Official Distributor
SKU
MPN
ILC 191 ME/AN
Weight
0.624 kg
This product is Not Cancellable/Not Returnable
Series ILC
ILC 191 ME/AN - Controller
Inline controller with integrated pulse/direction/PWM interface, RS-485/RS-422, analog inputs (0 ... 10 V), and analog outputs (0 ... 10 V), with programming options according to IEC 61131-3
- Memory extendable by up to 2 GB via plug-in SD card
- Free engineering with PC Worx Express (IEC 61131-3)
- Complete INTERBUS master (4096 I/O points)
- PROFINET-Device
- Modbus/TCP-Client
- Integrated FTP and HTML5 web server
- Numerous protocols supported such as: HTTP, FTP, SNTP, SNMP, SMTP, SQL, MySQL, etc.
- Integrated analog I/Os
- Integrated RS-485/RS-422 interface
Technical Specifications
Product properties
Product family | Inline-Controller |
Type | modular |
Display
Diagnostics display | No |
System properties
Processor | Altera Nios® II 64 MHz |
Retentive data storage | 48 kByte (NVRAM) |
IEC 61131 runtime system
Program Memory | 1 Mbyte |
Data storage system | 1 Mbyte |
Number of control tasks | 8 |
INTERBUS-Master
Amount of Process Data | max. 4096 bit (INTERBUS) |
Number of supported devices | max. 128 |
Number of local bus devices that can be connected | max. 63 (observe current consumption) |
Number of devices with parameter channel | max. 24 |
Number of supported branch terminals with remote bus branch | max. 3 |
Modbus/TCP-Client
Amount of Process Data | max. 32768 bit (internal Modbus /TCP client) |
Number of Modbus/TCP clients | max. 16 later than FW 4.42 |
PROFINET
Device function | PROFINET device |
Specification | 2.2 |
Device ID | 0096hex / 150dez |
Vendor ID | 00B0hex / 176dez |
Function
Diagnostics display | No |
Controller redundancy | No |
Safety function | No |
Functionality
Programming languages supported | Instruction list (IL) |
Programming languages supported | Symbolic flowchart (SFC) |
Programming languages supported | Ladder diagram (LD) |
Programming languages supported | Function block diagram (FBD) |
Programming languages supported | Structured text (ST) |
System requirements
Engineering tool | PC Worx |
Engineering tool | PC Worx Express |
Configuration tool | Config+ Version 1.01 or later |
Diagnostics tool | DIAG+ |
Runtime system | eCLR |
Application interface | OPC |
Electrical properties
Transmission medium | Copper |
Real-time clock
Realtime Clock | Yes |
Description realtime clock | integrated (rechargeable battery buffered) |
Potentials: 24 V supply UILC
Supply Voltage | 24 V DC -15 % / +20 % (in accordance with EN 61131-2) |
Supply Voltage Range | 19.2 V DC ... 30 V DC |
Potentials: 7.5 V communications power UL (potential jumper)
Supply Voltage | 7.5 V DC ±5 % |
Potentials: 24 V analog supply UANA (potential jumper)
Supply Voltage | 24 V DC -15 % / +20 % |
Supply Voltage Range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
Potentials: 24 V main supply UM
Supply Voltage | 24 V DC -15 % / +20 % (in accordance with EN 61131-2) |
Supply Voltage Range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
Current draw | max. 8 A DC |
Current draw | 6 mA (without sensors) |
Potentials: 24 V segment supply US
Supply Voltage | 24 V DC -15 % / +20 % (in accordance with EN 61131-2) |
Supply Voltage Range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
Current draw | max. 8 A DC |
Current draw | 10 mA (without actuators) |
Analog:
Input name | Analog inputs |
Number of Inputs | 2 |
A/D converter resolution | 11 bit |
Connection Method | Inline potential distributor |
Connection technology | 2-conductor |
Note regarding the connection technology | Inline potential distributor |
Voltage input signal | 0 V DC ... 10 V DC (Resolution: 11 bits) |
Input resistance of voltage input | typ. 324 kΩ |
Limit frequency (3 dB) | 100 Hz |
Common mode voltage range signal - ground | 0 V ... 10 V |
Digital:
Input name | Digital inputs |
Description of the input | EN 61131-2 type 1 NPN/PNP |
Number of Inputs | 8 |
Cable Length | max. 30 m |
Connection Method | Inline potential distributor |
Connection technology | 2-, 3-, 4-conductor |
Input voltage range | -0.5 V ... 30 V |
Input voltage range "0" signal | -0.5 V ... 5 V |
Input voltage range "1" signal | 15 V ... 30 V |
Nominal input current at UIN | typ. 7 mA |
Nominal input current at UIN | max. 15 mA |
Input filter time | typ. 5 ms (Signal change 01) |
Input filter time | typ. 5 ms () |
Typical response time | min. 3 ms |
Analog:
Output name | Analog outputs |
Connection Method | Inline potential distributor |
Connection technology | 2-conductor |
Number of Outputs | 2 |
D/A conversion time | 10 ms |
D/A converter resolution | 11 bit |
Voltage output signal | 0 V DC ... 10 V DC |
Load/output load voltage output | > 1 kΩ |
Digital:
Output name | Digital outputs |
Connection Method | Spring-cage connection |
Connection technology | 2-, 3-, 4-conductor |
Number of Outputs | 4 |
Output Voltage | 24 V DC |
Maximum Output Current per channel | 500 mA |
Maximum output current per module / terminal block | 2 A |
Nominal load, lamp | 12 W |
Nominal load, ohmic | 12 W |
Pulse direction
Output name | Pulse directional output for 5 V signals |
Number of pulse direction outputs | 2 (can be used as an alternative to pulse width modulation) |
Output Voltage | 5 V ±5 % |
Limit frequency | 150 kHz |
Inline connector
Connection Method | Spring-cage connection |
Conductor cross section, rigid | 0.08 mm² ... 1.5 mm² |
Conductor cross section, flexible | 0.08 mm² ... 1.5 mm² |
Conductor cross section AWG | 28 ... 16 |
Interfaces
Web server | yes |
Ethernet
Bus system | RJ45 |
Number of interfaces | 2 |
Connection Method | RJ45 jack |
Transmission Speed | 10/100 Mbps |
No. of channels | 2 |
INTERBUS local bus (master)
Number of interfaces | 1 |
Connection Method | Inline data jumper |
Transmission Speed | 500 kBaud / 2 MBaud (can be switched) |
Parameterization/operation/diagnostics
Bus system | RS-232 |
Number of interfaces | 1 |
Connection Method | 6-pos. MINI DIN socket (PS/2) |
Transmission Speed | max. 115.2 kbps |
Transmission physics | Copper |
No. of channels | 1 |
RS-422/-485
Bus system | RS-485/-422 |
Number of interfaces | 1 |
Connection Method | 4-pos. for full duplex |
Connection Method | 2-pos. for half duplex |
Dimensions
Width | 164 mm |
Height | 136.8 mm |
Depth | 71.5 mm |
Material specifications
Color | green |
Ambient conditions
Degree of Protection | IP20 |
Ambient Temperature (Operation) | -25 °C ... 55 °C |
Ambient temperature (storage/transport) | -25 °C ... 85 °C |
Permissible humidity (operation) | 10 % ... 95 % (according to DIN EN 61131-2) |
Permissible humidity (storage/transport) | 10 % ... 95 % (according to DIN EN 61131-2) |
Shock | 25g, Criterion 1, according to IEC 60068-2-27 |
Vibration (Operation) | 5g |
Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Resistance to gases that may endanger the functions, in acc. with DIN 40046-36, DIN 40046-37 | Sulfur dioxide (SO2) 10 ±0.3 ppm (test duration: 10 days), hydrogen sulfide (H2S) 1 ±0.3 ppm (test duration: 4 days), both at 25°C and with 75% humidity |
EMC data
Conformance with EMC directives | Immunity test in accordance with EN IEC 61000-6-2 Electrostatic discharge (ESD)IEC 61000-4-2 Criterion B, ±6 kV contact discharge, ±8 kV air discharge |
Conformance with EMC directives | Immunity test in accordance with EN IEC 61000-6-2 Electromagnetic fieldsIEC 61000-4-3 Criterion A, Field intensity: 10 V/m |
Conformance with EMC directives | Immunity test in accordance with EN IEC 61000-6-2 Fast transients (burst)IEC 61000-4-4 Criterion A, all interfaces ±1 kVCriterion B, all interfaces ±2 kV |
Conformance with EMC directives | Immunity test in accordance with EN IEC 61000-6-2 Transient overvoltage (surge)IEC 61000-4-5 Criterion B; DC supply lines: ±0.5 kV/±1.0 kV (symmetrical/asymmetrical), fieldbus cable shielding: ±1.0 kV |
Conformance with EMC directives | Immunity test in accordance with EN IEC 61000-6-2 Conducted interferenceIEC 61000-4-6 Criterion A, Test voltage 10 V |
Conformance with EMC directives | Noise emission test in accordance with EN 61000-6-4/IEC 61000-6-4 Class A |
Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
Mounting
Mounting Type | DIN rail mounting |
Accessories
Why Proax for Phoenix Contact 2700074?
Proax is an authorized distributor of Phoenix Contact 2700074 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended