Series PSI-MOS-DNET-FO
PSI-MOS-DNET/FO 850 T - FO converters
Fiber optic converter with integrated optical diagnostics, for DeviceNet™, CAN, CANopen® up to 1000 kbps, T-coupler, interfaces: 1 x CAN, 1 x Alarm, 2 x FO (B-FOC), 850 nm, for PCF/fiberglass (multi-mode)
- Data rates of up to 1 Mbps
- Supply voltage and data signals routed through the DIN rail connectors
- Can be combined with PSI-MOS FO converters in a modular way thanks to DIN rail connectors
- Automatic data rate detection or fixed data rate setting via DIP switches
- Integrated optical diagnostics for continuous monitoring of FO paths
- High-quality electrical isolation between all interfaces (DeviceNet // fiber optic ports // power supply // DIN rail connector)
- Connections can be plugged in via a COMBICON screw terminal block
- Redundant power supply possible by means of optional system power supply unit
- Floating switch contact for advance warning of critical FO paths
Technical Specifications
Utilization restriction
EMC note | EMC: class A product, see manufacturer's declaration in the download area |
CCCex note | Use in potentially explosive areas is not permitted in China. |
Product properties
MTTF | 543 Years (SN 29500 standard, temperature 25°C, operating cycle 21%) |
MTTF | 247 Years (SN 29500 standard, temperature 40°C, operating cycle 34.25%) |
MTTF | 102 Years (SN 29500 standard, temperature 40°C, operating cycle 100%) |
MTBF | 400 Years (Telcordia standard, 25°C temperature, 21% operating cycle (5 days a week, 8 hours a day)) |
MTBF | 64 Years (Telcordia standard, 40°C temperature, 34.25% operating cycle (5 days a week, 12 hours a day)) |
Electrical properties
Electrical isolation | VCC // CAN |
Maximum power dissipation for nominal condition | 3.6 W |
Test voltage data interface/power supply | 1.5 kVrms (50 Hz, 1 min.) |
Supply
Supply Voltage Range | 11 V DC ... 30 V DC (via pluggable COMBICON screw terminal block) |
Nominal Supply Voltage | 24 V DC |
Typical current consumption | 180 mA (24 V DC) |
Max. current consumption | ≤ 2 A (For operation in a joining station, via the DIN rail connector) |
Function
Status and diagnostic indicators | LEDs: VCC (supply voltage), NET (Mod/Net status), FO signal (fiber optic signal quality), ERR (broken fiber, fiber optic) |
Switching
Output name | Relay output |
Number of Outputs | 1 |
Contact switching type | N/O contact |
Minimum Switching Voltage | 11 V DC |
Maximum Switching Voltage | 30 V DC |
Supply
Tightening torque | 0.56 Nm ... 0.79 Nm |
Interfaces
Bit distortion, input | ± 35 % (permitted) |
Bit distortion, output | < 6.25 % |
Signal | CAN |
Signal | CANopen® |
Signal | DeviceNet™ |
Data: optical FO
No. of channels | 2 |
Transmit capacity, minimum | -17.6 dBm (50/125 µm) |
Transmit capacity, minimum | -14.6 dBm (62,5/125 µm) |
Transmit capacity, minimum | -4 dBm (200/230 µm) |
Transmission protocol | Protocol transparent for CAN interface |
Connection Method | B-FOC (ST®) |
Wavelength | 850 nm |
Minimum receiver sensitivity | -29 dBm (50/125 µm) |
Minimum receiver sensitivity | -29 dBm (62,5/125 µm) |
Minimum receiver sensitivity | -28.1 dBm (200/230 µm) |
Transmission medium | PCF fiber |
Transmission medium | Multi-mode fiberglass |
Data: CAN interface, in accordance with ISO/IS 11898 for DeviceNet™, CAN, CANopen®
Transmission Speed | ≤ 1 Mbps (Configurable via DIP switches) |
Connection Method | COMBICON plug-in screw terminal block |
No. of channels | 2 (CAN_High / CAN_Low) |
Transmission length | ≤ 5000 m (Dependent on the data rate and the protocol used) |
Number of bus devices | ≤ 64 (per potential segment) |
Number of bus devices | ≤ 63 (DeviceNet™, can be addressed logically) |
Number of bus devices | ≤ 128 (CANopen®, can be addressed logically) |
Termination resistor | 124 Ω (Integrated and ready to be switched) |
Single conductor/terminal point, rigid | 0.2 mm² ... 2.5 mm² |
Single-wire/terminal point, flexible | 0.2 mm² ... 2.5 mm² |
Max. AWG conductor cross section, flexible | 14 |
Min. AWG conductor cross section, flexible | 24 |
Single-wire/terminal point, rigid AWG max. | 14 |
Single-wire/terminal point, rigid AWG min. | 24 |
Transmission medium | 2-wire twisted pair, shielded |
Transmission method | CSMA/CA |
File format/coding | Bit stuffing, NRZ |
Dimensions
Width | 35 mm |
Height | 102 mm |
Depth | 119 mm |
Material specifications
Color (Housing) | green (RAL 6021) |
Material (Housing) | PA 6.6-FR |
FO cable
Fiber types | 200/230 µm |
Fiber types | 50/125 µm |
Fiber types | 62.5/125 µm |
Fiber types | PCF fiber |
Fiber types | Fiberglass |
Ambient conditions
Degree of Protection | IP20 |
Ambient Temperature (Operation) | -20 °C ... 60 °C |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Altitude | ≤ 5000 m (For restrictions, see the manufacturer's declaration for altitude operation) |
Permissible humidity (operation) | 30 % ... 95 % (non-condensing) |
CE
Certificate | CE-compliant |
ATEX
Identification | II 3 G Ex nA IIC T4 Gc X |
Note | Please follow the special installation instructions in the documentation! |
UL, USA/Canada
Identification | 508 Listed |
Corrosive gas test
Identification | ISA-S71.04-1985 G3 Harsh Group A |
Shipbuilding
Identification | DNV GL |
DNV GL data
Temperature | B |
Humidity | A |
Vibration | A |
EMC | B |
Enclosure | Required protection according to the Rules shall be provided upon installation on board |
EMC data
Noise immunity | EN 61000-6-2 |
Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
Noise emission | EN 55011 |
Electrostatic discharge
Standards/regulations | EN 61000-4-2 |
Contact discharge | ± 6 kV |
Discharge in air | ± 8 kV |
Comments | Criterion B |
Electromagnetic HF field
Standards/regulations | EN 61000-4-3 |
Field intensity | 10 V/m |
Comments | Criterion A |
Fast transients (burst)
Standards/regulations | EN 61000-4-4 |
Input | ± 2 kV |
Signal | ± 2 kV |
Comments | Criterion B |
Surge current load (surge)
Standards/regulations | EN 61000-4-5 |
Input | ± 0.5 kV |
Signal | ± 1 kV |
Comments | Criterion B |
Conducted interference
Standards/regulations | EN 61000-4-6 |
Comments | Criterion A |
Voltage | 10 V |
Emitted interference
Standards/regulations | EN 55011 |
Comments | Class A, industrial applications |
Criteria
Criterion A | Normal operating behavior within the specified limits. |
Criterion B | Temporary impairment to operational behavior that is corrected by the device itself. |
Standards and Regulations
Free from substances that could impair the application of coating | in accordance with VW-AUDI-Seat central standard P-VW 3.10.7 57 65 0 |
Mounting
Mounting Type | DIN rail mounting |
Accessories
Why Proax for Phoenix Contact PSI-MOS-DNET/FO 850 T?
Proax is an authorized distributor of Phoenix Contact PSI-MOS-DNET/FO 850 T and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Alternate Names | PSIMOSDNETFO850T |
Pack Size | 1 |
Recommended