The figure shows the versions with screw connection
SKU
MPN
PSR-SPP-24-230UC/ESAM4/3X1/1X2
Weight
0.411 kg
Series PSR-SPP
PSR-SPP-24-230UC/ESAM4/3X1/1X2 - Safety relays
Safety relay for emergency stop and safety door monitoring up to SIL 3 or Cat. 4, PL e in accordance with EN ISO 13849, 1- or 2-channel operation, 3 enabling current paths, nominal input voltage: 24 V AC/DC ... 230 V AC/DC, plug-in Push-in terminal block
- With inrush current reduction, therefore suitable for coupling to failsafe controllers (PSR-ESP4)
- 1- and 2-channel control
- With wide-range input (PSR-ESAM4/3X1)
Technical Specifications
Utilization restriction
EMC note | EMC: class A product, see manufacturer's declaration in the download area |
Product properties
Product family | PSRclassic |
Application | Emergency stop |
Application | Safety door |
Application | Light grid |
Mechanical service life | approx. 107 cycles |
Relay type | Electromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3 |
Electrical properties
Maximum power dissipation for nominal condition | 2.88 W |
Nominal operating mode | 100% operating factor |
Air clearances and creepage distances between the power circuits
Rated Insulation Voltage | 250 V AC |
Rated surge voltage/insulation | 6 kV/safe isolation, reinforced insulation and 6 kV between input circuits and output contact current paths (13/14, 23/24, 33/34), as well as between output contact current paths (13/14, 23/24, 33/34). |
General
Input voltage range | 24 V AC/DC ... 230 V AC/DC |
Input voltage range in reference to UN | 0.85 ... 1.1 |
Typical input current at UN | 120 mA (at 24 V DC) |
Typical input current at UN | 20 mA (at 120 V AC) |
Typical input current at UN | 10 mA (for 230 V AC) |
Voltage at input/start and feedback circuit | approx. 24 V DC |
Typical response time | 50 ms (manual start) |
Typical response time | 60 ms (automatic start) |
Typ. starting time with Us | 500 ms (when controlled via A1) |
Typical release time | 20 ms (when controlled via S11/S12 and S21/S22) |
Typical release time | 50 ms (at 24 V DC) |
Typical release time | 110 ms (at 120 V AC) |
Typical release time | 280 ms (for 230 V AC) |
Concurrence | ∞ |
Recovery time | 1 s |
Maximum switching frequency | 0.5 Hz |
Protective circuit | Surge protection; Suppressor diode and varistors |
Max. permissible overall conductor resistance | 11 Ω |
Operating voltage display | 1 x green LED |
Status display | 2 x green LEDs |
Output data
Contact switching type | 3 enabling current paths |
Contact switching type | 1 signaling current path |
Contact Material | AgSnO2, + 0.2 µm Au |
Maximum Switching Voltage | 250 V AC/DC |
Minimum Switching Voltage | 10 V AC/DC |
Limiting Continuous Current | 6 A (N/O contact / N/C contact) |
Maximum Inrush Current | 6 A |
Inrush current, minimum | 10 mA |
Sq. Total current | 50 A2 (ITH2 = I12 + I22 + ... + IN2) |
Interrupting rating (ohmic load) max. | 192 W (24 V DC, τ = 0 ms) |
Interrupting rating (ohmic load) max. | 384 W (48 V DC, τ = 0 ms) |
Interrupting rating (ohmic load) max. | 80 W (110 V DC, τ = 0 ms) |
Interrupting rating (ohmic load) max. | 66 W (220 V DC, τ = 0 ms) |
Interrupting rating (ohmic load) max. | 2000 VA (250 V AC, τ = 0 ms) |
Maximum interrupting rating (inductive load) | 48 W (24 V DC, τ = 40 ms) |
Maximum interrupting rating (inductive load) | 48 W (48 V DC, τ = 40 ms) |
Maximum interrupting rating (inductive load) | 48 W (110 V DC, τ = 40 ms) |
Maximum interrupting rating (inductive load) | 48 W (220 V DC, τ = 40 ms) |
Switching capacity min. | 360 mW |
Switching capacity (360/h cycles) | 4 A (24 V (DC13)) |
Switching capacity (360/h cycles) | 4 A (230 V (AC15)) |
Switching capacity (3600/h cycles) | 2.5 A (24 V (DC13)) |
Switching capacity (3600/h cycles) | 3 A (230 V (AC15)) |
Output fuse | 6 A gG NEOZED |
Output fuse | B6/C4A gL/gG automatic device |
Connection technology
pluggable | yes |
Conductor connection
Connection Method | Push-in connection |
Conductor cross section, rigid | 0.2 mm² ... 1.5 mm² |
Conductor cross section, flexible | 0.2 mm² ... 1.5 mm² |
Conductor cross section, flexible, with ferrule, with plastic sleeve | 0.25 mm² ... 1.5 mm² (only together with CRIMPFOX 6) |
Conductor cross section flexible, with ferrule without plastic sleeve | 0.25 mm² ... 1.5 mm² (only together with CRIMPFOX 6) |
Conductor cross section AWG | 24 ... 16 |
Stripping length | 8 mm |
Dimensions
Width | 45 mm |
Height | 112 mm |
Depth | 114.5 mm |
Material specifications
Color | yellow |
Safety data
Stop category | 0 |
Safety data: EN ISO 13849
Category | 4 |
Performance level (PL) | e |
Safety data: IEC 61508 - High demand
Safety Integrity Level (SIL) | 3 |
Safety data: IEC 61508 - Low demand
Safety Integrity Level (SIL) | 3 |
Safety data: EN IEC 62061
Safety Integrity Level (SIL) | 3 |
Ambient conditions
Degree of Protection | IP54 |
Degree of Protection | IP20 |
Min. degree of protection of inst. location | IP54 |
Ambient Temperature (Operation) | -20 °C ... 55 °C |
Ambient temperature (storage/transport) | -25 °C ... 85 °C |
Maximum altitude | ≤ 2000 m (Above sea level) |
Max. permissible humidity (storage/transport) | 75 % (on average, 85% infrequently, non-condensing) |
Max. permissible relative humidity (operation) | 75 % (on average, 85% infrequently, non-condensing) |
Shock | 15g |
Vibration (Operation) | 10 Hz ... 150 Hz, 2g |
Air clearances and creepage distances between the power circuits
Standards/regulations | DIN EN 50178/VDE 0160 |
Mounting
Mounting Type | DIN rail mounting |
Mounting Position | any |
Why Proax for Phoenix Contact 2981127?
Proax is an authorized distributor of Phoenix Contact 2981127 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.