Phoenix ContactOfficial Distributor

By Phoenix Contact

SKU
MPN
FL SWITCH 1008E
Weight
0.875 kg
This product is Not Cancellable/Not Returnable
Series FL-SWITCH

FL SWITCH 1008E - Industrial Ethernet Switch

Ethernet switch with eight RJ45 ports, meets IEC 61850-3 and IEEE 1613 standards. Automatic detection of data transmission speed of 10/100 Mbps (RJ45) with autocrossing function.

  • Wide operating temperature range of -40 °C ... 75 °C
  • QoS-prioritized (Quality of Service) messages
  • Network structure according to IEC 61850
  • IEEE 1613
  • Alarm contact for power supply and link status diagnostics
  • Local diagnostic indicators with LEDs
  • Intended for use in power substations
  • Auto negotiation and autocrossing detection simplifies installation and setup
Technical Specifications

Dimensions

Width54.4 mm
Height146.4 mm
Depth125 mm

Material specifications

Housing MaterialAluminum

Mounting

Mounting TypeDIN rail mounting

Ethernet (RJ45)

Connection MethodRJ45
Note on the connection methodAuto negotiation and autocrossing
Transmission Speed10/100 Mbps
Transmission physicsEthernet in RJ45 twisted pair
Transmission length100 m
No. of channels8 (RJ45 ports)
Data flow control/protocolsIEC 61850-3, IEEE 1613

Product properties

Product familyUnmanaged Switch 1000
TypeBlock design
MTTF86.6 Years (MIL-HDBK-217F standard, temperature 25°C, operating cycle 100%)

Insulation characteristics

Protection classIII (VDE 0106, IEC 60536)

Switch functions

Basic FunctionsUnmanaged switch / autonegotiation, complies with IEEE 802.3, store and forward switching mode, includes QoS and alarm contact. Meets IEC 61850-3 and IEEE 1613 standards
Signal contact control voltage24 V DC
Signal contact control current100 mA
MAC address table2k
Status and diagnostic indicatorsLEDs: US1, US2 (redundant voltage supply), link and activity per port
Additional functionsAutonegotiation

Security functions

Basic FunctionsUnmanaged switch / autonegotiation, complies with IEEE 802.3, store and forward switching mode, includes QoS and alarm contact. Meets IEC 61850-3 and IEEE 1613 standards

Electrical properties

Local diagnosticsUS1, US2 Supply voltage Green LED
Local diagnosticsLNK/ACT Link status/data transmission Green LED
Local diagnostics100 Data transmission speed Green LED
Local diagnosticsAlarm Power failure at US1 or US2/Link failure
Maximum power dissipation for nominal condition10.56 W
Transmission mediumCopper

Supply

Supply voltage (DC)24 V DC (redundant)
Supply voltage (DC)48 V DC
Supply Voltage Range12 V DC ... 57 V DC
Inrush Current9.84 A (0.2 ms)
Residual ripple3.6 VPP (within the permitted voltage range)
Typical current consumption440 mA (at US = 24 V DC)

Function

Signal contact control voltage24 V DC
Signal contact control current100 mA

Connection technology

Connection namePower supply

Power supply

Connection MethodCOMBICON plug-in screw terminal block
Conductor cross section, rigid0.2 mm² ... 2.5 mm²
Conductor cross section, flexible0.2 mm² ... 2.5 mm²
Conductor cross section AWG24 ... 14
Stripping length7 mm

Ambient conditions

Degree of ProtectionIP20
Ambient Temperature (Operation)-40 °C ... 75 °C
Ambient temperature (storage/transport)-45 °C ... 85 °C
Permissible humidity (operation)5 % ... 95 % (non-condensing)
Air pressure (operation)82 kPa ... 108 kPa (up to 1500 m above sea level)

Standards and Regulations

Standards/specificationsIEC 61850-3
Standards/specificationsIEEE 1613

EMC data

Conformance with EMC directivesIEC 61000-6-2 IEC 61000-4-2 (ESD) Criterion B
Conformance with EMC directivesIEC 61000-4-3 (immunity to radiated interference) Criterion A
Conformance with EMC directivesIEC 61000-4-4 (burst) Criterion A
Conformance with EMC directivesIEC 61000-4-5 (surge) Criterion B
Conformance with EMC directivesIEC 61000-4-6 (immunity to conducted interference) Criterion A
Conformance with EMC directivesIEC 61000-4-8 (immunity to magnetic fields) Criterion A
Conformance with EMC directivesIEC 61000-4-9 (immunity to pulsed magnetic field) Criterion B
Conformance with EMC directivesEN 55022 (emitted interference) Criterion B
Noise immunityIEC 61850-3, IEEE 1613, EN 61000-6-2: 2005
Noise emissionEN 61000-6-4

Functionality

Basic FunctionsUnmanaged switch / autonegotiation, complies with IEEE 802.3, store and forward switching mode, includes QoS and alarm contact. Meets IEC 61850-3 and IEEE 1613 standards

Signaling

Status displayLEDs: US1, US2 (redundant voltage supply), link and activity per port
Accessories

Why Proax for Phoenix Contact 2891065?

Proax is an authorized distributor of Phoenix Contact 2891065 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information

Pack Size1
Recommended

Available for order

Phoenix Contact Availability