2702495
SKU
PHX2702495
MPN
IB IL AI 4/I/4-20-ECO
Weight
0.085 kg
Series IB-IL-AI
IB IL AI 4/I/4-20-ECO - Analog module
Inline, Analog input terminal, Analog inputs: 4, 4 mA ... 20 mA, connection technology: 2-conductor, transmission speed in the local bus: 500 kbps, degree of protection: IP20, including Inline connector
- 4 analog input channels
- Connection of sensors in 2-conductor technology
- Current range: 4 mA ... 20 mA
- Data format: standardized representation
- Resolution: 12 bits
- Diagnostic indicator
Technical Specifications
Dimensions
| Width | 12.2 mm |
| Height | 119.8 mm |
| Depth | 71.5 mm |
Inline local bus
| Number of interfaces | 2 |
| Connection Method | Inline data jumper |
| Transmission Speed | 500 kbps |
Module
| ID code (dec.) | 126 |
| ID code (hex) | 7E |
| Length code (hex) | 04 |
| Length code (dec) | 04 |
| Process data channel | 64 bit |
| Input address area | 8 Byte |
| Output address area | 0 Byte |
| Register length | 64 bit |
| Required parameter data | 1 Byte |
| Required configuration data | 4 Byte |
Analog: General
| Input name | Analog inputs |
| Description of the input | Single-ended inputs, current |
| Number of Inputs | 4 |
| A/D converter resolution | 12 bit |
| Connection Method | Inline connector |
| Connection technology | 2-conductor |
| Note regarding the connection technology | shielded, twisted pair |
| Current Input Signal | 4 mA ... 20 mA |
| Input resistance current input | 200 Ω |
| Data formats | Standardized representation |
| Measured value representation | 16 bits |
| Protective circuit | Overload protection; max. ±10 V DC, corresponds to max. ±50 mA through the shunts |
| Protective circuit | Transient protection; Suppressor diode |
Product properties
| Product family | Inline |
| Type | modular |
| Scope of delivery | including Inline connector |
| Diagnostics messages | Failure of the internal I/O supply I/O error message sent to the bus coupler |
| Diagnostics messages | Checksum error I/O error message sent to the bus coupler |
Potentials
| Power consumption | typ. 0.8 W |
| Power consumption | max. 0.9 W |
Potentials: Communications power (UL)
| Supply Voltage | 7.5 V DC (via voltage jumper) |
| Current draw | max. 70 mA |
| Current draw | typ. 60 mA |
Potentials: Supply of analog modules (UANA)
| Supply Voltage | 24 V DC (via voltage jumper) |
| Supply Voltage Range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Current draw | max. 20 mA |
| Current draw | typ. 15 mA |
Electrical isolation/isolation of the voltage ranges
| Test voltage: Bus logic (local bus, communications power) | 500 V AC, 50 Hz, 1 min. |
| Test voltage: Analog I/O | 500 V AC, 50 Hz, 1 min. |
| Test voltage: Functional ground | 500 V AC, 50 Hz, 1 min. |
Connection technology
| Connection name | Inline connector |
Conductor connection
| Connection Method | Spring-cage connection |
| Conductor cross section rigid | 0.08 mm² ... 1.5 mm² |
| Conductor cross section flexible | 0.08 mm² ... 1.5 mm² |
| Conductor cross section AWG | 28 ... 16 |
| Stripping length | 8 mm |
Inline connector
| Connection Method | Spring-cage connection |
| Conductor cross section, rigid | 0.08 mm² ... 1.5 mm² |
| Conductor cross section, flexible | 0.08 mm² ... 1.5 mm² |
| Conductor cross section AWG | 28 ... 16 |
| Stripping length | 8 mm |
Ambient conditions
| Ambient Temperature (Operation) | 0 °C ... 55 °C |
| Degree of Protection | IP20 |
| Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Ambient temperature (storage/transport) | -25 °C ... 85 °C |
| Permissible humidity (operation) | 10 % ... 95 % (according to DIN EN 61131-2) |
| Permissible humidity (storage/transport) | 10 % ... 95 % (according to DIN EN 61131-2) |
Standards and Regulations
| Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
Mounting
| Mounting Type | DIN rail mounting |
Accessories
Why Proax for Phoenix Contact 2702495?
Proax is an authorized distributor of Phoenix Contact 2702495 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
| Pack Size | 1 |
Recommended
IB IL AI 4/EF-2MBD-PAC - Inline, Analog input terminal, Analog inputs: 4, 0 V ... 5 V, -5 V ... 5 V, 0 V ... 10 V, -10 V ... 10 V, 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA, connection technology: 2-, 3-, 4-conductor, transmission speed in the local bus: 2 Mbps, degree of protection: IP20, including Inline connectors and marking fields
IB IL AI 4/EF-PAC - Inline, Analog input terminal, Analog inputs: 4, 0 V ... 5 V, -5 V ... 5 V, 0 V ... 10 V, -10 V ... 10 V, 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA, connection technology: 2-, 3-, 4-conductor, transmission speed in the local bus: 500 kbps, degree of protection: IP20, including Inline connectors and marking fields
IB IL AI 4/EF-XC-PAC - Inline, Analog input terminal, Analog inputs: 4, 0 V ... 5 V, -5 V ... 5 V, 0 V ... 10 V, -10 V ... 10 V, 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA, connection technology: 2-, 3-, 4-conductor, transmission speed in the local bus: 500 kbps, Extreme conditions version, degree of protection: IP20, including Inline connectors and marking fields
IB IL AI 2/SF-230-PAC - Inline, Analog input terminal, Analog inputs: 2, 0 V ... 10 V, -10 V ... 10 V, 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA, connection technology: 2-conductor, transmission speed in the local bus: 500 kbps, 3 dB base frequency at 230 Hz, degree of protection: IP20, including Inline connector and labeling field
IB IL AI 2/SF-ME - Inline, Analog input terminal, Analog inputs: 2, 0 V ... 10 V, -10 V ... 10 V, 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA, connection technology: 2-conductor, transmission speed in the local bus: 500 kbps, degree of protection: IP20, including Inline connector and labeling field
IB IL AI 2/SF-PAC - Inline, Analog input terminal, Analog inputs: 2, 0 V ... 10 V, -10 V ... 10 V, 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA, connection technology: 2-conductor, transmission speed in the local bus: 500 kbps, degree of protection: IP20, including Inline connector and labeling field
Inline, Analog input terminal, Analog inputs: 2, 0 V ... 10 V, -10 V ... 10 V, 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA, connection technology: 2-conductor, transmission speed in the local bus: 500 kbps, Extreme conditions version, degree of protection: IP20, including Inline connector and labeling field
IB IL AI 2-HART-PAC - Inline, Analog input terminal, Analog inputs: 2, 4 mA ... 20 mA, 0 mA ... 25 mA, connection technology: 2-conductor, transmission speed in the local bus: 500 kbps, HART functionality, HART protocol transmission, degree of protection: IP20, including Inline connectors and marking fields
IB IL AI 2/4-20-PAC - Inline, Analog input terminal, Analog inputs: 2, 0 V ... 10 V, -10 V ... 10 V, 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA, connection technology: 2-conductor, transmission speed in the local bus: 500 kbps, degree of protection: IP20, including Inline connector and labeling field
IB IL AI 8/IS-PAC - Inline, Analog input terminal, Analog inputs: 8, 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA, 0 mA ... 40 mA, -40 mA ... 40 mA, connection technology: 2-, 3-conductor, transmission speed in the local bus: 500 kbps, integrated sensor supply, degree of protection: IP20, including Inline connectors and marking fields