AXL F BK PB - Bus coupler
Axioline F, Bus coupler, PROFIBUS DP, D-SUB-9 female connector, transmission speed in the local bus: 100 Mbps, degree of protection: IP20, including bus base module and Axioline F connector
- PROFIBUS connection via 9-pos. D-SUB socket
- Electrical isolation between PROFIBUS interface and logic
- Rotary coding switches for setting the PROFIBUS address
- DP/V1 for class 1 and class 2 masters
- PROFIBUS data transmission speed of 9.6 kbps to 12 Mbps
- Dynamic configuration is supported
- I&M functions
- Firmware can be updated
- Typical cycle time of the Axioline F local bus is around 10 μs
- Supports the operation of Axioline Smart Elements
- Supports passive Smart Elements (firmware version 2.20 or later)
Technical Specifications
Dimensions
Width | 45 mm |
Height | 126.1 mm |
Depth | 74 mm |
Note on dimensions | The depth applies when a TH 35-7.5 DIN rail is used (in accordance with EN 60715). |
PROFIBUS DP
Number of interfaces | 1 |
Connection Method | D-SUB-9 female connector |
Transmission Speed | 9.6 kbps ... 12 Mbps |
Axioline F local bus
Number of interfaces | 1 |
Connection Method | Bus base module |
Transmission Speed | 100 Mbps |
Service
Number of interfaces | 1 |
Connection Method | Micro USB type B |
Fieldbus: Local bus gateway
Max. number of local bus devices | 63 (Consider the logic current consumed by the devices) |
System limits
Number of supported devices | max. 63 (per station) |
Number of local bus devices that can be connected | max. 63 |
Product properties
Product family | Axioline F |
Type | block modular |
Mounting Position | any (observe temperature derating) |
Scope of delivery | including bus base module and Axioline F connector |
Insulation characteristics
Overvoltage category | II (IEC 60664-1, EN 60664-1) |
Pollution degree | 2 (IEC 60664-1, EN 60664-1) |
Potentials: Communications power UL feed-in (the supply of the Axioline F local bus UBus is generated from UL)
Supply Voltage | 24 V DC |
Supply Voltage Range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
Current draw | max. 567 mA (with 2 A at UBus for the I/Os and UL = 24 V) |
Power consumption | max. 13.7 W (2.0 A on UBus, UL = 24 V) |
Protective circuit | Surge protection; electronic |
Protective circuit | Reverse polarity protection; electronic |
Potentials: Axioline F local bus supply (UBus)
Supply Voltage | 5 V DC (via bus base module) |
Power Supply Unit | 2 A |
Electrical isolation/isolation of the voltage ranges
Test voltage: PROFIBUS interface / 24 V communications voltage (UL) feed-in | 500 V AC, 50 Hz, 1 min. |
Test voltage: PROFIBUS interface / functional ground | 500 V AC, 50 Hz, 1 min. |
Test voltage: 24 V communications voltage (UL) feed-in / functional ground | 500 V AC, 50 Hz, 1 min. |
Connection technology
Connection name | Axioline F connector |
Note on the connection method | Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual. |
Conductor connection
Connection Method | Push-in connection |
Conductor cross section rigid | 0.2 mm² ... 1.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 1.5 mm² |
Conductor cross section AWG | 24 ... 16 |
Stripping length | 8 mm |
Axioline F connector
Connection Method | Push-in connection |
Note on the connection method | Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual. |
Conductor cross section, rigid | 0.2 mm² ... 1.5 mm² |
Conductor cross section, flexible | 0.2 mm² ... 1.5 mm² |
Conductor cross section AWG | 24 ... 16 |
Stripping length | 8 mm |
Ambient conditions
Ambient Temperature (Operation) | -25 °C ... 60 °C (Mounting position: wall mounting on horizontal DIN rail) |
Ambient Temperature (Operation) | -25 °C ... 55 °C (Mounting position: any) |
Degree of Protection | IP20 |
Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
Permissible humidity (storage/transport) | 5 % ... 95 % (non-condensing) |
Standards and Regulations
Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
Mounting
Mounting Type | DIN rail mounting |
Mounting Position | any (observe temperature derating) |
Accessories
Why Proax for Phoenix Contact 2688530?
Proax is an authorized distributor of Phoenix Contact 2688530 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended