Official Distributor
SKU
MPN
AXL F CNT2 INC2 1F
Weight
0.254 kg
This product is Not Cancellable/Not Returnable
Series AXL-F-CNT2
AXL F CNT2 INC2 1F - Function module
Axioline F, Function module, Counter inputs: 2, Incremental encoder inputs: 2, Symmetrical and asymmetrical encoders, Digital inputs: 8, 24 V DC, Digital outputs: 2, 24 V DC, transmission speed in the local bus: 100 Mbps, degree of protection: IP20, including bus base module and Axioline F connectors
- 2 channels, selectable for each channel: counter function or position detection using incremental encoder
- Maximum input frequency: 300 kHz (one channel wired) or 100 kHz (both channels wired)
- 32-bit counter (up and down)
- Output control according to two limit values
- Counter: counting (source) is controlled via a control input (gate)
- Counter: single or periodic counting
- Incremental encoder acquisition: Acquisition of digital signals from symmetrical and asymmetrical incremental encoders
- Incremental encoder acquisition: evaluation of linear or rotary axes
- Device rating plate stored
Technical Specifications
Dimensions
Width | 53.6 mm |
Height | 126.1 mm |
Depth | 54 mm |
Note on dimensions | The depth applies when a TH 35-7.5 DIN rail is used (in accordance with EN 60715). |
Axioline F local bus
Number of interfaces | 2 |
Connection Method | Bus base module |
Transmission Speed | 100 Mbps |
Module
ID code (hex) | none |
Input address area | 28 Byte |
Output address area | 28 Byte |
Required parameter data | 115 Byte |
Required configuration data | 7 Byte |
Digital:
Input name | Digital inputs |
Description of the input | EN 61131-2, type 3 |
Number of Inputs | 8 (CNT: G1, G2, Dir1, Dir2; INC: Ref1, Ref2, L1, L2) |
Connection Method | Push-in connection |
Connection technology | 1-conductor (optional 2, 3-conductor) |
Input voltage range "0" signal | -3 V DC ... 5 V DC |
Input voltage range "1" signal | 11 V DC ... 30 V DC |
Nominal input voltage UIN | 24 V DC |
Nominal input current at UIN | 2.5 mA (per channel) |
Encoder
Number of Inputs | 2 (A1, /A1, B1, /B1, Z1, /Z1; A2, /A2, B2, /B2, Z2, /Z2) |
Input name | Incremental encoder inputs |
Encoder signals | Symmetrical and asymmetrical encoders |
Cable Length | max. 30 m |
Counter:
Input name | Counter inputs |
Description of the input | EN 61131-2, type 3 |
Connection Method | Push-in connection |
Number of Inputs | 2 (S1, S2) |
Input Voltage | 24 V DC |
Input voltage range "0" signal | -3 V DC ... 5 V DC |
Input voltage range "1" signal | 11 V DC ... 30 V DC |
Input Frequency | max. 300 kHz (1 channel wired) |
Input Frequency | max. 100 kHz (more than one channel wired or Z signal monitoring via the firmware) |
Input Current | 2.5 mA (per channel) |
Resolution | 32 bits |
Permissible cable length | max. 30 m |
Digital:
Output name | Digital outputs |
Connection Method | Push-in connection |
Connection technology | 1-conductor |
Number of Outputs | 2 (Out1, Out2) |
Protective circuit | Short-circuit protection |
Protective circuit | Overload protection |
Output Voltage | 24 V DC |
Maximum Output Current per channel | 500 mA |
Nominal Output Voltage | 24 V DC |
Nominal load, inductive | max. 12 VA (1.2 H, 48 Ω, with nominal voltage) |
Nominal load, lamp | max. 12 W (at nominal voltage) |
Nominal load, ohmic | max. 12 W (48 Ω, with nominal voltage) |
Product properties
Product family | Axioline F |
Type | block modular |
Mounting Position | any (no temperature derating) |
Scope of delivery | including bus base module and Axioline F connectors |
Insulation characteristics
Overvoltage category | II (IEC 60664-1, EN 60664-1) |
Pollution degree | 2 (IEC 60664-1, EN 60664-1) |
Electrical properties
Maximum power dissipation for nominal condition | 0.6 W |
Encoder
Number | 2 (UE1, UE2) |
Nominal Output Voltage | 5 V DC |
Voltage range | 5 V DC ... 5.5 V DC |
Current carrying capacity | max. 250 mA |
Protective circuit | Short-circuit protection; electronic |
Number | 2 (US1, US2) |
Nominal Output Voltage | 24 V DC |
Voltage range | 19.2 V DC ... 30 V DC |
Current carrying capacity | typ. 500 mA |
Protective circuit | Short-circuit protection; electronic |
Number | max. 2 (A, /A, B, /B, (Z, /Z)) |
Designation | Symmetrical incremental encoders |
Type of connection of signals | Push-in connection |
Encoder supply voltage | 5 V DC |
Encoder supply voltage | 24 V DC |
Signal voltage level | Differential signal (signal – inverted signal) ±0.5 V, minimum; ±6 V, maximum |
Common mode voltage range signal - ground | -10 V ... 13.2 V |
Input Frequency | max. 300 kHz (1 channel wired) |
Input Frequency | max. 100 kHz (more than one channel wired or Z signal monitoring via the firmware) |
Number | max. 2 (A, B, (Z)) |
Designation | Asymmetrical incremental encoder |
Type of connection of signals | Push-in connection |
Signal voltage level | Low ≤ 2.5 V, high ≥ 3.5 V (up to 27 V, maximum) |
Input Frequency | max. 300 kHz (1 channel wired) |
Input Frequency | max. 100 kHz (more than one channel wired or Z signal monitoring via the firmware) |
Potentials: Axioline F local bus supply (UBus)
Supply Voltage | 5 V DC (via bus base module) |
Current draw | max. 120 mA |
Current draw | typ. 100 mA |
Power consumption | max. 0.6 W |
Power consumption | typ. 0.5 W |
Potentials: Feed-in of supply voltage (UI)
Supply Voltage | 24 V DC |
Supply Voltage Range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
Current draw | max. 2.5 A (dependent on the encoder or sensor type used and the load on the digital output.) |
Power consumption | max. 60 W (of which 1.6 W internal losses) |
Protective circuit | Surge protection; electronic (35 V, 0.5 s) |
Protective circuit | Reverse polarity protection; parallel diode; with external 5 A fuse (only for commissioning) |
Electrical isolation/isolation of the voltage ranges
Test voltage: 5 V supply of the local bus (UBus) / 24 V supply (I/Os) | 500 V AC, 50 Hz, 1 min. |
Test voltage: 5 V supply of the local bus (UBus) / functional ground | 500 V AC, 50 Hz, 1 min. |
Test voltage: 24 V supply (I/O) / functional ground | 500 V AC, 50 Hz, 1 min. |
Connection technology
Connection name | Axioline F connector |
Note on the connection method | Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual. |
Conductor connection
Connection Method | Push-in connection |
Conductor cross section rigid | 0.2 mm² ... 1.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 1.5 mm² |
Conductor cross section AWG | 24 ... 16 |
Stripping length | 8 mm |
Axioline F connector
Connection Method | Push-in connection |
Note on the connection method | Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual. |
Conductor cross section, rigid | 0.2 mm² ... 1.5 mm² |
Conductor cross section, flexible | 0.2 mm² ... 1.5 mm² |
Conductor cross section AWG | 24 ... 16 |
Stripping length | 8 mm |
Ambient conditions
Ambient Temperature (Operation) | -25 °C ... 60 °C |
Degree of Protection | IP20 |
Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
Permissible humidity (storage/transport) | 5 % ... 95 % (non-condensing) |
Standards and Regulations
Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
Mounting
Mounting Type | DIN rail mounting |
Mounting Position | any (no temperature derating) |
Accessories
Why Proax for Phoenix Contact 2688093?
Proax is an authorized distributor of Phoenix Contact 2688093 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended
- 2701239 - Axioline F, Function module, Counter inputs: 2, Incremental encoder inputs: 2, Symmetrical and asymmetrical encoders, Digital inputs: 8, 24 V DC, Digital outputs: 2, 24 V DC, Extreme conditions version, transmission speed in the local bus: 100 Mbps, degree of protection: IP20, including bus base module and Axioline F connectors
- 2701916 - Axioline F, Digital I/O module, Digital inputs: 8, 24 V DC, connection technology: 1-conductor, Digital outputs: 8, 24 V DC, 500 mA, connection technology: 1-conductor, transmission speed in the local bus: 100 Mbps, degree of protection: IP20, including bus base module and Axioline F connectors
- 2702017 - Axioline F, Digital I/O module, Digital inputs: 8, 24 V DC, connection technology: 1-conductor, Digital outputs: 8, 24 V DC, 500 mA, connection technology: 1-conductor, Extreme conditions version, transmission speed in the local bus: 100 Mbps, degree of protection: IP20, including bus base module and Axioline F connectors
- 2702071 - Axioline F, Digital I/O module, Digital inputs: 8, 24 V DC, connection technology: 3-conductor, Digital outputs: 8, 24 V DC, 500 mA, connection technology: 3-conductor, transmission speed in the local bus: 100 Mbps, degree of protection: IP20, including bus base module and Axioline F connectors