2865463
SKU
PHX2865463
MPN
MACX MCR-EX-SL-NAM-2T
Weight
0.187 kg
This product is Not Cancellable/Not Returnable
Series MACX-MCR-EX-SL-NAM
MACX MCR-EX-SL-NAM-2T - Isolation amplifier
Ex i NAMUR isolating amplifier For operating proximity sensors and switches in Ex areas. The signals are transmitted via 2 transistor outputs (passive) to the safe area. Line fault detection (LFD), 3-way isolation, SIL 2.
- Power supply and error indication possible via DIN rail connector
- Up to SIL 2 in accordance with EN 61508
- Installation in zone 2, protection type "n" (EN 60079-15) permitted
- Signal output 2 can also be used as an error signaling output
- Line fault detection (LFD), can be activated/deactivated, error indicated by flashing red LED with disabling of transistor output
- LED indicators for supply voltage, switching state, and malfunction in accordance with NAMUR NE 44
- 4-way electrical isolation
- Direction of operation can be selected (operating or closed circuit current behavior)
- 2 transistor signal outputs (passive); up to 5 kHz
- Input for NAMUR proximity sensors (EN 60947-5-6), floating contacts or contacts with resistance circuit, [Ex ia] IIC
Technical Specifications
Utilization restriction
| EMC note | EMC: class A product, see manufacturer's declaration in the download area |
Product properties
| Product family | MACX Analog |
| Application | Digital IN |
| No. of channels | 1 |
| Type | Ex i signal conditioners with SIL functional safety |
| Configuration | DIP switches |
Insulation characteristics: GB Standard
| Overvoltage category | II |
| Pollution degree | 2 |
Functionality
| Configuration | DIP switches |
Electrical properties
| Electrical isolation | 3-way isolation |
| Electrical isolation between input and output | yes |
Electrical isolation Input/output
| Electrical isolation | 375 V (Peak value in accordance with IEC/EN 60079-11) |
Electrical isolation Input/output/supply, DIN rail connector
| Rated Insulation Voltage | 300 Vrms |
| Test voltage | 2.5 kV AC (50 Hz, 60 s) |
| Insulation | Safe isolation in accordance with IEC/EN 61010-1 |
Electrical isolation Input/supply, DIN rail connector
| Electrical isolation | 375 V (Peak value in accordance with IEC/EN 60079-11) |
Electrical isolation Output 1/output 2
| Rated Insulation Voltage | 50 Vrms |
| Test voltage | 1 kV AC (50 Hz, 60 s) |
| Insulation | Basic insulation in accordance with IEC/EN 61010-1 |
Supply
| Nominal Supply Voltage | 24 V DC |
| Supply Voltage Range | 19.2 V DC ... 30 V DC (24 V DC, -20 % ... +25 %) |
| Max. current consumption | < 28 mA (24 V DC) |
| Power dissipation | ≤ 800 mW |
| Power consumption | ≤ 800 mW |
Signal: NAMUR
| Description of the input | Intrinsically safe |
| Number of Inputs | 1 |
| Available Input Sources | NAMUR proximity sensors (IEC/EN 60947-5-6) |
| Available Input Sources | Floating switch contacts |
| Available Input Sources | Switch contacts with resistance circuit |
| Switching threshold "0" signal current | < 1.2 mA (blocking) |
| Switching threshold "1" signal, current | > 2.1 mA (conductive) |
| Short-circuit current | 8 mA |
| Switching hysteresis | < 0.2 mA |
| Line fault detection | < 0.05 mA ... 0.35 mA (Line break) |
| Line fault detection | < 100 Ω ... 360 Ω (Short circuit) |
| Line fault detection | Activated /deactivated via DIP switch |
| Non-load voltage | 8 V DC |
Switching: Transistor
| Output description | passive |
| Minimum Switching Voltage | 3 V DC |
| Maximum Switching Voltage | 30 V DC |
| Drop (ΔU) | < 1.4 V |
| Max. switching current | 50 mA (short-circuit-proof) |
| Min. switching current | 5 mA (short-circuit-proof) |
| Switching frequency | ≤ 5 kHz |
Signal
| Number of Outputs | 2 |
Connection data
| Connection Method | Screw connection |
| Stripping length | 7 mm |
| Screw thread | M3 |
| Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section AWG | 24 ... 14 |
| Tightening torque | 0.5 Nm ... 0.6 Nm |
Test socket
| Max. diameter | 2 mm |
Ex data
| Ex installation (EPL) | Gc |
| Ex installation (EPL) | Div. 2 |
| Ex i circuits (EPL) | Ga |
| Ex i circuits (EPL) | Da |
| Ex i circuits (EPL) | Ma |
| Ex i circuits (EPL) | Div. 1 |
Safety data
| Max. internal inductance Li | negligible |
| Max. internal capacitance Ci | 1.1 nF |
| Max. output voltage Uo | 9.6 V |
| Max. output current Io | 10 mA |
| Max. output power Po | 25 mW |
| Safety-related maximum voltage Um | 253 V AC |
| Safety-related maximum voltage Um | 125 V DC |
| IIA (simple circuit): Max. external inductivity Lo / Max. external capacitance Co | 1000 mH / 210 µF |
| IIB/IIIC (simple circuit): Max. external inductivity Lo / Max. external capacitance Co | 1000 mH / 26 µF |
| IIC (simple circuit): Max. external inductivity Lo / Max. external capacitance Co | 300 mH / 3.6 µF |
| IIC (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co | 100 mH / 510 nF, 50 mH / 580 nF, 5 mH / 600 nF, 1 mH / 600 nF, 10 µH / 600 nF |
| IIB/IIA/IIIC (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co | 100 mH / 1 µF, 5 mH / 1 µF, 1 mH / 1 µF, 10 µH / 1 µF |
Data
| No. of channels | 0 |
Signaling
| Status display | Green LED (supply voltage) |
| Status display | LED yellow (switching state) |
| Status display | Red LED (line errors) |
Dimensions
| Width | 12.5 mm |
| Height | 112.5 mm |
| Depth | 113.7 mm |
| Depth NS 35/7,5 | 114.5 mm (Snapped onto DIN rail NS 35/7,5 in accordance with EN 60715) |
Material specifications
| Color | gray (RAL 7042) |
| Flammability rating according to UL 94 | V0 (Housing) |
| Housing Material | PA 6.6-FR |
Safety data
| Safety Integrity Level (SIL) | 2 |
| Safety Integrity Level (SIL) | 2 |
Ambient conditions
| Degree of Protection | IP20 (not assessed by UL) |
| Ambient Temperature (Operation) | -40 °C ... 70 °C (Any mounting position) |
| Ambient Temperature (Operation) | -40 °C ... 70 °C (Derating) |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
Altitude range (≤ 2000 m)
| Altitude | ≤ 2000 m (The technical data refers to altitudes ≤2000 m above mean sea level. For altitudes >2000 m above mean sea level, refer to the data sheet.) |
| Ambient Temperature (Operation) | -40 °C ... 60 °C |
| Ambient Temperature (Operation) | -40 °C ... 70 °C (Derating) |
| Rated Insulation Voltage | 265 V AC/DC (UIsolation “ec”: Supply, input / output) |
Altitude range (≤ 3000 m)
| Height Range | > 2000 m ... 3000 m |
| Ambient Temperature (Operation) | -40 °C ... 54 °C |
| Ambient Temperature (Operation) | -40 °C ... 63 °C (Derating) |
| Safety-related maximum voltage Um | 190 V AC |
| Safety-related maximum voltage Um | 110 V DC |
| Rated Insulation Voltage | 190 V AC/DC (UIsolation “ec”: Supply, input / output) |
Altitude range (≤ 4000 m)
| Height Range | > 3000 m ... 4000 m |
| Ambient Temperature (Operation) | -40 °C ... 48 °C |
| Ambient Temperature (Operation) | -40 °C ... 56 °C (Derating) |
| Safety-related maximum voltage Um | 60 V |
| Rated Insulation Voltage | 60 V AC/DC (UIsolation “ec”: Supply, input / output) |
Altitude range (≤ 5000 m)
| Height Range | > 4000 m ... 5000 m |
| Ambient Temperature (Operation) | -40 °C ... 42 °C |
| Ambient Temperature (Operation) | -40 °C ... 49 °C (Derating) |
| Safety-related maximum voltage Um | 60 V |
| Rated Insulation Voltage | 60 V AC/DC (UIsolation “ec”: Supply, input / output) |
CE
| Certificate | CE-compliant |
| Note | and EN 61326 |
ATEX
| Identification | II (1) G [Ex ia Ga] IIC |
| Identification | II (1) D [Ex ia Da] IIIC |
| Identification | II 3(1) G Ex ec [ia Ga] IIC T4 Gc |
| Identification | I (M1) [Ex ia Ma] I |
| Certificate | IBExU 08 ATEX 1100 X |
UKCA Ex (UKEX)
| Identification | I (M1) [Ex ia Ma] I |
| Identification | II (1) G [Ex ia Ga] IIC |
| Identification | II (1) D [Ex ia Da] IIIC |
| Identification | II 3 (1) G Ex ec [ia Ga] IIC T4 Gc |
| Certificate | CML 22UKEX3527X |
IECEx
| Identification | [Ex ia Ga] IIC |
| Identification | [Ex ia Da] IIIC |
| Identification | Ex ec [ia Ga] IIC T4 Gc |
| Identification | [Ex ia Ma] I |
| Certificate | IECEx IBE 08.0005X |
CCC / China-Ex
| Identification | [Ex ia Ga] IIC |
| Identification | [Ex iaD] |
| Identification | Ex nA [ia Ga] IIC T4 Gc |
| Certificate | NEPSI GYJ20.1313X |
UL, USA/Canada
| Identification | Class I Div 2; IS for Class I, II, III Div 1 |
| Certificate | , C.D.-No 83104549 |
Shipbuilding approval
| Certificate | DNV GL TAA00000AG |
Safety Integrity Level (SIL, IEC 61508)
| Identification | 2 |
INMETRO
| Identification | [Ex ia Ga] IIC |
| Identification | [Ex ia Da] IIIC |
| Identification | Ex ec [ia Ga] IIC T4 Gc |
| Identification | [Ex ia Ma] I |
| Certificate | DNV 18.0141 X |
DNV GL data
| Temperature | B |
| Humidity | B |
| Vibration | A |
| EMC | B |
| Enclosure | Required protection according to the Rules shall be provided upon installation on board |
EMC data
| Noise immunity | EN 61000-6-2 |
| Electromagnetic compatibility | Conformance with EMC directive |
| Noise emission | EN 61000-6-4 |
Electromagnetic HF field
| Designation | Electromagnetic RF field |
| Standards/regulations | EN 61000-4-3 |
| Evaluation criterion | A |
Fast transients (burst)
| Designation | Fast transients (burst) |
| Standards/regulations | EN 61000-4-4 |
| Evaluation criterion | A |
Conducted interference
| Designation | Conducted interferences |
| Standards/regulations | EN 61000-4-6 |
| Evaluation criterion | A |
Standards and Regulations
| Electrical isolation | 3-way isolation |
GB Standard
| Standards/regulations | GB 3626.20 |
| Standards/regulations | GB 3836.1 |
| Standards/regulations | GB 3836.4 |
| Standards/regulations | GB 3836.8 |
| Standards/regulations | GB 12476.1 |
| Standards/regulations | GB 12476.4 |
Mounting
| Mounting Type | DIN rail mounting |
Accessories
Why Proax for Phoenix Contact 2865463?
Proax is an authorized distributor of Phoenix Contact 2865463 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
| Pack Size | 1 |
Recommended