Official Distributor
SKU
MPN
IB IL AI 2-HART-PAC
Weight
0.245 kg
This product is Not Cancellable/Not Returnable
Series IB-IL-AI
IB IL AI 2-HART-PAC - Analog module
Inline, Analog input terminal, Analog inputs: 2, 4 mA ... 20 mA, 0 mA ... 25 mA, connection technology: 2-conductor, transmission speed in the local bus: 500 kbps, HART functionality, HART protocol transmission, degree of protection: IP20, including Inline connectors and marking fields
- Two differential signal inputs for current sensors
- Connection of sensors in 2-conductor technology (active and passive sensors)
- Current ranges: 4 mA ... 20 mA, 0 mA ... 25 mA
- Both channels preset to the 4 mA ... 20 mA measuring range and IB IL format
- Transmission of the HART protocol with PCP
- Measured values can be represented in three different formats
- Resolution depends on the representation format and the measuring range
- Measured value acquisition with a resolution of 16 bits
- Point-to-point and multi-drop connections possible
- Connection of a hand-held operating panel possible
- A maximum of 5 HART devices can be connected per channel
- Polling and burst modes
- FDT/DTM support with AutomationXplorer+ (unavailable since 2019)
Technical Specifications
Dimensions
Width | 48.8 mm |
Height | 135 mm |
Depth | 71.5 mm |
Inline local bus
Number of interfaces | 2 |
Connection Method | Inline data jumper |
Transmission Speed | 500 kbps |
Transmission physics | Copper |
Module
ID code (dec.) | 220 |
ID code (hex) | DC |
Length code (hex) | 02 |
Length code (dec) | 02 |
Process data channel | 32 bit |
Input address area | 4 Byte |
Output address area | 4 Byte |
Register length | 64 bit |
Required parameter data | 9 Byte |
Required configuration data | 5 Byte |
Analog: General
Input name | Analog inputs |
Description of the input | Differential inputs, current |
Number of Inputs | 2 |
A/D conversion time | approx. 10 µs (bus-synchronous) |
A/D converter resolution | 16 bit |
Connection Method | Inline shield connector |
Connection technology | 2-conductor |
Note regarding the connection technology | shielded |
Current Input Signal | 4 mA ... 20 mA |
Current Input Signal | 0 mA ... 25 mA |
Input resistance current input | 250 Ω |
Data formats | IB IL, standardized representation, PIO |
Limit frequency (3 dB) | 25 Hz |
Common mode voltage range signal - ground | 40 V (Between current input and functional ground) |
Measuring Principle | Successive approximation |
Measured value resolution | 16 bits (15 bits + sign bit) |
Measured value representation | 16 bit two's complement |
Protective circuit | Surge protection; Suppressor diode |
Product properties
Product family | Inline |
Type | modular |
Scope of delivery | including Inline connectors and marking fields |
Operating mode | Process data operation with 2 words, PCP with 2 words |
Special Properties | HART functionality |
Special Properties | HART protocol transmission |
Diagnostics messages | Failure of the internal I/O supply yes |
Diagnostics messages | I/O error Error message in the process data |
Diagnostics messages | User error Error message in the process data |
Insulation characteristics
Overvoltage category | II (IEC 60664-1, EN 60664-1) |
Pollution degree | 2 (IEC 60664-1, EN 60664-1) |
Potentials
Power consumption | typ. 1.9 W |
Potentials: Communications power (UL)
Supply Voltage | 7.5 V DC (via voltage jumper) |
Current draw | max. 110 mA |
Current draw | typ. 95 mA |
Potentials: Supply of analog modules (UANA)
Supply Voltage | 24 V DC (via voltage jumper) |
Supply Voltage Range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
Current draw | max. 150 mA |
Current draw | typ. 50 mA |
Electrical isolation/isolation of the voltage ranges
Test voltage: 7.5 V supply (bus logic), 24 V supply UANA / I/O | 500 V AC, 50 Hz, 1 min. |
Test voltage: 7.5 V supply (bus logic), 24 V supply UANA / functional ground | 500 V AC, 50 Hz, 1 min. |
Test voltage: I/O/functional ground | 500 V AC, 50 Hz, 1 min. |
Connection technology
Connection name | Inline connector |
Conductor connection
Connection Method | Spring-cage connection |
Conductor cross section rigid | 0.08 mm² ... 1.5 mm² |
Conductor cross section flexible | 0.08 mm² ... 1.5 mm² |
Conductor cross section AWG | 28 ... 16 |
Stripping length | 8 mm |
Inline connector
Connection Method | Spring-cage connection |
Conductor cross section, rigid | 0.08 mm² ... 1.5 mm² |
Conductor cross section, flexible | 0.08 mm² ... 1.5 mm² |
Conductor cross section AWG | 28 ... 16 |
Stripping length | 8 mm |
Ambient conditions
Ambient Temperature (Operation) | -25 °C ... 55 °C |
Degree of Protection | IP20 |
Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Ambient temperature (storage/transport) | -25 °C ... 85 °C |
Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
Permissible humidity (storage/transport) | 10 % ... 95 % (non-condensing) |
Standards and Regulations
Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
Mounting
Mounting Type | DIN rail mounting |
Accessories
Why Proax for Phoenix Contact 2862149?
Proax is an authorized distributor of Phoenix Contact 2862149 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended
- Inline, Module d'entrée analogique, Entrées analogiques: 2, 0 V ... 10 V, -10 V ... 10 V, 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA, connectique: 2 fils, vitesse de transmission dans le bus local: 500 kBit/s, Modèle pour conditions extrêmes, indice de protection: IP20, avec Inline contacts et porte-étiquette
- 2861577 - Inline, Analog input terminal, Analog inputs: 2, 0 V ... 10 V, -10 V ... 10 V, 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA, connection technology: 2-conductor, transmission speed in the local bus: 500 kbps, 3 dB base frequency at 230 Hz, degree of protection: IP20, including Inline connector and labeling field
- 2878447 - Inline, Analog input terminal, Analog inputs: 4, 0 V ... 5 V, -5 V ... 5 V, 0 V ... 10 V, -10 V ... 10 V, 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA, connection technology: 2-, 3-, 4-conductor, transmission speed in the local bus: 500 kbps, degree of protection: IP20, including Inline connectors and marking fields
- 2701215 - Inline, Analog input terminal, Analog inputs: 4, 0 V ... 5 V, -5 V ... 5 V, 0 V ... 10 V, -10 V ... 10 V, 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA, connection technology: 2-, 3-, 4-conductor, transmission speed in the local bus: 500 kbps, Extreme conditions version, degree of protection: IP20, including Inline connectors and marking fields
- 2878641 - Inline, Analog input terminal, Analog inputs: 4, 0 V ... 5 V, -5 V ... 5 V, 0 V ... 10 V, -10 V ... 10 V, 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA, connection technology: 2-, 3-, 4-conductor, transmission speed in the local bus: 2 Mbps, degree of protection: IP20, including Inline connectors and marking fields
- 2861661 - Inline, Analog input terminal, Analog inputs: 8, 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA, 0 mA ... 40 mA, -40 mA ... 40 mA, connection technology: 2-, 3-conductor, transmission speed in the local bus: 500 kbps, integrated sensor supply, degree of protection: IP20, including Inline connectors and marking fields