The figure shows 120 UC version
2901425
SKU
PHX2901425
MPN
PSR-SPP-120UC/ESAM4/3X1/1X2/B
Weight
0.237 kg
Series PSR-SPP
PSR-SPP-120UC/ESAM4/3X1/1X2/B - Safety relays
Safety relay for emergency stop and safety door monitoring up to SIL 3 or Cat. 4, PL e in accordance with EN ISO 13849, 1- or 2-channel operation, 3 enabling current paths, nominal input voltage: 120 V AC/DC, pluggable Push-in terminal block
- Up to Cat. 4/PL e in accordance with EN ISO 13849-1, SIL 3 in accordance with EN IEC 62061, SIL 3 in accordance with IEC 61508
- Manually monitored and automatic activation in a single device
- Basic insulation
- 1- and 2-channel control
- 3 enabling current paths, 1 signaling current path
Technical Specifications
Product properties
| Product family | PSRclassic |
| Application | Emergency stop |
| Application | Safety door |
| Mechanical service life | approx. 10⁷ cycles |
| Relay type | Electromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3 |
Electrical properties
| Maximum power dissipation for nominal condition | 4.56 W |
| Nominal operating mode | 100% operating factor |
Air clearances and creepage distances between the power circuits
| Rated Insulation Voltage | 250 V AC |
| Rated surge voltage/insulation | 4 kV / basic insulation (safe isolation, reinforced insulation, and 6 kV between A1-A2/logic/enabling and signaling current paths) |
General
| Input voltage range | 110 V AC/DC ... 120 V AC/DC |
| Input voltage range in reference to UN | 0.85 ... 1.1 |
| Typical input current at UN | 38 mA |
| Voltage at input/start and feedback circuit | ~ 24 V DC |
| Typical response time | 40 ms (man. start) |
| Typ. starting time with Us | 330 ms (when controlled via A1) |
| Typical release time | 60 ms (when controlled via A1) |
| Typical release time | 20 ms (when controlled via S11/S12 and S21/S22) |
| Concurrence | ∞ |
| Recovery time | 1 s |
| Maximum switching frequency | 0.5 Hz |
| Protective circuit | Surge protection; Varistor 275 VRMS (A1-A2) |
| Protective circuit | Surge protection; Varistor |
| Max. permissible overall conductor resistance | 50 Ω |
| Operating voltage display | Green LED |
| Status display | Green LED |
Output data
| Contact switching type | 3 enabling current paths |
| Contact switching type | 1 signaling current path |
| Contact Material | AgSnO2, + 0.2 µm Au |
| Maximum Switching Voltage | 250 V AC/DC |
| Minimum Switching Voltage | 10 V AC/DC |
| Limiting Continuous Current | 6 A (N/O contact) |
| Limiting Continuous Current | 5 A (N/C contact) |
| Maximum Inrush Current | 6 A |
| Inrush current, minimum | 10 mA |
| Sq. Total current | 72 A2 |
| Interrupting rating (ohmic load) max. | 144 W (24 V DC, τ = 0 ms) |
| Interrupting rating (ohmic load) max. | 230 W (48 V DC, τ = 0 ms) |
| Interrupting rating (ohmic load) max. | 68 W (110 V DC, τ = 0 ms) |
| Interrupting rating (ohmic load) max. | 88 W (220 V DC, τ = 0 ms) |
| Interrupting rating (ohmic load) max. | 2000 VA (250 V AC, τ = 0 ms) |
| Maximum interrupting rating (inductive load) | 48 W (24 V DC, τ = 40 ms) |
| Maximum interrupting rating (inductive load) | 40 W (48 V DC, τ = 40 ms) |
| Maximum interrupting rating (inductive load) | 35 W (110 V DC, τ = 40 ms) |
| Maximum interrupting rating (inductive load) | 33 W (220 V DC, τ = 40 ms) |
| Switching capacity min. | 100 mW |
| Switching capacity (360/h cycles) | 6 A (24 V DC) |
| Switching capacity (360/h cycles) | 5 A (230 V AC) |
| Switching capacity (3600/h cycles) | 3 A (24 V (DC13)) |
| Switching capacity (3600/h cycles) | 3 A (230 V (AC 15)) |
| Output fuse | 10 A gL/gG NEOZED (N/O contact) |
| Output fuse | 6 A gL/gG NEOZED (N/C contact) |
Connection technology
| pluggable | yes |
Conductor connection
| Connection Method | Push-in connection |
| Conductor cross section rigid | 0.2 mm² ... 1.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 1.5 mm² |
| Conductor cross section, flexible, with ferrule, with plastic sleeve | 0.25 mm² ... 1.5 mm² (only together with CRIMPFOX 6) |
| Conductor cross section flexible, with ferrule without plastic sleeve | 0.25 mm² ... 1.5 mm² (only together with CRIMPFOX 6) |
| Conductor cross-section AWG | 24 ... 16 |
| Stripping length | 8 mm |
Dimensions
| Width | 22.5 mm |
| Height | 112 mm |
| Depth | 114.5 mm |
Material specifications
| Housing Material | Polyamide |
Safety data
| Stop category | 0 |
Safety data: EN ISO 13849
| Category | 4 |
| Performance level (PL) | e |
Safety data: IEC 61508 - High demand
| Safety Integrity Level (SIL) | 3 |
Safety data: IEC 61508 - Low demand
| Safety Integrity Level (SIL) | 3 |
Safety data: EN IEC 62061
| Safety Integrity Level (SIL) | 3 |
Ambient conditions
| Degree of Protection | IP20 |
| Min. degree of protection of inst. location | IP54 |
| Ambient Temperature (Operation) | -25 °C ... 55 °C |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Maximum altitude | ≤ 2000 m (Above sea level) |
| Max. permissible humidity (storage/transport) | 75 % (on average, 85% infrequently, non-condensing) |
| Max. permissible relative humidity (operation) | 75 % (on average, 85% infrequently, non-condensing) |
| Shock | 15g |
| Vibration (Operation) | 10 Hz ... 150 Hz, 2g |
Air clearances and creepage distances between the power circuits
| Standards/regulations | IEC 60664-1 |
Mounting
| Mounting Type | DIN rail mounting |
| Mounting Position | any |
Why Proax for Phoenix Contact 2901425?
Proax is an authorized distributor of Phoenix Contact 2901425 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
| Pack Size | 1 |
Recommended