Series AXL-F-UTH
AXL F UTH8 1F - Temperature module
Axioline F, Temperature recording module, Analog inputs: 8 (8 inputs for thermocouples or linear voltage, plus 1 input -5 V to +5 V), connection technology: 2-conductor (shielded, twisted pair), transmission speed in the local bus: 100 Mbps, degree of protection: IP20, including bus base module and Axioline F connectors
- 8 analog input channels for the connection of thermocouples or linear voltages from -100 mV to +100 mV
- 1 analog input channel for the connection of voltages from -5 V to +5 V
- Connection of sensors in 2-conductor technology
- Internal detection and compensation of cold junction temperature (can be parameterized)
- External connection of Pt 100 cold junction sensors possible
- Easy to use due to internal linearization of the sensor characteristic curves
- Low tolerances (typically ±0.01% for sensor type K)
- High temperature stability (typically 5 ppm/K)
- High resistance to electromagnetic interference (Class A)
- "Channel Scout" function
- Device rating plate stored
- Installation monitoring with indication via diagnostic LED for each channel
Technical Specifications
Dimensions
Width | 53.6 mm |
Height | 126.1 mm |
Depth | 54 mm |
Note on dimensions | The depth applies when a TH 35-7.5 DIN rail is used (in accordance with EN 60715). |
Axioline F local bus
Number of interfaces | 2 |
Connection Method | Bus base module |
Transmission Speed | 100 Mbps |
Module
Input address area | 18 Byte |
Output address area | 18 Byte |
Required parameter data | 27 Byte (20 bytes for configuration with GSD AXL UTH 8 (packed)) |
Required configuration data | 7 Byte |
Analog
Input name | Analog inputs |
Description of the input | Inputs for thermocouples or linear voltage |
Number of Inputs | 8 + 1 (8 inputs for thermocouples or linear voltage, plus 1 input -5 V to +5 V) |
Connection Method | Push-in connection |
Connection technology | 2-conductor (shielded, twisted pair) |
A/D converter resolution | 24 bit |
Sensor types (RTD) that can be used | Pt 100 (4 external cold junctions, can also be used as a sensor input) |
Sensor types that can be used (TC) | U, T, L, J, E, K, N, S, R, B, C, W, HK |
Measuring Principle | Sigma/Delta process |
Measured value representation | 16 bits (15 bits + sign bit) |
Input filter time | 40 ms |
Input filter time | 60 ms |
Input filter time | 100 ms |
Input filter time | 120 ms (adjustable) |
Protective circuit | Short-circuit protection, overload protection of the inputs |
Protective circuit | Transient protection of inputs |
Product properties
Product family | Axioline F |
Type | block modular |
Mounting Position | any (no temperature derating; Parameterize the mounting position using the object 0080hex ParaTable!) |
Scope of delivery | including bus base module and Axioline F connectors |
Insulation characteristics
Overvoltage category | II (IEC 60664-1, EN 60664-1) |
Pollution degree | 2 (IEC 60664-1, EN 60664-1) |
Potentials
Power consumption | typ. 1.63 W (entire device) |
Power consumption | max. 2.58 W (entire device) |
Potentials: Axioline F local bus supply (UBus)
Supply Voltage | 5 V DC (via bus base module) |
Current draw | max. 180 mA |
Current draw | typ. 115 mA |
Power consumption | max. 0.9 W |
Power consumption | typ. 0.55 W |
Potentials: Supply for analog modules (UA)
Supply Voltage | 24 V DC |
Supply Voltage Range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
Current draw | max. 70 mA |
Current draw | typ. 45.3 mA |
Power consumption | max. 1.68 W |
Protective circuit | Surge protection; electronic (35 V, 0.5 s) |
Protective circuit | Reverse polarity protection; Polarity protection diode |
Protective circuit | Transient protection; Suppressor diode |
Electrical isolation/isolation of the voltage ranges
Test voltage: 5 V supply of the local bus (UBus) / 24 V supply (I/Os) | 500 V AC, 50 Hz, 1 min. |
Test voltage: 5 V supply of the local bus (UBus) / functional ground | 500 V AC, 50 Hz, 1 min. |
Test voltage: 24 V supply (I/O) / functional ground | 500 V AC, 50 Hz, 1 min. |
Connection technology
Connection name | Axioline F connector |
Note on the connection method | Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual. |
Conductor connection
Connection Method | Push-in connection |
Conductor cross section rigid | 0.2 mm² ... 1.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 1.5 mm² |
Conductor cross section AWG | 24 ... 16 |
Stripping length | 8 mm |
Axioline F connector
Connection Method | Push-in connection |
Note on the connection method | Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual. |
Conductor cross section, rigid | 0.2 mm² ... 1.5 mm² |
Conductor cross section, flexible | 0.2 mm² ... 1.5 mm² |
Conductor cross section AWG | 24 ... 16 |
Stripping length | 8 mm |
Ambient conditions
Ambient Temperature (Operation) | -25 °C ... 60 °C |
Degree of Protection | IP20 |
Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
Permissible humidity (storage/transport) | 5 % ... 95 % (non-condensing) |
Standards and Regulations
Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
Mounting
Mounting Type | DIN rail mounting |
Mounting Position | any (no temperature derating; Parameterize the mounting position using the object 0080hex ParaTable!) |
Accessories
- Paire de blocs de jonction pour tension thermoélectrique, TC type E, tension nominale: 400 V, intensité nominale: 1 A, nombre de connexions: 4, nombre de pôles: 2, type de raccordement: Raccordement vissé, 1er étage, section : 0,2 mm2 - 4 mm2, type de montage: NS 35/7,5, NS 35/15, NS 32, coloris: gris
Why Proax for Phoenix Contact 2688417?
Proax is an authorized distributor of Phoenix Contact 2688417 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended
- 2702464 - Axioline F, Temperature recording module, Analog inputs: 8 (8 inputs for thermocouples or linear voltage, plus 1 input -5 V to +5 V), connection technology: 2-conductor (shielded, twisted pair), transmission speed in the local bus: 100 Mbps, Extreme conditions version, degree of protection: IP20, including bus base module and Axioline F connectors
- 2688598 - Axioline F, Temperature recording module, Analog inputs: 4 (4 inputs for thermocouples or linear voltage, plus 1 input -5 V to +5 V), connection technology: 2-conductor (shielded, twisted pair), transmission speed in the local bus: 100 Mbps, degree of protection: IP20, including bus base module and Axioline F connectors
- 2701235 - Axioline F, Temperature recording module, Analog inputs: 8 (for resistance temperature detectors), connection technology: 2-, 3-, 4-conductor (shielded), transmission speed in the local bus: 100 Mbps, Extreme conditions version, degree of protection: IP20, including bus base module and Axioline F connectors
- 2702120 - Axioline F, Temperature recording module, Analog inputs: 8 (for resistance temperature detectors), connection technology: 2-, 4-conductor (shielded), transmission speed in the local bus: 100 Mbps, measuring dynamics up to 8 Hz, degree of protection: IP20, including bus base module and Axioline F connectors
- 1035430 - Axioline F, Temperature recording module, Analog inputs: 4 (for resistance temperature detectors), connection technology: 2-, 3-, 4-conductor (shielded), transmission speed in the local bus: 100 Mbps, Extreme conditions version, degree of protection: IP20, including bus base module and Axioline F connectors
- Axioline F, Module d'entrée numérique, Sécurité fonctionnelle, PROFIsafe, destiné uniquement au raccordement sur des contrôleurs Phoenix Contact ou Siemens, Entrées TOR: 4 (avec affectation de deux canaux), 8 (avec affectation d'un canal), 24 V DC, connectique: 2, 3 ou 4 fils, indice de protection: IP20
- Axioline F, Module à relais, Sécurité fonctionnelle, PROFIsafe, destiné uniquement au raccordement sur des contrôleurs Phoenix Contact ou Siemens, Entrées de signalisation: 2, Sorties OUT24V_0 et OUT24V_1: 2, Sorties de relais sécurisées: 4 (indépendant du potentiel), Contact NO, indice de protection: IP20