AXL F AI4 I XC 1H - Analog module
Axioline F, Analog input module, Analog inputs: 4, 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA, connection technology: 2-, 3-, 4-conductor, transmission speed in the local bus: 100 Mbps, integrated sensor supply, Extreme conditions version, degree of protection: IP20, including bus base module and Axioline F connectors
- 4 analog, bipolar input channels for the connection of current signals
- Connection of sensors in 2-, 3-, and 4-conductor technology
- Current ranges: 0 mA ... 20 mA, 4 mA ... 20 mA, ±20 mA
- Simultaneous scanning of all channels by means of simultaneous sampling
- High crosstalk attenuation between the channels, thanks to separate signal paths
- Particularly robust against electromagnetic interference
- Device rating plate stored
- Can be used under extreme ambient conditions
- Extended temperature range of -40 °C ... +70 °C (see “Tested successfully: use under extreme ambient conditions” in the data sheet)
- Partially coated PCBs
Technical Specifications
Dimensions
Width | 35 mm |
Height | 126.1 mm |
Depth | 54 mm |
Note on dimensions | The depth applies when a TH 35-7.5 DIN rail is used (in accordance with EN 60715). |
Utilization restriction
EMC note | EMC: class A product, see manufacturer's declaration in the download area |
Axioline F local bus
Number of interfaces | 2 |
Connection Method | Bus base module |
Transmission Speed | 100 Mbps |
Module
Input address area | 8 Byte |
Output address area | 8 Byte |
Required parameter data | 7 Byte |
Required configuration data | 6 Byte |
Analog: General
Input name | Analog inputs |
Description of the input | Differential inputs, current |
Number of Inputs | 4 |
A/D conversion time | 31.25 µs |
A/D converter resolution | 16 bit |
Connection Method | Push-in connection |
Connection technology | 2-, 3-, 4-conductor |
Note regarding the connection technology | shielded |
Current Input Signal | 0 mA ... 20 mA |
Current Input Signal | 4 mA ... 20 mA |
Current Input Signal | -20 mA ... 20 mA |
Input resistance current input | 104 Ω (typical) |
Data formats | IB IL, S7-compatible |
Input filter | 30 Hz, 12 kHz and mean-value generation (can be parameterized) |
Limit frequency (3 dB) | 30 Hz |
Limit frequency (3 dB) | 12 kHz |
Measured value representation | 16 bits (15 bits + sign bit) |
Protective circuit | Transient protection of inputs; Suppressor diode |
Protective circuit | Overload protection of the inputs; No; ±5.2 V DC, maximum, Imax = 50 mA |
Product properties
Product family | Axioline F |
Type | block modular |
Mounting Position | any (no temperature derating) |
Scope of delivery | including bus base module and Axioline F connectors |
Special Properties | integrated sensor supply |
Special Properties | Extreme conditions version |
Insulation characteristics
Overvoltage category | II (IEC 60664-1, EN 60664-1) |
Pollution degree | 2 (IEC 60664-1, EN 60664-1) |
Potentials
Power consumption | typ. 1.51 W (Device, total, plus the power consumption of the external sensors) |
Power consumption | max. 1.83 W (Device, total, plus the power consumption of the external sensors) |
Potentials: Axioline F local bus supply (UBus)
Supply Voltage | 5 V DC (via bus base module) |
Current draw | max. 150 mA |
Current draw | typ. 120 mA |
Power consumption | max. 0.75 W |
Power consumption | typ. 0.6 W |
Potentials: Supply for analog modules (UA)
Supply Voltage | 24 V DC (I/O supply and sensor supply) |
Supply Voltage Range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
Current draw | max. 245 mA (IiS = 4 x 50 mA (full load)) |
Current draw | max. 45 mA (IiS = 0 mA) |
Current draw | typ. 118 mA (IiS = 4 x 20 mA (nominal load)) |
Current draw | max. 125 mA (IiS = 4 x 20 mA (nominal load)) |
Current draw | typ. 238 mA (IiS = 4 x 50 mA (full load)) |
Power consumption | max. 5.88 W (Full load) |
Protective circuit | Surge protection; electronic (35 V, 0.5 s) |
Protective circuit | Reverse polarity protection; up to HW 02: polarity protection diodefrom HW 03: parallel diode; with external 5 A fuse (for startup only) |
Protective circuit | Transient protection; Suppressor diode |
Supply:
Designation | Sensor supply UiS |
Supply Voltage | 24 V DC (from UA) |
Current consumption | max. 50 mA (per channel) |
Electrical isolation/isolation of the voltage ranges
Test voltage: 5 V supply of the local bus (UBus) / 24 V supply (I/Os) | 500 V AC, 50 Hz, 1 min. |
Test voltage: 5 V supply of the local bus (UBus)/analog inputs | 500 V AC, 50 Hz, 1 min. |
Test voltage: 5 V supply of the local bus (UBus) / functional ground | 500 V AC, 50 Hz, 1 min. |
Test voltage: 24 V supply (I/O)/analog inputs | 500 V AC, 50 Hz, 1 min. |
Test voltage: 24 V supply (I/O) / functional ground | 500 V AC, 50 Hz, 1 min. |
Test voltage: Analog inputs/functional ground | 500 V AC, 50 Hz, 1 min. |
Connection technology
Connection name | Axioline F connector |
Note on the connection method | Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual. |
Conductor connection
Connection Method | Push-in connection |
Conductor cross section rigid | 0.2 mm² ... 1.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 1.5 mm² |
Conductor cross section AWG | 24 ... 16 |
Stripping length | 8 mm |
Axioline F connector
Connection Method | Push-in connection |
Note on the connection method | Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual. |
Conductor cross section, rigid | 0.2 mm² ... 1.5 mm² |
Conductor cross section, flexible | 0.2 mm² ... 1.5 mm² |
Conductor cross section AWG | 24 ... 16 |
Stripping length | 8 mm |
Ambient conditions
Ambient Temperature (Operation) | -25 °C ... 60 °C (Standard, applications with UL approval, use in zone 2 potentially explosive area) |
Ambient Temperature (Operation) | -40 °C ... 70 °C (Extended, see section “Tested successfully: use under extreme ambient conditions” in the data sheet.) |
Degree of Protection | IP20 |
Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
Permissible humidity (storage/transport) | 5 % ... 95 % (non-condensing) |
Standards and Regulations
Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
ATEX
Identification | II 3 G Ex ec IIC T4 Gc |
Certificate | UL 20 ATEX 2441X |
References to standards | EN IEC 60079-0, EN IEC 60079-7 |
UKEX
Identification | II 3 G Ex ec IIC T4 Gc |
Certificate | PxCIMA22UKEX2701949X |
References to standards | EN IEC 60079-0, EN IEC 60079-7 |
IECEx
Identification | Ex ec IIC T4 Gc |
Certificate | IECEx ULD 20.0026X |
References to standards | IEC 60079-0 Ed. 7, IEC 60079-7 Ed. 5.1 |
UL, USA/Canada
Identification | cULus |
Certificate | E238705 |
UL Ex, USA / Canada
Identification | Class I, Zone 2, AEx ec IIC T4 |
Identification | Class I, Division 2, Groups A, B, C, and D, T4 |
Identification | Ex ec IIC T4 Gc X |
Certificate | E366272 |
References to standards | UL 60079-0 Ed. 7 / CSA C22.2 NO. 60079-0 Ed. 4 |
References to standards | UL 60079-7 Ed. 5 / CSA C22.2 NO. 60079-7 Ed. 2 |
CCC / China-Ex
Identification | Ex ec IIC T4 Gc |
Certificate | , 2021122309114456 |
References to standards | GB/T 3836.1-2021, GB/T 3836.3-2021 |
Mounting
Mounting Type | DIN rail mounting |
Mounting Position | any (no temperature derating) |
Accessories
Why Proax for Phoenix Contact AXL F AI4 I XC 1H?
Proax is an authorized distributor of Phoenix Contact AXL F AI4 I XC 1H and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Alternate Names | AXLFAI4IXC1H |
Pack Size | 1 |
Recommended
- 2688491 - Axioline F, Analog input module, Analog inputs: 4, 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA, connection technology: 2-, 3-, 4-conductor, transmission speed in the local bus: 100 Mbps, integrated sensor supply, degree of protection: IP20, including bus base module and Axioline F connectors
- 2702008 - Axioline F, Analog input module, Analog inputs: 4, 0 V ... 5 V, -5 V ... 5 V, 0 V ... 10 V, -10 V ... 10 V, connection technology: 2-, 3-, 4-conductor, transmission speed in the local bus: 100 Mbps, integrated sensor supply, Extreme conditions version, degree of protection: IP20, including bus base module and Axioline F connectors
- 2688501 - Axioline F, Analog input module, Analog inputs: 4, 0 V ... 5 V, -5 V ... 5 V, 0 V ... 10 V, -10 V ... 10 V, connection technology: 2-, 3-, 4-conductor, transmission speed in the local bus: 100 Mbps, integrated sensor supply, degree of protection: IP20, including bus base module and Axioline F connectors
- 2702072 - Axioline F, Analog I/O module, Analog inputs: 2, 0 V ... 5 V, -5 V ... 5 V, 0 V ... 10 V, -10 V ... 10 V, 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA, connection technology: 2-conductor, Analog outputs: 2, 0 V ... 5 V, -5 V ... 5 V, 0 V ... 10 V, -10 V ... 10 V, 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA, connection technology: 2-conductor, transmission speed in the local bus: 100 Mbps, degree of protection: IP20, including bus base module and Axioline F connectors
- 1035429 - Axioline F, Analog I/O module, Analog inputs: 2, 0 V ... 5 V, -5 V ... 5 V, 0 V ... 10 V, -10 V ... 10 V, 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA, connection technology: 2-conductor, Analog outputs: 2, 0 V ... 5 V, -5 V ... 5 V, 0 V ... 10 V, -10 V ... 10 V, 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA, connection technology: 2-conductor, transmission speed in the local bus: 100 Mbps, Extreme conditions version, degree of protection: IP20, including bus base module and Axioline F connectors
- 1052434 - Axioline F, Analog input module, Active analog inputs: 8 (HART), 4 mA ... 20 mA, connection technology: 2-conductor, transmission speed in the local bus: 100 Mbps, Extreme conditions version, HART functionality, degree of protection: IP20, including bus base module and Axioline F connectors
- 2702525 - Axioline F, Analog input module, Analog inputs: 8, 0 V ... 5 V, -5 V ... 5 V, 0 V ... 10 V, -10 V ... 10 V, 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA, connection technology: 2-conductor, transmission speed in the local bus: 100 Mbps, for SAFE AI applications with service-free continuous operation, degree of protection: IP20, including bus base module and Axioline F connectors
- 2701232 - Axioline F, Analog input module, Analog inputs: 8, 0 V ... 5 V, -5 V ... 5 V, 0 V ... 10 V, -10 V ... 10 V, 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA, connection technology: 2-conductor, transmission speed in the local bus: 100 Mbps, Extreme conditions version, degree of protection: IP20, including bus base module and Axioline F connectors
- 2688064 - Axioline F, Analog input module, Analog inputs: 8, 0 V ... 5 V, -5 V ... 5 V, 0 V ... 10 V, -10 V ... 10 V, 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA, connection technology: 2-conductor, transmission speed in the local bus: 100 Mbps, degree of protection: IP20, including bus base module and Axioline F connectors
- 1087080 - Axioline F, Analog output module, Analog outputs: 4 (HART), 0 mA ... 20 mA, 4 mA ... 20 mA, connection technology: 2-conductor, transmission speed in the local bus: 100 Mbps, Extreme conditions version, HART functionality, degree of protection: IP20, including bus base module and Axioline F connectors
- 2702153 - Axioline F, Analog output module, Analog outputs: 4, 0 V ... 5 V, -5 V ... 5 V, 0 V ... 10 V, -10 V ... 10 V, 0 mA ... 20 mA, 4 mA ... 20 mA, connection technology: 2-conductor, transmission speed in the local bus: 100 Mbps, Extreme conditions version, degree of protection: IP20, including bus base module and Axioline F connectors
- 2688527 - Axioline F, Analog output module, Analog outputs: 4, 0 V ... 5 V, -5 V ... 5 V, 0 V ... 10 V, -10 V ... 10 V, 0 mA ... 20 mA, 4 mA ... 20 mA, connection technology: 2-conductor, transmission speed in the local bus: 100 Mbps, degree of protection: IP20, including bus base module and Axioline F connectors
- 2701237 - Axioline F, Analog output module, Analog outputs: 8, 0 V ... 5 V, -5 V ... 5 V, 0 V ... 10 V, -10 V ... 10 V, 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA, connection technology: 2-conductor, transmission speed in the local bus: 100 Mbps, Extreme conditions version, degree of protection: IP20, including bus base module and Axioline F connectors
- 2688080 - Axioline F, Analog output module, Analog outputs: 8, 0 V ... 5 V, -5 V ... 5 V, 0 V ... 10 V, -10 V ... 10 V, 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA, connection technology: 2-conductor, transmission speed in the local bus: 100 Mbps, degree of protection: IP20, including bus base module and Axioline F connectors