SKU
MPN
AXL F DO32/1 1F
Weight
0.236 kg
Series AXL-F-DO

AXL F DO32/1 1F - Digital module

Axioline F, Digital output module, Digital outputs: 32, 24 V DC, 500 mA, connection technology: 1-conductor, transmission speed in the local bus: 100 Mbps, degree of protection: IP20, including bus base module and Axioline F connectors

  • 32 digital outputs
  • 24 V DC, 500 mA
  • Connection of actuators in 1-conductor technology
  • Minimum update time of < 100 μs
  • Device rating plate stored
Technical Specifications

Dimensions

Width53.6 mm
Height126.1 mm
Depth54 mm
Note on dimensionsThe depth applies when a TH 35-7.5 DIN rail is used (in accordance with EN 60715).

Axioline F local bus

Number of interfaces2
Connection MethodBus base module
Transmission Speed100 Mbps

Module

Input address area0 Byte
Output address area4 Byte
Required parameter data 1 Byte
Required configuration data 6 Byte

Digital:

Output nameDigital outputs
Connection MethodPush-in connection
Connection technology1-conductor
Number of Outputs32
Protective circuitShort-circuit protection, overload protection of the outputs; electronic
Output Voltage24 V DC
Limitation of the voltage induced on circuit interruption-32.8 V ... -15 V
Maximum Output Current per module8 A (up to HW 04, provide external protection)
Maximum Output Current per module16 A (from HW 05, provide external protection)
Nominal Output Voltage24 V DC
Load min.10 kΩ
Output voltage when switched offmax. 1 V
Output current when switched offmax. 300 µA
Nominal load, inductivemax. 12 VA (1.2 H, 48 Ω, with nominal voltage)
Nominal load, lampmax. 12 W (at nominal voltage)
Nominal load, ohmicmax. 12 W (48 Ω, with nominal voltage)
Switching frequencymax. 5500 per second (with ohmic load)
Switching frequencymax. 1 per second (with inductive load)
Switching frequencymax. 16 per second (with nominal lamp load)
Reverse voltage resistance to short pulseslimited protection up to 0.5 A for 1 s
Behavior with overloadShutdown with automatic restart
Behavior with inductive overloadOutput can be destroyed
Signal delaymax. 150 µs (when switched on)
Signal delaymax. 200 µs (during switching off with ohmic nominal load)
Overcurrent shut-downas of 0.7 A
Output current with ground connection interrupt when switched off< 1 mA

Product properties

Product familyAxioline F
Typeblock modular
Mounting Positionany (no temperature derating)
Scope of deliveryincluding bus base module and Axioline F connectors

Insulation characteristics

Overvoltage categoryII (IEC 60664-1, EN 60664-1)
Pollution degree2 (IEC 60664-1, EN 60664-1)

Electrical properties

Maximum power dissipation for nominal condition2.7 W

Potentials: Axioline F local bus supply (UBus)

Supply Voltage5 V DC (via bus base module)
Current drawmax. 120 mA (up to HW 04)
Current drawmax. 60 mA (from HW 05)
Power consumptionmax. 600 mW (up to HW 04)
Power consumptionmax. 300 mW (from HW 05)

Potentials: Supply for digital output modules (UO)

Supply Voltage24 V DC
Supply Voltage Range19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current drawmax. 8 A (up to HW 04, provide external protection)
Current drawmax. 16 A (from HW 05, provide external protection; if the total current of 8 A is exceeded, connect the supply at the power connector parallel via both terminal points.)
Power consumptionmax. 240 W (up to HW 04, of which 1.5 W constitute internal losses)
Power consumptionmax. 480 W (from HW 05, of which max. 2.4 W constitute internal losses)
Protective circuitSurge protection; electronic (35 V, 0.5 s)
Protective circuitReverse polarity protection; parallel diode; with external 5 A fuse (only for commissioning)

Electrical isolation/isolation of the voltage ranges

Test voltage: 5 V supply of the local bus (UBus) / 24 V supply (I/Os)500 V AC, 50 Hz, 1 min.
Test voltage: 5 V supply of the local bus (UBus) / functional ground500 V AC, 50 Hz, 1 min.
Test voltage: 24 V supply (I/O) / functional ground500 V AC, 50 Hz, 1 min.

Connection technology

Connection nameAxioline F connector
Note on the connection methodPlease observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual.

Conductor connection

Connection MethodPush-in connection
Conductor cross section rigid0.2 mm² ... 1.5 mm²
Conductor cross section flexible0.2 mm² ... 1.5 mm²
Conductor cross section AWG24 ... 16
Stripping length8 mm

Axioline F connector

Connection MethodPush-in connection
Note on the connection methodPlease observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual.
Conductor cross section, rigid0.2 mm² ... 1.5 mm²
Conductor cross section, flexible0.2 mm² ... 1.5 mm²
Conductor cross section AWG24 ... 16
Stripping length8 mm

Ambient conditions

Ambient Temperature (Operation)-25 °C ... 60 °C
Degree of ProtectionIP20
Air pressure (operation)70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)70 kPa ... 106 kPa (up to 3000 m above sea level)
Ambient temperature (storage/transport)-40 °C ... 85 °C
Permissible humidity (operation)5 % ... 95 % (non-condensing)
Permissible humidity (storage/transport)5 % ... 95 % (non-condensing)

Standards and Regulations

Protection classIII (IEC 61140, EN 61140, VDE 0140-1)

Mounting

Mounting TypeDIN rail mounting
Mounting Positionany (no temperature derating)
Accessories

Why Proax for Phoenix Contact 2688051?

Proax is an authorized distributor of Phoenix Contact 2688051 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information

Pack Size1
Recommended

Not in stock

Request lead time or order—we'll ensure quick delivery

Phoenix Contact Availability