Official Distributor
SKU
MPN
AXL F SSDO8/3 1F
Weight
0.351 kg
This product is Not Cancellable/Not Returnable
AXL F SSDO8/3 1F - Safety module
Axioline F, Digital output module, Functional safety, SafetyBridge technology, Digital outputs: 4 (for 2-channel assignment), 8 (for 1-channel assignment), 2 A, connection technology: 2-, 3-conductor, degree of protection: IP20
- Cost-effective system configuration, as no safety PLC or safe fieldbus system is required
- Flexible use, thanks to compatibility with all bus couplers from the Axioline F range
- Reduced installation time, thanks to fast wiring and easy handling
- Easy configuration using the free SAFECONF software
- Up to Cat. 4/PL e in accordance with EN ISO 13849-1, SIL 3 in accordance with EN IEC 62061, SIL 3 in accordance with IEC 61508
Technical Specifications
Dimensions
Width | 53.6 mm |
Height | 126.1 mm |
Depth | 54 mm |
Note on dimensions | Housing dimensions |
Axioline F local bus
No. of channels | 1 |
Connection Method | Bus base module |
Module
Input address area | 8 Byte |
Output address area | 8 Byte |
Required parameter data | 1 Byte |
Required configuration data | 7 Byte |
Digital:
Output name | Digital outputs |
Connection Method | Direct plug-in technology |
Connection technology | 2-, 3-conductor |
Number of Outputs | 4 (for 2-channel assignment) |
Number of Outputs | 8 (for 1-channel assignment) |
Number of Outputs | 8 |
Protective circuit | Overload protection, freewheeling circuit for inductive loads,Discharge circuit for accelerated discharge of capacitive loads |
Output Voltage | 24 V DC |
Output Current | max. 2 A (per channel) |
Output Current | max. 1.5 A (per channel according to CULUS) |
Output Current | max. 4 A (per group) |
Output Current | max. 3 A (per group according to CULUS) |
Output Current | max. 8 A (Total current of all outputs; Please observe the notes in the user manual.) |
Output Current | max. 6 A (Total current of all outputs according to CULUS) |
Maximum Output Current per channel | 2 A |
Maximum output current per module / terminal block | 8 A |
Behavior with overload | Affected output is disabled and a diagnostic message is generated. |
Product properties
Product family | Axioline F |
Application | Functional safety |
Application | SafetyBridge technology |
Type | modular |
Electrical properties
Transmission medium | Copper |
Potentials
Protective circuit | Protection against polarity reversal, EMC protective circuit, undervoltage detection |
Potentials: Axioline F local bus supply (UBus)
Supply Voltage | 5 V DC (via bus base module) |
Current draw | max. 280 mA |
Current draw | typ. 260 mA (all outputs set; supply by UO of 19.2 V DC ... 30 V DC) |
Potentials: Supply for digital output modules (UO)
Supply Voltage | 24 V DC |
Supply Voltage Range | 19.2 V DC ... 30.2 V DC (including all tolerances, including ripple) |
Current draw | typ. 25 mA (all outputs set; supply from UO with 30 V DC; without supply to the actuators) |
Connection technology
Connection name | Axioline F connector |
Conductor connection
Connection Method | Push-in connection |
Conductor cross section rigid | 0.2 mm² ... 1.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 1.5 mm² |
Conductor cross section AWG | 24 ... 16 |
Stripping length | 8 mm |
Axioline F connector
Connection Method | Push-in connection |
Conductor cross section, rigid | 0.2 mm² ... 1.5 mm² |
Conductor cross section, flexible | 0.2 mm² ... 1.5 mm² |
Conductor cross section AWG | 24 ... 16 |
Stripping length | 8 mm |
Ambient conditions
Ambient Temperature (Operation) | -35 °C ... 60 °C (Mounting position: any) |
Degree of Protection | IP20 |
Air pressure (operation) | 70 kPa ... 108 kPa (up to 3000 m above sea level) |
Air pressure (storage/transport) | 66 kPa ... 108 kPa (up to 3500 m above sea level) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Permissible humidity (operation) | 10 % ... 75 % (on average, 85% infrequently, non-condensing) |
Permissible humidity (storage/transport) | 10 % ... 75 % (non-condensing) |
Standards and Regulations
Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
Mounting
Mounting Type | DIN rail mounting |
Accessories
Why Proax for Phoenix Contact 2702264?
Proax is an authorized distributor of Phoenix Contact 2702264 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended
- 2702120 - Axioline F, Temperature recording module, Analog inputs: 8 (for resistance temperature detectors), connection technology: 2-, 4-conductor (shielded), transmission speed in the local bus: 100 Mbps, measuring dynamics up to 8 Hz, degree of protection: IP20, including bus base module and Axioline F connectors
- 2701235 - Axioline F, Temperature recording module, Analog inputs: 8 (for resistance temperature detectors), connection technology: 2-, 3-, 4-conductor (shielded), transmission speed in the local bus: 100 Mbps, Extreme conditions version, degree of protection: IP20, including bus base module and Axioline F connectors
- 1035430 - Axioline F, Temperature recording module, Analog inputs: 4 (for resistance temperature detectors), connection technology: 2-, 3-, 4-conductor (shielded), transmission speed in the local bus: 100 Mbps, Extreme conditions version, degree of protection: IP20, including bus base module and Axioline F connectors
- 2688417 - Axioline F, Temperature recording module, Analog inputs: 8 (8 inputs for thermocouples or linear voltage, plus 1 input -5 V to +5 V), connection technology: 2-conductor (shielded, twisted pair), transmission speed in the local bus: 100 Mbps, degree of protection: IP20, including bus base module and Axioline F connectors
- 2702464 - Axioline F, Temperature recording module, Analog inputs: 8 (8 inputs for thermocouples or linear voltage, plus 1 input -5 V to +5 V), connection technology: 2-conductor (shielded, twisted pair), transmission speed in the local bus: 100 Mbps, Extreme conditions version, degree of protection: IP20, including bus base module and Axioline F connectors
- 2688598 - Axioline F, Temperature recording module, Analog inputs: 4 (4 inputs for thermocouples or linear voltage, plus 1 input -5 V to +5 V), connection technology: 2-conductor (shielded, twisted pair), transmission speed in the local bus: 100 Mbps, degree of protection: IP20, including bus base module and Axioline F connectors