Axioline F, Temperature recording module, Analog inputs: 8 (8 inputs for thermocouples or linear voltage, plus 1 input -5 V to +5 V), connection technology: 2-conductor (shielded, twisted pair), transmission speed in the local bus: 100 Mbps, degree of protection: IP20, including bus base module and Axioline F connectors

  • 8 analog input channels for the connection of thermocouples or linear voltages from -100 mV to +100 mV
  • 1 analog input channel for the connection of voltages from -5 V to +5 V
  • Connection of sensors in 2-conductor technology
  • Internal detection and compensation of cold junction temperature (can be parameterized)
  • External connection of Pt 100 cold junction sensors possible
  • Easy to use due to internal linearization of the sensor characteristic curves
  • Low tolerances (typically ±0.01% for sensor type K)
  • High temperature stability (typically 5 ppm/K)
  • High resistance to electromagnetic interference (Class A)
  • "Channel Scout" function
  • Device rating plate stored
  • Installation monitoring with indication via diagnostic LED for each channel
Technical Specifications

Dimensions

Width53.6 mm
Height126.1 mm
Depth54 mm
Note on dimensionsThe depth applies when a TH 35-7.5 DIN rail is used (in accordance with EN 60715).

Axioline F local bus

Number of interfaces2
Connection MethodBus base module
Transmission Speed100 Mbps

Module

Input address area18 Byte
Output address area18 Byte
Required parameter data 27 Byte (20 bytes for configuration with GSD AXL UTH 8 (packed))
Required configuration data 7 Byte

Analog

Input nameAnalog inputs
Description of the inputInputs for thermocouples or linear voltage
Number of Inputs8 + 1 (8 inputs for thermocouples or linear voltage, plus 1 input -5 V to +5 V)
Connection MethodPush-in connection
Connection technology2-conductor (shielded, twisted pair)
A/D converter resolution24 bit
Sensor types (RTD) that can be usedPt 100 (4 external cold junctions, can also be used as a sensor input)
Sensor types that can be used (TC)U, T, L, J, E, K, N, S, R, B, C, W, HK
Measuring PrincipleSigma/Delta process
Measured value representation16 bits (15 bits + sign bit)
Input filter time40 ms
Input filter time60 ms
Input filter time100 ms
Input filter time120 ms (adjustable)
Protective circuitShort-circuit protection, overload protection of the inputs
Protective circuitTransient protection of inputs

Product properties

Product familyAxioline F
Typeblock modular
Mounting Positionany (no temperature derating; Parameterize the mounting position using the object 0080hex ParaTable!)
Scope of deliveryincluding bus base module and Axioline F connectors

Insulation characteristics

Overvoltage categoryII (IEC 60664-1, EN 60664-1)
Pollution degree2 (IEC 60664-1, EN 60664-1)

Potentials

Power consumptiontyp. 1.63 W (entire device)
Power consumptionmax. 2.58 W (entire device)

Potentials: Axioline F local bus supply (UBus)

Supply Voltage5 V DC (via bus base module)
Current drawmax. 180 mA
Current drawtyp. 115 mA
Power consumptionmax. 0.9 W
Power consumptiontyp. 0.55 W

Potentials: Supply for analog modules (UA)

Supply Voltage24 V DC
Supply Voltage Range19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current drawmax. 70 mA
Current drawtyp. 45.3 mA
Power consumptionmax. 1.68 W
Protective circuitSurge protection; electronic (35 V, 0.5 s)
Protective circuitReverse polarity protection; Polarity protection diode
Protective circuitTransient protection; Suppressor diode

Electrical isolation/isolation of the voltage ranges

Test voltage: 5 V supply of the local bus (UBus) / 24 V supply (I/Os)500 V AC, 50 Hz, 1 min.
Test voltage: 5 V supply of the local bus (UBus) / functional ground500 V AC, 50 Hz, 1 min.
Test voltage: 24 V supply (I/O) / functional ground500 V AC, 50 Hz, 1 min.

Connection technology

Connection nameAxioline F connector
Note on the connection methodPlease observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual.

Conductor connection

Connection MethodPush-in connection
Conductor cross section rigid0.2 mm² ... 1.5 mm²
Conductor cross section flexible0.2 mm² ... 1.5 mm²
Conductor cross section AWG24 ... 16
Stripping length8 mm

Axioline F connector

Connection MethodPush-in connection
Note on the connection methodPlease observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual.
Conductor cross section, rigid0.2 mm² ... 1.5 mm²
Conductor cross section, flexible0.2 mm² ... 1.5 mm²
Conductor cross section AWG24 ... 16
Stripping length8 mm

Ambient conditions

Ambient Temperature (Operation)-25 °C ... 60 °C
Degree of ProtectionIP20
Air pressure (operation)70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)70 kPa ... 106 kPa (up to 3000 m above sea level)
Ambient temperature (storage/transport)-40 °C ... 85 °C
Permissible humidity (operation)5 % ... 95 % (non-condensing)
Permissible humidity (storage/transport)5 % ... 95 % (non-condensing)

Standards and Regulations

Protection classIII (IEC 61140, EN 61140, VDE 0140-1)

Mounting

Mounting TypeDIN rail mounting
Mounting Positionany (no temperature derating; Parameterize the mounting position using the object 0080hex ParaTable!)
Accessories

Why Proax for Phoenix Contact 2688417?

Proax is an authorized distributor of Phoenix Contact 2688417 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information

Pack Size1
Recommended

Available for order

Phoenix Contact Availability