Official Distributor
SKU
Weight
0.239 kg
This product is Not Cancellable/Not Returnable
Series AXL-F-DO
AXL F DO4/3 AC 1F - Digital module
Axioline F, Digital output module, Digital outputs: 4 (Triac outputs with zero voltage switch), 230 V AC, 2 A, connection technology: 3-conductor, transmission speed in the local bus: 100 Mbps, degree of protection: IP20, including bus base module and Axioline F connectors
- 4 digital outputs
- Connection of actuators in 2- and 3-conductor technology
- Device rating plate stored
- Diagnostic and status indicators
Technical Specifications
Dimensions
Width | 53.6 mm |
Height | 126.1 mm |
Depth | 54 mm |
Note on dimensions | The depth applies when a TH 35-7.5 DIN rail is used (in accordance with EN 60715). |
Axioline F local bus
Number of interfaces | 2 |
Connection Method | Bus base module |
Transmission Speed | 100 Mbps |
Module
Input address area | 0 Byte |
Output address area | 1 Byte |
Required parameter data | 1 Byte |
Required configuration data | 6 Byte |
Digital:
Output name | Digital outputs |
Connection Method | Push-in connection |
Connection technology | 3-conductor |
Number of Outputs | 4 (Triac outputs with zero voltage switch) |
Protective circuit | External protection required; I2t-value (a half-wave): 340 A2s |
Output Voltage | 230 V AC |
Maximum Output Current per module | 8 A (provide external protection) |
Nominal Output Voltage | 230 V AC |
Output voltage range | 24 V AC ... 230 V AC -20 % / +15 % (50/60 Hz) |
Load min. | 5.1 kΩ (at 230 V) |
Output voltage when switched off | see diagram |
Nominal load, ohmic | max. 460 W (at nominal voltage) |
Switching frequency | max. 100 per second (with ohmic load) |
Reverse voltage resistance to short pulses | Reverse voltage proof |
Behavior with overload | Output may be damaged |
Signal delay | max. 10 ms (at 50 Hz) |
Product properties
Product family | Axioline F |
Type | block modular |
Mounting Position | any (observe temperature and current derating) |
Scope of delivery | including bus base module and Axioline F connectors |
Potentials: Axioline F local bus supply (UBus)
Supply Voltage | 5 V DC (via bus base module) |
Current draw | max. 120 mA |
Power consumption | max. 600 mW |
Potentials: Supply for digital output modules (UO)
Supply Voltage | 230 V AC |
Supply Voltage Range | 12 V AC ... 253 V AC (including all tolerances, including ripple, 50 ... 60 Hz) |
Current draw | max. 8 A (provide external protection) |
Power consumption | max. 2024 VA (of which 8 VA internal losses) |
Protective circuit | Surge protection; Varistor 275 V |
Electrical isolation/isolation of the voltage ranges
Test voltage: I/Os / logic | 4 kV |
Test voltage: I/Os / logic | 5 kV |
Test voltage: I/O/functional ground | 4 kV |
Test voltage: I/O/functional ground | 5 kV |
Test voltage: I/O area AC / PE | 4 kV |
Connection technology
Connection name | Axioline F connector |
Note on the connection method | Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual.When selecting the cables, please note that in the case of a small conductor cross section and high current, the terminal point temperature may be up to 30 K above the ambient temperature. |
Conductor connection
Connection Method | Push-in connection |
Conductor cross section rigid | 0.5 mm² ... 1.5 mm² |
Conductor cross section flexible | 0.5 mm² ... 1.5 mm² |
Conductor cross section AWG | 20 ... 16 |
Stripping length | 8 mm |
Axioline F connector
Connection Method | Push-in connection |
Note on the connection method | Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual.When selecting the cables, please note that in the case of a small conductor cross section and high current, the terminal point temperature may be up to 30 K above the ambient temperature. |
Conductor cross section, rigid | 0.5 mm² ... 1.5 mm² |
Conductor cross section, flexible | 0.5 mm² ... 1.5 mm² |
Conductor cross section AWG | 20 ... 16 |
Stripping length | 8 mm |
Ambient conditions
Ambient Temperature (Operation) | -25 °C ... 60 °C (max. 2 A/channel for wall mounting on horizontal DIN rail; max. 1 A/channel for any mounting position) |
Ambient Temperature (Operation) | -25 °C ... 50 °C (max. 2 A/channel for any mounting position) |
Degree of Protection | IP20 |
Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
Permissible humidity (storage/transport) | 5 % ... 95 % (non-condensing) |
Mounting
Mounting Type | DIN rail mounting |
Mounting Position | any (observe temperature and current derating) |
Accessories
Why Proax for Phoenix Contact 2702068?
Proax is an authorized distributor of Phoenix Contact 2702068 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended
- 2702071 - Axioline F, Digital I/O module, Digital inputs: 8, 24 V DC, connection technology: 3-conductor, Digital outputs: 8, 24 V DC, 500 mA, connection technology: 3-conductor, transmission speed in the local bus: 100 Mbps, degree of protection: IP20, including bus base module and Axioline F connectors