Official Distributor
SKU
MPN
PT 4-L/HESI (5X20)
Weight
0.027 kg
Series PT
PT 4-L/HESI (5X20) - Fuse modular terminal block
Fuse modular terminal block, fuse type: Glass / ceramics / ..., fuse type: G / 5 x 20, nom. voltage: 500 V, nominal current: 28 A, connection method: Push-in connection, Rated cross section: 4 mm2, cross section: 0.2 mm2- 6 mm2, connection method: Push-in connection, Rated cross section: 4 mm2, cross section: 0.2 mm2- 6 mm2, mounting type: NS 35/7,5, NS 35/15, color: black
- Easy and tool-free direct plug-in thanks to push-in multi-conductor connection
Technical Specifications
Notes
General | The current is determined by the fuse used, the voltage by the selected LED.If the fuse is faulty, the downstream circuit will not be disconnected. |
Product properties
Number of Connections | 4 |
Number of rows | 3 |
Potentials | 2 |
Insulation characteristics
Overvoltage category | III |
Degree of pollution | 3 |
Electrical properties
Fuse type | Glass / ceramics / ... |
Rated surge voltage | 6 kV |
Maximum power dissipation for nominal condition | 1.02 W |
Fuse | G / 5 x 20 |
Maximum power dissipation | max. 1.6 W (with single arrangement of the fuse terminal block in the event of overload) |
Maximum power dissipation | max. 1.6 W (With interconnected arrangement of several fuse terminal blocks in the event of overload) |
Maximum power dissipation | max. 4 W (with single arrangement of the fuse terminal block in the event of a short-circuit) |
Maximum power dissipation | max. 2.5 W (With interconnected arrangement of several fuse terminal blocks in the event of a short-circuit) |
Connection data
Number of connections per level | 2 |
Nominal cross section | 4 mm² |
Level 1
Stripping length | 10 mm ... 12 mm |
Internal cylindrical gage | A4 |
Connection in acc. with standard | IEC 60947-7-3 |
Conductor cross section rigid | 0.2 mm² ... 6 mm² |
Cross section AWG | 24 ... 10 (converted acc. to IEC) |
Conductor cross section flexible | 0.2 mm² ... 6 mm² |
Conductor cross section, flexible [AWG] | 24 ... 10 (converted acc. to IEC) |
Conductor cross-section flexible (ferrule without plastic sleeve) | 0.25 mm² ... 4 mm² |
Flexible conductor cross section (ferrule with plastic sleeve) | 0.25 mm² ... 4 mm² |
2 conductors with the same cross section, flexible, with TWIN ferrule with plastic sleeve | 0.5 mm² ... 1 mm² |
Nominal Current | 28 A |
Maximum Load Current | 32 A (with 6 mm² conductor cross section, rigid) |
Nominal Voltage | 500 V |
Nominal cross section | 4 mm² |
Level 2
Stripping length | 10 mm ... 12 mm |
Connection in acc. with standard | IEC 60947-7-3 |
Conductor cross section rigid | 0.2 mm² ... 6 mm² |
Cross section AWG | 24 ... 10 (converted acc. to IEC) |
Conductor cross section flexible | 0.2 mm² ... 6 mm² |
Conductor cross section, flexible [AWG] | 24 ... 10 (converted acc. to IEC) |
Conductor cross-section flexible (ferrule without plastic sleeve) | 0.25 mm² ... 4 mm² |
Flexible conductor cross section (ferrule with plastic sleeve) | 0.25 mm² ... 4 mm² |
Conductor cross-section flexible (2 conductors with the same cross-section, with TWIN ferrule and plastic sleeve) | 0.5 mm² ... 1 mm² |
Nominal Current | 6.3 A |
Maximum Load Current | 6.3 A (the current is determined by the fuse used) |
Nominal Voltage | 500 V (the voltage is determined by the fuse used) |
Nominal cross section | 4 mm² |
Level 1 Connection cross sections directly pluggable
Conductor cross section rigid | 0.5 mm² ... 6 mm² |
Conductor cross section, rigid [AWG] | 20 ... 10 (converted acc. to IEC) |
Conductor cross-section flexible (ferrule without plastic sleeve) | 0.5 mm² ... 4 mm² |
Flexible conductor cross section (ferrule with plastic sleeve) | 0.5 mm² ... 4 mm² |
Level 2 Connection cross sections directly pluggable
Conductor cross section rigid | 0.5 mm² ... 6 mm² |
Conductor cross section, rigid [AWG] | 20 ... 10 (converted acc. to IEC) |
Conductor cross-section flexible (ferrule without plastic sleeve) | 0.5 mm² ... 4 mm² |
Flexible conductor cross section (ferrule with plastic sleeve) | 0.5 mm² ... 4 mm² |
Rated data (ATEX/IECEx)
Identification | II 3 G Ex ec llC Gc |
Operating temperature range | -60 °C ... 130 °C |
Ex-certified accessories | 3002619 D-PT 4-PE/L/HESI |
Ex-certified accessories | 1205066 SZS 1,0X4,0 VDE |
Ex-certified accessories | 3022276 CLIPFIX 35-5 |
Ex-certified accessories | 3022218 CLIPFIX 35 |
List of bridges | Plug-in bridge / FBS 2-6 / 3030336 |
List of bridges | Plug-in bridge / FBS 3-6 / 3030242 |
List of bridges | Plug-in bridge / FBS 4-6 / 3030255 |
List of bridges | Plug-in bridge / FBS 5-6 / 3030349 |
List of bridges | Plug-in bridge / FBS 10-6 / 3030271 |
List of bridges | Plug-in bridge / FBS 20-6 / 3030365 |
Bridge data | 19 A / 4 mm² |
Rated voltage | 275 V |
for bridging with bridge | 275 V |
- At bridging between non-adjacent terminal blocks | 275 V |
- At cut-to-length bridging with cover | 275 V |
Rated Insulation Voltage | 250 V |
Output | (Permanent) |
Ex connection data General
Nominal cross section | 4 mm² |
Rated cross section AWG | 12 |
Connection capacity rigid | 0.2 mm² ... 6 mm² |
Connection capacity AWG | 24 ... 10 |
Connection capacity flexible | 0.2 mm² ... 4 mm² |
Connection capacity AWG | 24 ... 12 |
Output | (Permanent) |
Ex level Level 2
Rated current | 29 A (4 mm²) |
Maximum Load Current | 32 A (6 mm²) |
Contact resistance | 0.9 mΩ |
Temperature increase | 40 K (29 A/4 mm²) |
Output | (Permanent) |
Ex level Level 3
Rated current | 6.3 A (4 mm²) |
Maximum Load Current | 6.3 A (6 mm²) |
Contact resistance | 5 mΩ |
Dimensions
Width | 6.2 mm |
Height | 118.5 mm |
Depth | 82.6 mm |
Depth on NS 35/7,5 | 83.9 mm |
Depth on NS 35/15 | 91.4 mm |
Material specifications
Color | black |
Flammability rating according to UL 94 | V0 |
Insulating material group | I |
Insulating material | PA |
Static insulating material application in cold | -60 °C |
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) | 130 °C |
Relative insulation material temperature index (Elec., UL 746 B) | 130 °C |
Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 - HL 3 |
Calorimetric heat release NFPA 130 (ASTM E 1354) | 28 MJ/kg |
Surface flammability NFPA 130 (ASTM E 162) | passed |
Specific optical density of smoke NFPA 130 (ASTM E 662) | passed |
Smoke gas toxicity NFPA 130 (SMP 800C) | passed |
Mechanical data
Open side panel | Yes |
Oscillation/broadband noise
Specification | DIN EN 50155 (VDE 0115-200):2008-03 |
Spectrum | Service life test category 1, class B, body mounted |
Frequency | f1 = 5 Hz to f2 = 150 Hz |
ASD level | 0.964 (m/s²)²/Hz |
Acceleration | 0.58g |
Test duration per axis | 5 h |
Test directions | X-, Y- and Z-axis |
Result | Test passed |
Shocks
Specification | DIN EN 50155 (VDE 0115-200):2008-03 |
Pulse shape | Half-sine |
Acceleration | 5g |
Shock duration | 30 ms |
Number of shocks per direction | 3 |
Test directions | X-, Y- and Z-axis (pos. and neg.) |
Result | Test passed |
Ambient conditions
Ambient Temperature (Operation) | -60 °C ... 110 °C (Operating temperature range incl. self-heating; for max. short-term operating temperature, see RTI Elec.) |
Ambient temperature (storage/transport) | -25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C) |
Ambient temperature (assembly) | -5 °C ... 70 °C |
Ambient temperature (actuation) | -5 °C ... 70 °C |
Permissible humidity (operation) | 20 % ... 90 % |
Permissible humidity (storage/transport) | 30 % ... 70 % |
Standards and Regulations
Connection in acc. with standard | IEC 60947-7-3 |
Connection in acc. with standard | IEC 60947-7-3 |
Mounting
Mounting Type | NS 35/7,5 |
Mounting Type | NS 35/15 |
Accessories
Why Proax for Phoenix Contact 3002608?
Proax is an authorized distributor of Phoenix Contact 3002608 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 50 |
Recommended
- 3002609 - Fuse modular terminal block, fuse type: Glass / ceramics / ..., fuse type: G / 5 x 20, nom. voltage: 24 V, nominal current: 28 A, connection method: Push-in connection, Rated cross section: 4 mm2, cross section: 0.2 mm2- 6 mm2, connection method: Push-in connection, Rated cross section: 4 mm2, cross section: 0.2 mm2- 6 mm2, mounting type: NS 35/7,5, NS 35/15, color: black
- 3002612 - Fuse modular terminal block, fuse type: Glass / ceramics / ..., fuse type: G / 5 x 20, nom. voltage: 500 V, nominal current: 28 A, connection method: Push-in connection, Rated cross section: 4 mm2, cross section: 0.2 mm2- 6 mm2, connection method: Push-in connection, Rated cross section: 4 mm2, cross section: 0.2 mm2- 6 mm2, mounting type: NS 35/7,5, NS 35/15, color: black
- 3002611 - Fuse modular terminal block, fuse type: Glass / ceramics / ..., fuse type: G / 5 x 20, nom. voltage: 500 V, nominal current: 28 A, connection method: Push-in connection, Rated cross section: 4 mm2, cross section: 0.2 mm2- 6 mm2, connection method: Push-in connection, Rated cross section: 4 mm2, cross section: 0.2 mm2- 6 mm2, mounting type: NS 35/7,5, NS 35/15, color: black