V, -5 V ... 5 V, 0 V ... 10 V, -10 V ... 10 V, 0 V ... 25 V, -25 V ... 25 V, 0 V ... 50 V, 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA, 0 mA ... 40 mA, -40 mA ... 40 mA, connection technology: 2-conductor, transmission speed in the local bus: 500 kbps, degree of protection: IP20, including Inline connectors and marking fields
- 8 analog single-ended signal inputs for the connection of either voltage or current signals
- Connection of sensors in 2-conductor technology
- Current ranges: 0 mA ... 20 mA, 4 mA ... 20 mA, ±20 mA, 0 mA ... 40 mA, ±40 mA
- Voltage ranges: 0 V ... 5 V, ±5 V, 0 V ... 10 V, ±10 V, 0 V ... 25 V, ±25 V, 0 V ... 50 V
- The channels are parameterized independently of one another via the bus system
- Measured values can be represented in five different formats
- 16-bit analog-to-digital converter
- Process data multiplex mode
- High measuring accuracy
Technical Specifications
Dimensions
| Width | 48.8 mm |
| Height | 136.8 mm |
| Depth | 71.5 mm |
| Note on dimensions | Housing dimensions |
Utilization restriction
| CCCex note | Use in potentially explosive areas is not permitted in China. |
Inline local bus
| Connection Method | Inline data jumper |
| Transmission Speed | 500 kbps |
| Transmission physics | Copper |
Module
| ID code (dec.) | 95 |
| ID code (hex) | 5F |
| Length code (hex) | 02 |
| Length code (dec) | 02 |
| Process data channel | 32 bit |
| Input address area | 4 Byte |
| Output address area | 4 Byte |
| Register length | 32 bit |
| Required parameter data | 6 Byte |
| Required configuration data | 5 Byte |
Analog: General
| Input name | Analog inputs |
| Description of the input | Single-ended inputs, voltage or current |
| Number of Inputs | 8 |
| A/D conversion time | approx. 10 µs |
| A/D converter resolution | 16 bit |
| Connection Method | Inline shield connector |
| Connection technology | 2-conductor |
| Note regarding the connection technology | shielded |
| Current Input Signal | 0 mA ... 20 mA |
| Current Input Signal | 4 mA ... 20 mA |
| Current Input Signal | -20 mA ... 20 mA |
| Current Input Signal | 0 mA ... 40 mA |
| Current Input Signal | -40 mA ... 40 mA |
| Input resistance current input | 25 Ω (Shunt) |
| Voltage input signal | 0 V ... 5 V |
| Voltage input signal | -5 V ... 5 V |
| Voltage input signal | 0 V ... 10 V |
| Voltage input signal | -10 V ... 10 V |
| Voltage input signal | 0 V ... 25 V |
| Voltage input signal | -25 V ... 25 V |
| Voltage input signal | 0 V ... 50 V |
| Input resistance of voltage input | > 240 kΩ |
| Data formats | IB IL, IB ST, IB RT, standardized representation, PIO format |
| Filtering | 1st order low pass |
| Limit frequency (3 dB) | 3.5 kHz |
| Measuring Principle | Successive approximation |
| Measured value resolution | 16 bits (15 bits + sign bit) |
| Measured value representation | 16 bit two's complement |
| Protective circuit | Surge protection, overcurrent protection; max. 100% overload (in relation to the nominal value) |
Product properties
| Product family | Inline |
| Type | modular |
| Scope of delivery | including Inline connectors and marking fields |
| Operating mode | Process data operation with 2 words |
| Diagnostics messages | Failure of the power supply at UANA |
| Diagnostics messages | I/O error Error message in the process data |
| Diagnostics messages | User error Error message in the process data |
Insulation characteristics
| Overvoltage category | II (IEC 60664-1, EN 60664-1) |
| Pollution degree | 2 (IEC 60664-1, EN 60664-1) |
Electrical properties
| Maximum power dissipation for nominal condition | 7.2 W |
Potentials
| Power consumption | typ. 936 mW (entire device) |
Potentials: Communications power (UL)
| Supply Voltage | 7.5 V DC (via voltage jumper) |
| Current draw | max. 55 mA |
| Current draw | typ. 48 mA |
Potentials: Supply of analog modules (UANA)
| Supply Voltage | 24 V DC (via voltage jumper) |
| Supply Voltage Range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Current draw | max. 35 mA |
| Current draw | typ. 24 mA |
Electrical isolation/isolation of the voltage ranges
| Test voltage: 7.5 V supply (bus logic), 24 V supply UANA / I/O | 500 V AC, 50 Hz, 1 min. |
| Test voltage: 7.5 V supply (bus logic), 24 V supply UANA / functional ground | 500 V AC, 50 Hz, 1 min. |
| Test voltage: I/O/functional ground | 500 V AC, 50 Hz, 1 min. |
Connection technology
| Connection name | Inline connector |
Conductor connection
| Connection Method | Spring-cage connection |
| Conductor cross section rigid | 0.08 mm² ... 1.5 mm² |
| Conductor cross section flexible | 0.08 mm² ... 1.5 mm² |
| Conductor cross section AWG | 28 ... 16 |
| Stripping length | 8 mm |
Inline connector
| Connection Method | Spring-cage connection |
| Conductor cross section, rigid | 0.08 mm² ... 1.5 mm² |
| Conductor cross section, flexible | 0.08 mm² ... 1.5 mm² |
| Conductor cross section AWG | 28 ... 16 |
| Stripping length | 8 mm |
Ambient conditions
| Ambient Temperature (Operation) | -25 °C ... 55 °C |
| Degree of Protection | IP20 |
| Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Ambient temperature (storage/transport) | -25 °C ... 85 °C |
| Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
| Permissible humidity (storage/transport) | 10 % ... 95 % (non-condensing) |
Standards and Regulations
| Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
Mounting
| Mounting Type | DIN rail mounting |
Accessories
Why Proax for Phoenix Contact 2861412?
Proax is an authorized distributor of Phoenix Contact 2861412 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
| Pack Size | 1 |
Recommended
IB IL AI 8/SF-XC-PAC - Inline, Analog input terminal, Analog inputs: 8, 0 V ... 5 V, -5 V ... 5 V, 0 V ... 10 V, -10 V ... 10 V, 0 V ... 25 V, -25 V ... 25 V, 0 V ... 50 V, 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA, 0 mA ... 40 mA, -40 mA ... 40 mA, connection technology: 2-conductor, transmission speed in the local bus: 500 kbps, Extreme conditions version, degree of protection: IP20, including Inline connectors and marking fields
IB IL AI 8/SF-2MBD-PAC - Inline, Analog input terminal, Analog inputs: 8, 0 V ... 5 V, -5 V ... 5 V, 0 V ... 10 V, -10 V ... 10 V, 0 V ... 25 V, -25 V ... 25 V, 0 V ... 50 V, 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA, 0 mA ... 40 mA, -40 mA ... 40 mA, connection technology: 2-conductor, transmission speed in the local bus: 2 Mbps, degree of protection: IP20, including Inline connectors and marking fields
IB IL AI 8/IS-PAC - Inline, Analog input terminal, Analog inputs: 8, 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA, 0 mA ... 40 mA, -40 mA ... 40 mA, connection technology: 2-, 3-conductor, transmission speed in the local bus: 500 kbps, integrated sensor supply, degree of protection: IP20, including Inline connectors and marking fields
IB IL AI 4/EF-PAC - Inline, Analog input terminal, Analog inputs: 4, 0 V ... 5 V, -5 V ... 5 V, 0 V ... 10 V, -10 V ... 10 V, 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA, connection technology: 2-, 3-, 4-conductor, transmission speed in the local bus: 500 kbps, degree of protection: IP20, including Inline connectors and marking fields
IB IL AI 4/EF-XC-PAC - Inline, Analog input terminal, Analog inputs: 4, 0 V ... 5 V, -5 V ... 5 V, 0 V ... 10 V, -10 V ... 10 V, 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA, connection technology: 2-, 3-, 4-conductor, transmission speed in the local bus: 500 kbps, Extreme conditions version, degree of protection: IP20, including Inline connectors and marking fields
IB IL AI 4/EF-2MBD-PAC - Inline, Analog input terminal, Analog inputs: 4, 0 V ... 5 V, -5 V ... 5 V, 0 V ... 10 V, -10 V ... 10 V, 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA, connection technology: 2-, 3-, 4-conductor, transmission speed in the local bus: 2 Mbps, degree of protection: IP20, including Inline connectors and marking fields
IB IL AI 2/SF-PAC - Inline, Analog input terminal, Analog inputs: 2, 0 V ... 10 V, -10 V ... 10 V, 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA, connection technology: 2-conductor, transmission speed in the local bus: 500 kbps, degree of protection: IP20, including Inline connector and labeling field
IB IL AI 2/SF-ME - Inline, Analog input terminal, Analog inputs: 2, 0 V ... 10 V, -10 V ... 10 V, 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA, connection technology: 2-conductor, transmission speed in the local bus: 500 kbps, degree of protection: IP20, including Inline connector and labeling field
Inline, Analog input terminal, Analog inputs: 2, 0 V ... 10 V, -10 V ... 10 V, 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA, connection technology: 2-conductor, transmission speed in the local bus: 500 kbps, Extreme conditions version, degree of protection: IP20, including Inline connector and labeling field
IB IL AI 2/SF-230-PAC - Inline, Analog input terminal, Analog inputs: 2, 0 V ... 10 V, -10 V ... 10 V, 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA, connection technology: 2-conductor, transmission speed in the local bus: 500 kbps, 3 dB base frequency at 230 Hz, degree of protection: IP20, including Inline connector and labeling field