IB IL AI 8/SF-2MBD-PAC - Analog module

Inline, Analog input terminal, Analog inputs: 8, 0 V ... 5 V, -5 V ... 5 V, 0 V ... 10 V, -10 V ... 10 V, 0 V ... 25 V, -25 V ... 25 V, 0 V ... 50 V, 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA, 0 mA ... 40 mA, -40 mA ... 40 mA, connection technology: 2-conductor, transmission speed in the local bus: 2 Mbps, degree of protection: IP20, including Inline connectors and marking fields

  • 8 analog single-ended signal inputs for the connection of either voltage or current signals
  • Connection of sensors in 2-conductor technology
  • Current ranges: 0 mA ... 20 mA, 4 mA ... 20 mA, ±20 mA, 0 mA ... 40 mA, ±40 mA
  • Voltage ranges: 0 V ... 5 V, ±5 V, 0 V ... 10 V, ±10 V, 0 V ... 25 V, ±25 V, 0 V ... 50 V
  • The channels are parameterized independently of one another via the bus system
  • Measured values can be represented in five different formats
  • 16-bit analog-to-digital converter
  • Process data multiplex mode
  • High measuring accuracy
Technical Specifications

Dimensions

Width48.8 mm
Height136.8 mm
Depth71.5 mm
Note on dimensionsHousing dimensions

Utilization restriction

EMC noteEMC: class A product, see manufacturer's declaration in the download area

Inline local bus

Connection MethodInline data jumper
Transmission Speed2 Mbps
Transmission physicsCopper

Module

ID code (dec.)95
ID code (hex)5F
Length code (hex)02
Length code (dec)02
Process data channel32 bit
Input address area4 Byte
Output address area4 Byte
Register length32 bit
Required parameter data 6 Byte
Required configuration data 5 Byte

Analog: General

Input nameAnalog inputs
Description of the inputSingle-ended inputs, voltage or current
Number of Inputs8
A/D conversion timeapprox. 10 µs
A/D converter resolution16 bit
Connection MethodInline shield connector
Connection technology2-conductor
Note regarding the connection technologyshielded
Current Input Signal0 mA ... 20 mA
Current Input Signal4 mA ... 20 mA
Current Input Signal-20 mA ... 20 mA
Current Input Signal0 mA ... 40 mA
Current Input Signal-40 mA ... 40 mA
Input resistance current input25 Ω ±0.01 % (Shunt)
Voltage input signal0 V ... 5 V
Voltage input signal-5 V ... 5 V
Voltage input signal0 V ... 10 V
Voltage input signal-10 V ... 10 V
Voltage input signal0 V ... 25 V
Voltage input signal-25 V ... 25 V
Voltage input signal0 V ... 50 V
Input resistance of voltage input> 240 kΩ ±0.01 %
Data formatsIB IL, IB ST, IB RT, standardized representation, PIO format
Limit frequency (3 dB)3.5 kHz
Measuring PrincipleSuccessive approximation
Measured value resolution16 bits (15 bits + sign bit)
Measured value representation16 bit two's complement

Product properties

Product familyInline
Typemodular
Scope of deliveryincluding Inline connectors and marking fields

Insulation characteristics

Overvoltage categoryII (IEC 60664-1, EN 60664-1)
Pollution degree2 (IEC 60664-1, EN 60664-1)

Potentials

Power consumptiontyp. 1086 mW (entire device)

Potentials: Communications power (UL)

Supply Voltage7.5 V DC (via voltage jumper)
Current drawmax. 85 mA
Current drawtyp. 68 mA

Potentials: Supply of analog modules (UANA)

Supply Voltage24 V DC (via voltage jumper)
Supply Voltage Range19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current drawmax. 38 mA
Current drawtyp. 24 mA

Electrical isolation/isolation of the voltage ranges

Test voltage: 5 V supply, incoming remote bus/7.5 V supply (bus logics)500 V AC, 50 Hz, 1 min.
Test voltage: 5 V supply, outgoing remote bus/7.5 V supply (bus logics)500 V AC, 50 Hz, 1 min.
Test voltage: 7.5 V supply (bus logic), 24 V supply UANA / I/O500 V AC, 50 Hz, 1 min.
Test voltage: 7.5 V supply (bus logic), 24 V supply UANA / functional ground500 V AC, 50 Hz, 1 min.
Test voltage: I/O/functional ground500 V AC, 50 Hz, 1 min.

Connection technology

Connection nameInline connector

Conductor connection

Connection MethodSpring-cage connection
Conductor cross section rigid0.08 mm² ... 1.5 mm²
Conductor cross section flexible0.08 mm² ... 1.5 mm²
Conductor cross section AWG28 ... 16
Stripping length8 mm

Inline connector

Connection MethodSpring-cage connection
Conductor cross section, rigid0.08 mm² ... 1.5 mm²
Conductor cross section, flexible0.08 mm² ... 1.5 mm²
Conductor cross section AWG28 ... 16
Stripping length8 mm

Ambient conditions

Ambient Temperature (Operation)-25 °C ... 55 °C
Degree of ProtectionIP20
Air pressure (operation)70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)70 kPa ... 106 kPa (up to 3000 m above sea level)
Ambient temperature (storage/transport)-25 °C ... 85 °C
Permissible humidity (operation)10 % ... 95 % (non-condensing)
Permissible humidity (storage/transport)10 % ... 95 % (non-condensing)

Standards and Regulations

Protection classIII (IEC 61140, EN 61140, VDE 0140-1)

Mounting

Mounting TypeDIN rail mounting

Why Proax for Phoenix Contact 2862042?

Proax is an authorized distributor of Phoenix Contact 2862042 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information

Pack Size1
Recommended

Available for order

Phoenix Contact Availability