Official Distributor
SKU
MPN
AXL F BK ETH NET2
Weight
0.229 kg
AXL F BK ETH NET2 - Bus coupler
Axioline F, Bus coupler, Ethernet (2 networks), RJ45 jack, transmission speed in the local bus: 100 Mbps, degree of protection: IP20, including bus base module and Axioline F connector
- 2 separate Ethernet ports (without integrated switch)
- 2 IP addresses
- Transmission speed of 10 Mbps and 100 Mbps
- Rotary coding switches for setting the IP address assignment and other functions
- Modbus/TCP (UDP) support
- BootP and DHCP
- Firmware can be updated
- Runtime in the bus coupler is negligible (almost 0 µs) (for Modbus/UDP)
- Typical cycle time of the Axioline F local bus is around 10 μs
Technical Specifications
Dimensions
Width | 45 mm |
Height | 126.1 mm |
Depth | 74 mm |
Note on dimensions | The depth applies when a TH 35-7.5 DIN rail is used (in accordance with EN 60715). |
Material specifications
Color | traffic grey A RAL 7042 |
Ethernet (2 networks)
Number of interfaces | 2 |
Connection Method | RJ45 jack |
Note on the connection method | Auto negotiation and autocrossing |
Transmission Speed | 10/100 Mbps (Half or full duplex mode (automatic detection, can be adjusted manually)) |
Transmission physics | Ethernet in RJ45 twisted pair |
Axioline F local bus
Number of interfaces | 1 |
Connection Method | Bus base module |
Transmission Speed | 100 Mbps |
Service
Number of interfaces | 1 |
Connection Method | Micro USB type B |
Fieldbus: Local bus gateway
Max. number of local bus devices | 63 (Consider the logic current consumed by the devices) |
System limits
Number of supported devices | max. 63 (per station) |
Number of local bus devices that can be connected | max. 63 |
Product properties
Product family | Axioline F |
Type | block modular |
Mounting Position | any (observe temperature derating) |
Scope of delivery | including bus base module and Axioline F connector |
Insulation characteristics
Overvoltage category | II (IEC 60664-1, EN 60664-1) |
Pollution degree | 2 (IEC 60664-1, EN 60664-1) |
Potentials: Communications power UL feed-in (the supply of the Axioline F local bus UBus is generated from UL)
Supply Voltage | 24 V DC |
Supply Voltage Range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
Current draw | max. 583 mA (with 2 A at UBus for the I/Os and UL = 24 V) |
Power consumption | max. 14 W (2.0 A on UBus, UL = 24 V) |
Protective circuit | Surge protection; electronic |
Protective circuit | Reverse polarity protection; electronic |
Potentials: Axioline F local bus supply (UBus)
Supply Voltage | 5 V DC (via bus base module) |
Power Supply Unit | 2 A |
Connection technology
Connection name | Axioline F connector |
Note on the connection method | Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual. |
Conductor connection
Connection Method | Push-in connection |
Conductor cross section rigid | 0.2 mm² ... 1.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 1.5 mm² |
Conductor cross section AWG | 24 ... 16 |
Stripping length | 8 mm |
Axioline F connector
Connection Method | Push-in connection |
Note on the connection method | Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual. |
Conductor cross section, rigid | 0.2 mm² ... 1.5 mm² |
Conductor cross section, flexible | 0.2 mm² ... 1.5 mm² |
Conductor cross section AWG | 24 ... 16 |
Stripping length | 8 mm |
Ambient conditions
Ambient Temperature (Operation) | -25 °C ... 60 °C (Mounting position: wall mounting on horizontal DIN rail) |
Ambient Temperature (Operation) | -25 °C ... 55 °C (Mounting position: any) |
Degree of Protection | IP20 |
Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
Permissible humidity (storage/transport) | 5 % ... 95 % (non-condensing) |
Standards and Regulations
Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
Mounting
Mounting Type | DIN rail mounting |
Mounting Type | DIN rail mounting |
Mounting Position | any (observe temperature derating) |
Accessories
Why Proax for Phoenix Contact 2702177?
Proax is an authorized distributor of Phoenix Contact 2702177 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |