Series IB-IL-AI
IB IL AI 2/SF-XC-PAC - Analog module
Inline, Analog input terminal, Analog inputs: 2, 0 V ... 10 V, -10 V ... 10 V, 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA, connection technology: 2-conductor, transmission speed in the local bus: 500 kbps, Extreme conditions version, degree of protection: IP20, including Inline connector and labeling field
- 2 analog single-ended signal inputs for the connection of either voltage or current signals
- Connection of sensors in 2-conductor technology
- Current ranges: 0 mA ... 20 mA, 4 mA ... 20 mA, ±20 mA
- Voltage ranges: 0 V ... 10 V, ±10 V
- The channels are parameterized independently of one another via the bus system
- Measured values can be represented in four different formats
- Resolution depends on the representation format and the measuring range
- Process data update of both channels within a max. of 1.5 ms
- Can be used under extreme ambient conditions
- Extended temperature range of -40 °C ... +70 °C (see “Tested successfully: use under extreme ambient conditions” in the data sheet)
- Coated PCBs
Technical Specifications
Dimensions
Width | 12.2 mm |
Height | 136.8 mm |
Depth | 71.5 mm |
Note on dimensions | Housing dimensions |
Inline local bus
Number of interfaces | 2 |
Connection Method | Inline data jumper |
Transmission Speed | 500 kbps |
Module
ID code (dec.) | 127 |
ID code (hex) | 7F |
Length code (hex) | 02 |
Length code (dec) | 02 |
Process data channel | 32 bit |
Input address area | 4 Byte |
Output address area | 4 Byte |
Register length | 32 bit |
Required parameter data | 6 Byte |
Required configuration data | 4 Byte |
Analog: General
Input name | Analog inputs |
Description of the input | Single-ended inputs, voltage or current |
Number of Inputs | 2 |
A/D conversion time | typ. 120 µs (per channel) |
Connection Method | Inline shield connector |
Connection technology | 2-conductor |
Note regarding the connection technology | shielded |
Current Input Signal | 0 mA ... 20 mA |
Current Input Signal | 4 mA ... 20 mA |
Current Input Signal | -20 mA ... 20 mA |
Input resistance current input | 50 Ω (Shunt) |
Voltage input signal | 0 V ... 10 V |
Voltage input signal | -10 V ... 10 V |
Input resistance of voltage input | > 220 kΩ |
Data formats | IB IL, IB ST, IB RT, standardized representation |
Limit frequency (3 dB) | 40 Hz |
Common mode voltage range signal - ground | 40 V (Between current input and functional ground) |
Common mode voltage range signal - ground | 40 V (between voltage input and functional ground) |
Measuring Principle | Successive approximation |
Measured value resolution | 16 bits (15 bits + sign bit) |
Measured value representation | 16 bit two's complement |
Protective circuit | Surge protection; Suppressor diodes in the analog inputs |
Product properties
Product family | Inline |
Type | modular |
Scope of delivery | including Inline connector and labeling field |
Operating mode | Process data operation with 2 words |
Special Properties | Extreme conditions version |
Diagnostics messages | Failure of the internal I/O supply yes |
Diagnostics messages | I/O error Error message in the process data |
Diagnostics messages | User error Error message in the process data |
Insulation characteristics
Overvoltage category | II (IEC 60664-1, EN 60664-1) |
Pollution degree | 2 (IEC 60664-1, EN 60664-1) |
Potentials
Power consumption | typ. 662 mW |
Power consumption | max. 882 mW |
Potentials: Communications power (UL)
Supply Voltage | 7.5 V DC (via voltage jumper) |
Current draw | max. 60 mA |
Current draw | typ. 45 mA |
Potentials: Supply of analog modules (UANA)
Supply Voltage | 24 V DC (via voltage jumper) |
Supply Voltage Range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
Current draw | max. 18 mA |
Current draw | typ. 13 mA |
Electrical isolation/isolation of the voltage ranges
Test voltage: 7.5 V supply (bus logic), 24 V supply UANA / I/O | 500 V AC, 50 Hz, 1 min. |
Test voltage: 7.5 V supply (bus logic), 24 V supply UANA / functional ground | 500 V AC, 50 Hz, 1 min. |
Test voltage: I/O/functional ground | 500 V AC, 50 Hz, 1 min. |
Connection technology
Connection name | Inline connector |
Conductor connection
Connection Method | Spring-cage connection |
Conductor cross section rigid | 0.08 mm² ... 1.5 mm² |
Conductor cross section flexible | 0.08 mm² ... 1.5 mm² |
Conductor cross section AWG | 28 ... 16 |
Stripping length | 8 mm |
Inline connector
Connection Method | Spring-cage connection |
Conductor cross section, rigid | 0.08 mm² ... 1.5 mm² |
Conductor cross section, flexible | 0.08 mm² ... 1.5 mm² |
Conductor cross section AWG | 28 ... 16 |
Stripping length | 8 mm |
Ambient conditions
Ambient Temperature (Operation) | -25 °C ... 55 °C (Standard) |
Ambient Temperature (Operation) | -40 °C ... 70 °C (Extended, see section “Tested successfully: use under extreme ambient conditions” in the data sheet.) |
Degree of Protection | IP20 |
Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
Permissible humidity (storage/transport) | 10 % ... 95 % (non-condensing) |
Standards and Regulations
Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
Mounting
Mounting Type | DIN rail mounting |
Accessories
Why Proax for Phoenix Contact IB IL AI 2/SF-XC-PAC?
Proax is an authorized distributor of Phoenix Contact IB IL AI 2/SF-XC-PAC and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Alternate Names | IBILAI2SFXCPAC |
Pack Size | 1 |
Recommended
- 2861577 - Inline, Analog input terminal, Analog inputs: 2, 0 V ... 10 V, -10 V ... 10 V, 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA, connection technology: 2-conductor, transmission speed in the local bus: 500 kbps, 3 dB base frequency at 230 Hz, degree of protection: IP20, including Inline connector and labeling field
- 2701215 - Inline, Analog input terminal, Analog inputs: 4, 0 V ... 5 V, -5 V ... 5 V, 0 V ... 10 V, -10 V ... 10 V, 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA, connection technology: 2-, 3-, 4-conductor, transmission speed in the local bus: 500 kbps, Extreme conditions version, degree of protection: IP20, including Inline connectors and marking fields
- 2878447 - Inline, Analog input terminal, Analog inputs: 4, 0 V ... 5 V, -5 V ... 5 V, 0 V ... 10 V, -10 V ... 10 V, 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA, connection technology: 2-, 3-, 4-conductor, transmission speed in the local bus: 500 kbps, degree of protection: IP20, including Inline connectors and marking fields
- 2878641 - Inline, Analog input terminal, Analog inputs: 4, 0 V ... 5 V, -5 V ... 5 V, 0 V ... 10 V, -10 V ... 10 V, 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA, connection technology: 2-, 3-, 4-conductor, transmission speed in the local bus: 2 Mbps, degree of protection: IP20, including Inline connectors and marking fields
- 2701159 - Inline, Analog input terminal, Analog inputs: 8, 0 V ... 5 V, -5 V ... 5 V, 0 V ... 10 V, -10 V ... 10 V, 0 V ... 25 V, -25 V ... 25 V, 0 V ... 50 V, 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA, 0 mA ... 40 mA, -40 mA ... 40 mA, connection technology: 2-conductor, transmission speed in the local bus: 500 kbps, Extreme conditions version, degree of protection: IP20, including Inline connectors and marking fields
- 2861412 - Inline, Analog input terminal, Analog inputs: 8, 0 V ... 5 V, -5 V ... 5 V, 0 V ... 10 V, -10 V ... 10 V, 0 V ... 25 V, -25 V ... 25 V, 0 V ... 50 V, 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA, 0 mA ... 40 mA, -40 mA ... 40 mA, connection technology: 2-conductor, transmission speed in the local bus: 500 kbps, degree of protection: IP20, including Inline connectors and marking fields