AXL F PWM2 1H - Function module

Axioline F, Function module, Pulse width modulation, transmission speed in the local bus: 100 Mbps, degree of protection: IP20, including bus base module and Axioline F connectors

  • 2 independent channels
  • Output of 5 V or 24 V signals
  • Push-pull output
  • Nominal current per output: 500 mA (at 24 V DC), 10 mA (at 5 V DC)
  • Frequency output (0 Hz ... 65535 Hz)
  • Frequency resolution can be configured using the divider (1 Hz, 0.1 Hz, 0.01 Hz)
  • Pulse width resolution can be configured using the divider (1 ms, 0.1 ms, 0.01 ms)
  • Configurable pulse duty factor (0 % ... 100 %)
  • Device rating plate stored
Technical Specifications

Dimensions

Width35 mm
Height126.1 mm
Depth54 mm
Note on dimensionsThe depth applies when a TH 35-7.5 DIN rail is used (in accordance with EN 60715).

Axioline F local bus

Number of interfaces2
Connection MethodBus base module
Transmission Speed100 Mbps

Module

Input address area0 Byte
Output address area8 Byte
Required parameter data 1 Byte
Required configuration data 6 Byte

Signal

Output namePWM outputs
Operating modePWM, pulse generator, push-pull output
Connection MethodPush-in connection
Connection technology2-conductor
Number of Outputs2
Frequency Range0 Hz ... 65535 Hz
Pulse duty factor0 % ... 100 %
Nominal Output Voltage24 V (UO - 1.1 V)
Nominal Output Voltage5 V DC
Nominal current INmax. 500 mA (at 24 V DC)
Nominal current INmax. 10 mA (at 5 V DC)
Nominal load, ohmicmax. 12 W (at 24 V DC nominal voltage)
Nominal load, ohmicmax. 50 mW (at 5 V DC nominal voltage)
Nominal load, inductivemax. 12 VA (at 24 V DC nominal voltage)
Nominal load, inductivemax. 50 mVA (at 5 V DC nominal voltage)
Nominal load, lampmax. 6 W (at nominal voltage)
Short-circuit-proofyes
Short-circuit currenttyp. 2.2 A (for approx. 1.2 µs, auto-retry after approx. 40 µs, 24 V output)
Short-circuit currenttyp. 24 mA (5 V output)
Transient surge protectionyes

Product properties

Product familyAxioline F
Typeblock modular
Mounting Positionany (no temperature derating)
Scope of deliveryincluding bus base module and Axioline F connectors
Special PropertiesPulse width modulation

Insulation characteristics

Overvoltage categoryII (IEC 60664-1, EN 60664-1)
Pollution degree2 (IEC 60664-1, EN 60664-1)

Potentials: Axioline F local bus supply (UBus)

Supply Voltage5 V DC (via bus base module)
Current drawmax. 150 mA
Power consumptionmax. 0.75 W

Potentials: Supply voltage input UO

Supply Voltage24 V DC
Supply Voltage Range19.2 V DC ... 30 V DC including all tolerances, including ripple
Current drawmax. 1.1 A
Power consumptionmax. 33 W (of which 1.3 W internal losses)
Protective circuitSurge protection; electronic (35 V, 0.5 s)
Protective circuitReverse polarity protection; parallel diode; with external 1 A fuse (for start-up only)

Electrical isolation/isolation of the voltage ranges

Test voltage: 5 V supply of the local bus (UBus) / 24 V supply (I/Os)500 V AC, 50 Hz, 1 min.
Test voltage: 5 V supply of the local bus (UBus) / functional ground500 V AC, 50 Hz, 1 min.
Test voltage: 24 V supply (I/O) / functional ground500 V AC, 50 Hz, 1 min.

Connection technology

Connection nameAxioline F connector
Note on the connection methodPlease observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual.

Conductor connection

Connection MethodPush-in connection
Conductor cross section rigid0.2 mm² ... 1.5 mm²
Conductor cross section flexible0.2 mm² ... 1.5 mm²
Conductor cross section AWG24 ... 16
Stripping length8 mm

Axioline F connector

Connection MethodPush-in connection
Note on the connection methodPlease observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual.
Conductor cross section, rigid0.2 mm² ... 1.5 mm²
Conductor cross section, flexible0.2 mm² ... 1.5 mm²
Conductor cross section AWG24 ... 16
Stripping length8 mm

Ambient conditions

Ambient Temperature (Operation)-25 °C ... 60 °C
Degree of ProtectionIP20
Air pressure (operation)70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)70 kPa ... 106 kPa (up to 3000 m above sea level)
Ambient temperature (storage/transport)-40 °C ... 85 °C
Permissible humidity (operation)5 % ... 95 % (non-condensing)
Permissible humidity (storage/transport)5 % ... 95 % (non-condensing)

Standards and Regulations

Protection classIII (IEC 61140, EN 61140, VDE 0140-1)

Mounting

Mounting TypeDIN rail mounting
Mounting Positionany (no temperature derating)
Accessories

Why Proax for Phoenix Contact AXL F PWM2 1H?

Proax is an authorized distributor of Phoenix Contact AXL F PWM2 1H and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information

Alternate NamesAXLFPWM21H
Pack Size1
Recommended

Available for order