Official Distributor
SKU
Weight
0.257 kg
This product is Not Cancellable/Not Returnable
AXL F PSDI8/4 1F - Module de sécurité
Axioline F, Module d'entrée numérique, Sécurité fonctionnelle, PROFIsafe, destiné uniquement au raccordement sur des contrôleurs Phoenix Contact ou Siemens, Entrées TOR: 4 (avec affectation de deux canaux), 8 (avec affectation d'un canal), 24 V DC, connectique: 2, 3 ou 4 fils, indice de protection: IP20
- Jusqu'à la cat. 4/PL e selon la norme EN ISO 13849-1, SIL 3 selon la norme EN CEI 62061, SIL 3 selon la norme CEI 61508
Technical Specifications
Dimensions
Width | 53.6 mm |
Height | 126.1 mm |
Depth | 54 mm |
Note on dimensions | Housing dimensions |
Axioline F local bus
Connection Method | Bus base module |
Module
Input address area | 5 Byte |
Output address area | 5 Byte |
Required parameter data | 22 Byte ((I-and F-parameters)) |
Required configuration data | 10 Byte |
Digital:
Input name | Digital inputs |
Description of the input | IEC 61131-2 type 3 |
Number of Inputs | 4 (for 2-channel assignment) |
Number of Inputs | 8 (for 1-channel assignment) |
Cable Length | max. 1000 m (200 m from the clock output to the safe input (total based on forward and return path)) |
Connection Method | Push-in connection |
Connection technology | 2-, 3-, 4-conductor |
Input Voltage | 24 V DC (via clock outputs T1 and T2 or external supply) |
Input voltage range | -3 V DC ... 30 V DC |
Nominal input voltage UIN | 24 V DC |
Nominal input current at UIN | typ. 4.2 mA |
Typical input current per channel | 4.2 mA |
Input filter time | 1.5 ms |
Input filter time | 3 ms (Default) |
Input filter time | 5 ms |
Input filter time | 15 ms |
Product properties
Product family | Axioline F |
Application | Functional safety |
Application | PROFIsafe |
Application | only for connection to Phoenix Contact or Siemens controller |
Type | modular |
Electrical properties
Maximum power dissipation for nominal condition | 2 W |
Transmission medium | Copper |
Potentials
Protective circuit | Protection against polarity reversal, EMC protective circuit, undervoltage detection |
Potentials: Axioline F local bus supply (UBus)
Supply Voltage | 5 V DC (via bus base module) |
Current draw | max. 310 mA |
Current draw | typ. 280 mA (all inputs set; supply by UI of 19.2 V DC ... 30 V DC) |
Potentials: Supply for digital input modules (UI)
Supply Voltage | 24 V DC |
Supply Voltage Range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
Current draw | typ. 9 mA (all inputs set; supply from UI with 30 V DC; without supply to the sensors via clock supplies T1 and T2) |
Connection technology
Connection name | Axioline F connector |
pluggable | yes |
Conductor connection
Connection Method | Push-in connection |
Conductor cross section rigid | 0.2 mm² ... 1.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 1.5 mm² |
Conductor cross section AWG | 24 ... 16 |
Axioline F connector
Connection Method | Push-in connection |
Conductor cross section, rigid | 0.2 mm² ... 1.5 mm² |
Conductor cross section, flexible | 0.2 mm² ... 1.5 mm² |
Conductor cross section AWG | 24 ... 16 |
Ambient conditions
Ambient Temperature (Operation) | -35 °C ... 60 °C (Mounting position: any) |
Degree of Protection | IP20 |
Air pressure (operation) | 70 kPa ... 108 kPa (up to 3000 m above sea level) |
Air pressure (storage/transport) | 66 kPa ... 108 kPa (up to 3500 m above sea level) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Permissible humidity (operation) | 10 % ... 75 % (on average, 85% infrequently, non-condensing) |
Permissible humidity (storage/transport) | 10 % ... 75 % (non-condensing) |
Standards and Regulations
Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
Mounting
Mounting Type | DIN rail mounting |
Accessories
- Etiquette enfichable, pour le marquage de la série Axioline F de Phoenix Contact, Rouleau, jaune, vierge, repérable avec : THERMOMARK E.300 (D)/600 (D), THERMOMARK ROLL 2.0, THERMOMARK ROLL, THERMOMARK ROLL X1, THERMOMARK ROLLMASTER 300/600, THERMOMARK X1.2, type de montage: insertion, Nombre d'étiquettes: 500, hauteur du champ de texte: 46 mm, largeur du champ de texte: 35 mm
Why Proax for Phoenix Contact 2701559?
Proax is an authorized distributor of Phoenix Contact 2701559 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended
- Axioline F, Module à relais, Sécurité fonctionnelle, PROFIsafe, destiné uniquement au raccordement sur des contrôleurs Phoenix Contact ou Siemens, Entrées de signalisation: 2, Sorties OUT24V_0 et OUT24V_1: 2, Sorties de relais sécurisées: 4 (indépendant du potentiel), Contact NO, indice de protection: IP20
- 2702120 - Axioline F, Temperature recording module, Analog inputs: 8 (for resistance temperature detectors), connection technology: 2-, 4-conductor (shielded), transmission speed in the local bus: 100 Mbps, measuring dynamics up to 8 Hz, degree of protection: IP20, including bus base module and Axioline F connectors
- 2701235 - Axioline F, Temperature recording module, Analog inputs: 8 (for resistance temperature detectors), connection technology: 2-, 3-, 4-conductor (shielded), transmission speed in the local bus: 100 Mbps, Extreme conditions version, degree of protection: IP20, including bus base module and Axioline F connectors
- 1035430 - Axioline F, Temperature recording module, Analog inputs: 4 (for resistance temperature detectors), connection technology: 2-, 3-, 4-conductor (shielded), transmission speed in the local bus: 100 Mbps, Extreme conditions version, degree of protection: IP20, including bus base module and Axioline F connectors
- 2688417 - Axioline F, Temperature recording module, Analog inputs: 8 (8 inputs for thermocouples or linear voltage, plus 1 input -5 V to +5 V), connection technology: 2-conductor (shielded, twisted pair), transmission speed in the local bus: 100 Mbps, degree of protection: IP20, including bus base module and Axioline F connectors
- 2702464 - Axioline F, Temperature recording module, Analog inputs: 8 (8 inputs for thermocouples or linear voltage, plus 1 input -5 V to +5 V), connection technology: 2-conductor (shielded, twisted pair), transmission speed in the local bus: 100 Mbps, Extreme conditions version, degree of protection: IP20, including bus base module and Axioline F connectors
- 2688598 - Axioline F, Temperature recording module, Analog inputs: 4 (4 inputs for thermocouples or linear voltage, plus 1 input -5 V to +5 V), connection technology: 2-conductor (shielded, twisted pair), transmission speed in the local bus: 100 Mbps, degree of protection: IP20, including bus base module and Axioline F connectors