Series AXL-F-AI

AXL F AI8 HART XC 1F - Analog module

Axioline F, Analog input module, Active analog inputs: 8 (HART), 4 mA ... 20 mA, connection technology: 2-conductor, transmission speed in the local bus: 100 Mbps, Extreme conditions version, HART functionality, degree of protection: IP20, including bus base module and Axioline F connectors

  • Active analog input module
  • Sources power for up to 8 HART enabled, passive analog input signals
  • Cyclic access to PV, SV, TV, QV, and Loop Current
  • Current range: 4 mA ... 20 mA
  • Can be used under extreme ambient conditions
  • Extended temperature range of -40 °C ... +70 °C (see “Tested successfully: use under extreme ambient conditions” in the data sheet)
Technical Specifications

Dimensions

Width53.6 mm
Height126.1 mm
Depth77.14 mm
Note on dimensionsThe depth applies when a TH 35-7.5 DIN rail is used (in accordance with EN 60715).

Utilization restriction

EMC noteEMC: class A product, see manufacturer's declaration in the download area
CCCex noteUse in potentially explosive areas is not permitted in China.

Material specifications

Colortraffic grey A RAL 7042

Axioline F local bus

No. of channels2
Connection MethodBus base module
Transmission Speed100 Mbps

Module

Input address area48 Byte
Output address area0 Byte
Required parameter data 27 Byte
Required configuration data 6 Byte

Analog:

Input nameActive analog inputs
Description of the inputHART enabled, passive analog input signals
Number of Inputs8 (HART)
Connection MethodPush-in connection
Connection technology2-conductor
Note regarding the connection technologyshielded, twisted pair
Current Input Signal4 mA ... 20 mA

Product properties

Product familyAxioline F
Typeblock modular
Mounting Positionany (no temperature derating)
Scope of deliveryincluding bus base module and Axioline F connectors
Special PropertiesExtreme conditions version
Special PropertiesHART functionality

Potentials: Axioline F local bus supply (UBus)

Supply Voltage5 V DC (via bus base module)
Current drawmax. 60 mA
Current drawtyp. 40 mA

Potentials: Supply for analog modules (UA)

Supply Voltage24 V DC
Supply Voltage Range19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current drawmax. 240 mA

Electrical isolation/isolation of the voltage ranges

Test voltage: 5 V supply of the local bus (UBus) / 24 V supply (I/Os)500 V AC, 50 Hz, 1 min.
Test voltage: 5 V supply of the local bus (UBus) / functional ground500 V AC, 50 Hz, 1 min.
Test voltage: 24 V supply (I/O) / functional ground500 V AC, 50 Hz, 1 min.
Test voltage: Field to functional earth500 V AC, 50 Hz, 1 min.
Test voltage: Field to 5V or 24V supplies1500 V AC, 50 Hz, 1 min.

Connection technology

Connection nameAxioline F connector
Note on the connection methodPlease observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual.

Conductor connection

Connection MethodPush-in connection
Conductor cross section rigid0.2 mm² ... 1.5 mm²
Conductor cross section flexible0.2 mm² ... 1.5 mm²
Conductor cross section AWG24 ... 16
Stripping length8 mm

Axioline F connector

Connection MethodPush-in connection
Note on the connection methodPlease observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual.
Conductor cross section, rigid0.2 mm² ... 1.5 mm²
Conductor cross section, flexible0.2 mm² ... 1.5 mm²
Conductor cross section AWG24 ... 16
Stripping length8 mm

Ambient conditions

Ambient Temperature (Operation)-25 °C ... 60 °C (Standard)
Ambient Temperature (Operation)-40 °C ... 70 °C (Extended, see section “Tested successfully: use under extreme ambient conditions” in the data sheet.)
Degree of ProtectionIP20
Air pressure (operation)70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)70 kPa ... 106 kPa (up to 3000 m above sea level)
Ambient temperature (storage/transport)-40 °C ... 85 °C
Permissible humidity (operation)5 % ... 95 % (non-condensing)
Permissible humidity (storage/transport)5 % ... 95 % (non-condensing)

Standards and Regulations

Protection classIII (IEC 61140, EN 61140, VDE 0140-1)

ATEX

IdentificationII 3G Ex ec IIC T4 Gc
CertificateDEMKO 20 ATEX 2334X

IECEx

IdentificationEx ec IIC T4 Gc
CertificateIECEx UL 20.0002X

UKCA Ex (UKEX)

IdentificationII 3G Ex ec IIC T4 Gc
CertificatePxCAI22UKEx1052427X

Ex data

UL, USA / CanadaClass I, Div. 2, Groups A, B, C, D T4

Mounting

Mounting TypeDIN rail mounting
Mounting Positionany (no temperature derating)
Accessories

Why Proax for Phoenix Contact AXL F AI8 HART XC 1F?

Proax is an authorized distributor of Phoenix Contact AXL F AI8 HART XC 1F and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information

Alternate NamesAXLFAI8HARTXC1F
Pack Size1
Recommended

Available for order