Technical Specifications
Input data
| Input Voltage | 100 V AC -10 % / +20 % |
| Input Voltage | 110 V AC -10 % / +20 % |
| Input Voltage | 120 V AC -10 % / +15 % |
| Input Voltage | 130 V AC -15 % / +10 % |
| Voltage type of supply voltage | AC |
| Frequency range (fN) | 47.5 Hz ... 52.5 Hz |
| Bypass fuse | 40 A T 250 V |
| Permissible backup fuse | 40 A (Listed breaker) |
| Current consumption | nom. 24 A (100 V AC) |
| Current consumption | nom. 23.3 A (110 V AC) |
| Current consumption | nom. 24 A (120 V AC) |
| Current consumption | nom. 23.4 A (130 V AC) |
| Current consumption | max. 34.4 A (100 V AC) |
| Current consumption | max. 31.2 A (110 V AC) |
| Current consumption | max. 35.4 A (120 V AC) |
| Current consumption | max. 34.6 A (130 V AC) |
| Rated short-time current carrying capacity Icw | 6 kA |
Output data
| Classification according to IEC 62040-3 | VFI-SS-111 |
| Efficiency | > 94 % (100% load, battery charged) |
| Efficiency | > 90 % (100% load, battery charged) |
| Apparent power | 2500 VA |
| Real power | 2250 W |
| Power factor (cos phi) | 0.9 |
| Crest factor | 2.5 |
| Switch-over time | 0 ms |
| Connection in parallel | yes |
| Connection in parallel | max. 3 |
| Connection in series | No |
| Overload capability Mains operation | 120 % ... 150 % (20 s / 5 s, then switch to bypass operation) |
| Overload capability Battery operation | 120 % ... 150 % (20 s / 5 s, then shutdown) |
| Overload capability Bypass mode | 120 % ... 150 % (for a sustained period / 20 s, then shutdown) |
| Rated short-time current carrying capacity Icw | 6 kA |
Mains operation
| Output Voltage | 100 V AC ±2 % |
| Output Voltage | 110 V AC ±2 % |
| Output Voltage | 120 V AC ±2 % |
| Output Voltage | 130 V AC ±2 % |
| Form of output voltage | Pure sine |
| Output Current | nom. 20 A (100 V AC) |
| Output Current | nom. 18.2 A (110 V AC) |
| Output Current | nom. 20.8 A (120 V AC) |
| Output Current | nom. 19.2 A (130 V AC) |
| Maximum no-load power dissipation | 9 W |
| Power loss nominal load max. | < 120 W (100% load, battery charged) |
| Nominal output frequency | 50 Hz |
| Nominal output frequency | 60 Hz |
| Nominal output frequency | ±0.5 % (Output frequency tolerance) |
| Electronic current limitation | > 2 x Output: Current nom. (> 200 ms) |
Battery operation
| Maximum no-load power dissipation | 9 W |
| Power loss nominal load max. | 250 W (100% load, battery charged) |
| Nominal output frequency | 50 Hz |
| Nominal output frequency | 60 Hz |
| Nominal output frequency | ±0.5 % (Output frequency tolerance) |
| Total harmonic distortion factor (THD) | < 3 % (linear load) |
| Total harmonic distortion factor (THD) | < 8 % (non-linear load) |
| Electronic current limitation | > 2 x Output: Current nom. (> 200 ms) |
Input
| Input Voltage | 48 V DC |
| Input Voltage | max. 60 V DC |
| Input Current | max. 40 A |
| Nominal capacity range | 7 Ah ... 200 Ah |
| Charging current | max. 10 A |
Output
| Short-circuit current | 650 A (< 1,5 ms) |
General
| Connection in parallel | yes |
| Connection in parallel | max. 5 (per battery string) |
| Connection in series | No |
| IQ-Technology | yes |
| Permissible backup fuse | 40 A |
| Temperature sensor | yes |
| Permissible backup fuse | 40 A |
Interfaces
| Interface | Battery module communication interface |
| Number of interfaces | 1 |
| Connection Method | RJ45 |
| Position | 5.x |
| Locking | Locking clip |
| Transmission physics | Twisted-Pair 4x2 |
| Interface | Parallel operation communication interface |
| Number of interfaces | 2 |
| Connection Method | RJ45 |
| Position | 5.x |
| Locking | Locking clip |
| Transmission physics | Twisted-Pair 4x2 |
Signal input Bat.-Start
| Low signal | Connection to SGnd with < 2.7 kΩ |
| High signal | Open (> 200 kΩ between Bat.-Start and SGnd) |
Signal input Remote
| Low signal | Connection to SGnd with < 2.7 kΩ |
| High signal | Open (> 35 kΩ between Remote and SGnd) |
Signal output Alarm
| Position | 3.x |
| Signalization designation | Alarm |
| Position marking | 3.1 (Alarm) |
| Switching output | Transistor output, active |
| Output Voltage | 24 V |
| Continuous load current | ≤ 20 mA |
Signal output Battery mode
| Position | 3.x |
| Signalization designation | Bat.-Mode |
| Position marking | 3.2 (Bat.-Mode) |
| Switching output | Transistor output, active |
| Output Voltage | 24 V |
| Continuous load current | ≤ 20 mA |
Signal output Power Good
| Position | 3.x |
| Signalization designation | Power Good |
| Position marking | 3.3 (Power Good) |
| Switching output | Transistor output, active |
| Output Voltage | 24 V |
| Continuous load current | ≤ 20 mA |
Signal output Ready
| Position | 3.x |
| Signalization designation | Ready |
| Position marking | 3.4 (Ready) |
| Switching output | Transistor output, active |
| Output Voltage | 24 V |
| Continuous load current | ≤ 20 mA |
Signal output P > PN
| Position | 3.x |
| Signalization designation | P>Pn |
| Position marking | 3.5 (P>Pn) |
| Switching output | Transistor output, active |
| Output Voltage | 24 V |
| Continuous load current | ≤ 20 mA |
Signal output Service Required
| Position | 3.x |
| Signalization designation | Service Required |
| Position marking | 3.6 (Service Required) |
| Switching output | Transistor output, active |
| Output Voltage | 24 V |
| Continuous load current | ≤ 20 mA |
Signal ground SGnd
| Function | Signal ground |
| Reference potential | For signal inputs and signal outputs |
Product properties
| Product family | QUINT AC-USV |
Insulation characteristics
| Protection class | I |
| Overvoltage category | II |
| Pollution degree | 3 |
Item dimensions
| Width | 188 mm |
| Height | 240 mm |
| Depth | 143 mm |
Drill hole
| Diameter | 5.5 mm |
Installation dimensions
| Installation distance right/left | 0 mm / 0 mm |
| Installation distance top/bottom | 50 mm / 50 mm |
Mounting
| Mounting Type | Wall mounting |
Ambient conditions
| Degree of Protection | IP20 |
| Ambient Temperature (Operation) | -25 °C ... 60 °C (> 50 °C: 2,5 % / K) |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Maximum altitude | ≤ 4000 m (> 1000 m: 3 % / 1000 m) |
| Max. permissible relative humidity (operation) | ≤ 95 % |
| Shock | 30g in each direction, according to IEC 60068-2-27 |
| Vibration (Operation) | 5 Hz ... 100 Hz, 0.7g (EN 60068-2-6) |
UL
| Identification | UL/C-UL Recognized UL 1778 |
EMC data
| Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC |
| Interference emission | Noise emission |
| Noise immunity | Immunity |
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
| Conducted noise emission | EN 62040-02 (Class C2) |
Electrostatic discharge
| Standards/regulations | EN 61000-4-2 |
| Contact discharge | ± 6 kV |
| Discharge in air | ± 8 kV |
| Comments | Criterion A |
Electromagnetic HF field
| Standards/regulations | EN 61000-4-3 |
| Frequency Range | 80 MHz ... 6 GHz |
| Test field strength | 10 V/m |
| Comments | Criterion A |
Fast transients (burst)
| Standards/regulations | EN 61000-4-4 |
| Input | ± 2 kV |
| Input | ± 2 kV |
| Output | ± 2 kV |
| Signal | ± 2 kV |
| Signal | ± 2 kV (Communication parallel operation, battery module) |
| Comments | Criterion A |
Surge voltage load (surge)
| Standards/regulations | EN 61000-4-5 |
| Signal | 1 kV (asymmetrical) |
| Comments | Criterion B |
| Input/Output | ± 1 kV (symmetrical) |
| Input/Output | ± 2 kV (asymmetrical) |
Conducted interference
| Standards/regulations | EN 61000-4-6 |
| Frequency Range | 0.15 MHz ... 80 MHz |
| Signal | 10 V (asymmetrical) |
| Comments | Criterion A |
Power frequency magnetic field
| Standards/regulations | EN 61000-4-8 |
| Frequency | 60 Hz |
| Signal | 30 A/m |
| Comments | Criterion A |
Harmonic and interharmonic components
| Standards/regulations | EN 61000-4-13 |
| Comments | Criterion A |
Criteria
| Criterion A | Normal operating behavior within the specified limits. |
| Criterion B | Temporary impairment to operational behavior that is corrected by the device itself. |
Why Proax for Phoenix Contact 1136813?
Proax is an authorized distributor of Phoenix Contact 1136813 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
| Pack Size | 1 |
Recommended