Official Distributor
SKU
MPN
2701686
Weight
0.222 kg
This product is Not Cancellable/Not Returnable
AXL F BK S3 - Bus coupler
Axioline F, Bus coupler, Sercos, RJ45 jack, transmission speed in the local bus: 100 Mbps, degree of protection: IP20, including bus base module and Axioline F connector
- 2 Ethernet ports (with integrated switch)
- Rotary coding switches for setting the Sercos address
- Certified in accordance with Sercos V1.12
- Supports Sercos V1.31
- FSP-IO (Function Specific Profile-IO) for modular I/O devices
- Minimum Sercos III cycle time of 31.25 µs
- 8 connections (max. 4 consumer and max. 4 producer connections)
- Cross communication is possible up to reaching the maximum number of connections
- Synchronization between fieldbus and local bus
- The typical cycle time of the S20 system bus is around 10 μs
- Runtime in bus coupler is negligible (almost 0 µs)
- Firmware can be updated
- Supports the operation of Axioline Smart Elements
- Supports passive Smart Elements (firmware version 1.35 or later)
- Supports IOL-CONF (firmware version 1.35 or later)
Technical Specifications
Dimensions
Width | 45 mm |
Height | 126.1 mm |
Depth | 74 mm |
Note on dimensions | The depth applies when a TH 35-7.5 DIN rail is used (in accordance with EN 60715). |
Sercos
Number of interfaces | 2 |
Connection Method | RJ45 jack |
Note on the connection method | Auto negotiation and autocrossing |
Transmission Speed | 100 Mbps (full duplex) |
Transmission physics | Ethernet in RJ45 twisted pair |
Axioline F local bus
Number of interfaces | 1 |
Connection Method | Bus base module |
Transmission Speed | 100 Mbps |
Service
Number of interfaces | 1 |
Connection Method | USB type C (from HW 05) |
Connection Method | Micro USB type B (up to HW 04) |
Sercos
Equipment type | Sercos slave |
System-specific protocols | Sercos protocols Sercos |
Specification | Sercos specification 1.31 |
System limits
Number of supported devices | max. 63 (per station) |
Number of local bus devices that can be connected | max. 63 |
Product properties
Product family | Axioline F |
Type | block modular |
Mounting Position | any (observe temperature derating) |
Scope of delivery | including bus base module and Axioline F connector |
Insulation characteristics
Overvoltage category | II (IEC 60664-1, EN 60664-1) |
Pollution degree | 2 (IEC 60664-1, EN 60664-1) |
Potentials: Communications power UL feed-in (the supply of the Axioline F local bus UBus is generated from UL)
Supply Voltage | 24 V DC |
Supply Voltage Range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
Current draw | max. 570 mA (2.0 A at UBus, UL = 24 V, up to HW 04) |
Current draw | max. 670 mA (2.5 A at UBus, UL = 24 V, from HW 05) |
Power consumption | max. 13.7 W (2.0 A at UBus, UL = 24 V, up to HW 04) |
Power consumption | max. 16 W (2.5 A at UBus, UL = 24 V, from HW 05) |
Protective circuit | Surge protection; electronic |
Protective circuit | Reverse polarity protection; electronic |
Potentials: Axioline F local bus supply (UBus)
Supply Voltage | 5 V DC (via bus base module) |
Power Supply Unit | max. 2 A (up to HW 04) |
Power Supply Unit | max. 2.5 A (from HW 05) |
Electrical isolation/isolation of the voltage ranges
Test voltage: Ethernet interface 1 / Ethernet interface 2 | 1500 V AC, 50 Hz, 1 min. |
Test voltage: Ethernet interface 1 / 24 V communications voltage (UL) feed-in | 1500 V AC, 50 Hz, 1 min. |
Test voltage: Ethernet interface 2 / 24 V communications voltage (UL) feed-in | 1500 V AC, 50 Hz, 1 min. |
Test voltage: Ethernet interface 1 / functional ground | 1500 V AC, 50 Hz, 1 min. |
Test voltage: Ethernet interface 2 / functional ground | 1500 V AC, 50 Hz, 1 min. |
Test voltage: 24 V communications voltage (UL) feed-in / functional ground | 500 V AC, 50 Hz, 1 min. |
Connection technology
Connection name | Axioline F connector |
Note on the connection method | Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual. |
Conductor connection
Connection Method | Push-in connection |
Conductor cross section rigid | 0.2 mm² ... 1.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 1.5 mm² |
Conductor cross section AWG | 24 ... 16 |
Stripping length | 8 mm |
Axioline F connector
Connection Method | Push-in connection |
Note on the connection method | Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual. |
Conductor cross section, rigid | 0.2 mm² ... 1.5 mm² |
Conductor cross section, flexible | 0.2 mm² ... 1.5 mm² |
Conductor cross section AWG | 24 ... 16 |
Stripping length | 8 mm |
Ambient conditions
Ambient Temperature (Operation) | -25 °C ... 60 °C (Mounting position: wall mounting on horizontal DIN rail) |
Ambient Temperature (Operation) | -25 °C ... 55 °C (Mounting position: any) |
Degree of Protection | IP20 |
Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
Permissible humidity (storage/transport) | 5 % ... 95 % (non-condensing) |
Standards and Regulations
Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
Mounting
Mounting Type | DIN rail mounting |
Mounting Position | any (observe temperature derating) |
Accessories
Why Proax for Phoenix Contact AXL F BK S3?
Proax is an authorized distributor of Phoenix Contact AXL F BK S3 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.