Proax

Currency
0 Items
proax logo
Cart
Phoenix ContactOfficial Distributor

By Phoenix Contact

SKU
MPN
ILC 191 ME/AN
Weight
0.624 kg
This product is Not Cancellable/Not Returnable
Series ILC

ILC 191 ME/AN - Controller

Inline controller with integrated pulse/direction/PWM interface, RS-485/RS-422, analog inputs (0 ... 10 V), and analog outputs (0 ... 10 V), with programming options according to IEC 61131-3

  • Memory extendable by up to 2 GB via plug-in SD card
  • Free engineering with PC Worx Express (IEC 61131-3)
  • Complete INTERBUS master (4096 I/O points)
  • PROFINET-Device
  • Modbus/TCP-Client
  • Integrated FTP and HTML5 web server
  • Numerous protocols supported such as: HTTP, FTP, SNTP, SNMP, SMTP, SQL, MySQL, etc.
  • Integrated analog I/Os
  • Integrated RS-485/RS-422 interface
Technical Specifications

Product properties

Product familyInline-Controller
Typemodular

Display

Diagnostics displayNo

System properties

ProcessorAltera Nios® II 64 MHz
Retentive data storage48 kByte (NVRAM)

IEC 61131 runtime system

Program Memory1 Mbyte
Data storage system1 Mbyte
Number of control tasks8

INTERBUS-Master

Amount of Process Datamax. 4096 bit (INTERBUS)
Number of supported devicesmax. 128
Number of local bus devices that can be connectedmax. 63 (observe current consumption)
Number of devices with parameter channelmax. 24
Number of supported branch terminals with remote bus branchmax. 3

Modbus/TCP-Client

Amount of Process Datamax. 32768 bit (internal Modbus /TCP client)
Number of Modbus/TCP clientsmax. 16 later than FW 4.42

PROFINET

Device functionPROFINET device
Specification2.2
Device ID0096hex / 150dez
Vendor ID00B0hex / 176dez

Function

Diagnostics displayNo
Controller redundancyNo
Safety functionNo

Functionality

Programming languages supportedInstruction list (IL)
Programming languages supportedSymbolic flowchart (SFC)
Programming languages supportedLadder diagram (LD)
Programming languages supportedFunction block diagram (FBD)
Programming languages supportedStructured text (ST)

System requirements

Engineering toolPC Worx
Engineering toolPC Worx Express
Configuration toolConfig+ Version 1.01 or later
Diagnostics toolDIAG+
Runtime systemeCLR
Application interfaceOPC

Electrical properties

Transmission mediumCopper

Real-time clock

Realtime ClockYes
Description realtime clockintegrated (rechargeable battery buffered)

Potentials: 24 V supply UILC

Supply Voltage24 V DC -15 % / +20 % (in accordance with EN 61131-2)
Supply Voltage Range19.2 V DC ... 30 V DC

Potentials: 7.5 V communications power UL (potential jumper)

Supply Voltage7.5 V DC ±5 %

Potentials: 24 V analog supply UANA (potential jumper)

Supply Voltage24 V DC -15 % / +20 %
Supply Voltage Range19.2 V DC ... 30 V DC (including all tolerances, including ripple)

Potentials: 24 V main supply UM

Supply Voltage24 V DC -15 % / +20 % (in accordance with EN 61131-2)
Supply Voltage Range19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current drawmax. 8 A DC
Current draw6 mA (without sensors)

Potentials: 24 V segment supply US

Supply Voltage24 V DC -15 % / +20 % (in accordance with EN 61131-2)
Supply Voltage Range19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current drawmax. 8 A DC
Current draw10 mA (without actuators)

Analog:

Input nameAnalog inputs
Number of Inputs2
A/D converter resolution11 bit
Connection MethodInline potential distributor
Connection technology2-conductor
Note regarding the connection technologyInline potential distributor
Voltage input signal0 V DC ... 10 V DC (Resolution: 11 bits)
Input resistance of voltage inputtyp. 324 kΩ
Limit frequency (3 dB)100 Hz
Common mode voltage range signal - ground0 V ... 10 V

Digital:

Input nameDigital inputs
Description of the inputEN 61131-2 type 1 NPN/PNP
Number of Inputs8
Cable Lengthmax. 30 m
Connection MethodInline potential distributor
Connection technology2-, 3-, 4-conductor
Input voltage range-0.5 V ... 30 V
Input voltage range "0" signal-0.5 V ... 5 V
Input voltage range "1" signal15 V ... 30 V
Nominal input current at UINtyp. 7 mA
Nominal input current at UINmax. 15 mA
Input filter timetyp. 5 ms (Signal change 01)
Input filter timetyp. 5 ms ()
Typical response timemin. 3 ms

Analog:

Output nameAnalog outputs
Connection MethodInline potential distributor
Connection technology2-conductor
Number of Outputs2
D/A conversion time10 ms
D/A converter resolution11 bit
Voltage output signal0 V DC ... 10 V DC
Load/output load voltage output> 1 kΩ

Digital:

Output nameDigital outputs
Connection MethodSpring-cage connection
Connection technology2-, 3-, 4-conductor
Number of Outputs4
Output Voltage24 V DC
Maximum Output Current per channel500 mA
Maximum output current per module / terminal block2 A
Nominal load, lamp12 W
Nominal load, ohmic12 W

Pulse direction

Output namePulse directional output for 5 V signals
Number of pulse direction outputs2 (can be used as an alternative to pulse width modulation)
Output Voltage5 V ±5 %
Limit frequency150 kHz

Inline connector

Connection MethodSpring-cage connection
Conductor cross section, rigid0.08 mm² ... 1.5 mm²
Conductor cross section, flexible0.08 mm² ... 1.5 mm²
Conductor cross section AWG28 ... 16

Interfaces

Web serveryes

Ethernet

Bus systemRJ45
Number of interfaces2
Connection MethodRJ45 jack
Transmission Speed10/100 Mbps
No. of channels2

INTERBUS local bus (master)

Number of interfaces1
Connection MethodInline data jumper
Transmission Speed500 kBaud / 2 MBaud (can be switched)

Parameterization/operation/diagnostics

Bus systemRS-232
Number of interfaces1
Connection Method6-pos. MINI DIN socket (PS/2)
Transmission Speedmax. 115.2 kbps
Transmission physicsCopper
No. of channels1

RS-422/-485

Bus systemRS-485/-422
Number of interfaces1
Connection Method4-pos. for full duplex
Connection Method2-pos. for half duplex

Dimensions

Width164 mm
Height136.8 mm
Depth71.5 mm

Material specifications

Colorgreen

Ambient conditions

Degree of ProtectionIP20
Ambient Temperature (Operation)-25 °C ... 55 °C
Ambient temperature (storage/transport)-25 °C ... 85 °C
Permissible humidity (operation)10 % ... 95 % (according to DIN EN 61131-2)
Permissible humidity (storage/transport)10 % ... 95 % (according to DIN EN 61131-2)
Shock25g, Criterion 1, according to IEC 60068-2-27
Vibration (Operation)5g
Air pressure (operation)70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)70 kPa ... 106 kPa (up to 3000 m above sea level)
Resistance to gases that may endanger the functions, in acc. with DIN 40046-36, DIN 40046-37Sulfur dioxide (SO2) 10 ±0.3 ppm (test duration: 10 days), hydrogen sulfide (H2S) 1 ±0.3 ppm (test duration: 4 days), both at 25°C and with 75% humidity

EMC data

Conformance with EMC directivesImmunity test in accordance with EN IEC 61000-6-2 Electrostatic discharge (ESD)IEC 61000-4-2 Criterion B, ±6 kV contact discharge, ±8 kV air discharge
Conformance with EMC directivesImmunity test in accordance with EN IEC 61000-6-2 Electromagnetic fieldsIEC 61000-4-3 Criterion A, Field intensity: 10 V/m
Conformance with EMC directivesImmunity test in accordance with EN IEC 61000-6-2 Fast transients (burst)IEC 61000-4-4 Criterion A, all interfaces ±1 kVCriterion B, all interfaces ±2 kV
Conformance with EMC directivesImmunity test in accordance with EN IEC 61000-6-2 Transient overvoltage (surge)IEC 61000-4-5 Criterion B; DC supply lines: ±0.5 kV/±1.0 kV (symmetrical/asymmetrical), fieldbus cable shielding: ±1.0 kV
Conformance with EMC directivesImmunity test in accordance with EN IEC 61000-6-2 Conducted interferenceIEC 61000-4-6 Criterion A, Test voltage 10 V
Conformance with EMC directivesNoise emission test in accordance with EN 61000-6-4/IEC 61000-6-4 Class A
Electromagnetic compatibilityConformance with EMC Directive 2014/30/EU

Mounting

Mounting TypeDIN rail mounting
Accessories

Why Proax for Phoenix Contact 2700074?

Proax is an authorized distributor of Phoenix Contact 2700074 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information

Pack Size1
Recommended

Not in stock

Request lead time or order—we'll ensure quick delivery

Phoenix Contact Availability