Series PT
PT 4-F-ST - Surge protection plug
Surge protection plug for the base element, coarse protection for four signal lines grounded on one side.
- Easy testing and documentation with CHECKMASTER 2 with pluggable protective modules
- Maximum ease of maintenance, thanks to the 2-piece design
- Easy selection for all possible demands in MCR applications with a complete product portfolio
- The signal is not influenced during maintenance work, thanks to the impedance-neutral insertion and removal of protective plugs
Technical Specifications
Product properties
Product family | PLUGTRAB PT |
IEC test classification | C1 |
IEC test classification | C2 |
IEC test classification | C3 |
IEC test classification | D1 |
Type | Male |
Arrester can be tested with CHECKMASTER from software version: | From SW rev. 1.10 |
Wire pairs per module | 2 |
Insulation characteristics
Overvoltage category | III |
Pollution degree | 2 |
Electrical properties
Nominal voltage UN | 110 V AC |
Connection data
Connection Method | Screw connection (in connection with the base element) |
Screw thread | M3 |
Tightening torque | 0.5 Nm |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section rigid | 0.2 mm² ... 4 mm² |
Conductor cross section AWG | 24 ... 12 |
Dimensions
Width | 17.7 mm |
Height | 45 mm |
Depth | 52 mm |
Horizontal pitch | 1 Div. |
Complete module width | 17.7 mm |
Complete module height | 90 mm |
Complete module depth | 65.5 mm |
Material specifications
Color | black (RAL 9005) |
Flammability rating according to UL 94 | V-0 |
Housing Material | PA 6.6 |
Mechanical data
Open side panel | No |
Protective circuit
Direction of action | Line-Line & Line-Signal Ground/Shield & Signal Ground/Shield-Earth Ground |
Maximum continuous voltage UC | 60 V DC |
Maximum continuous voltage UC | 120 V AC |
Rated current | 2 A AC (80 °C) |
Rated current | 150 mA DC (80 °C) |
Operating effective current IC at UC | ≤ 2 µA |
Residual current IPE | ≤ 8 µA (with PT 4-BE) |
Residual current IPE | ≤ 2 µA (with PT 4+F-BE) |
Nominal discharge current In (8/20) µs (line-line) | 10 kA |
Nominal discharge current In (8/20) µs (line-ground) | 10 kA |
Pulse discharge current Iimp (10/350) µs (line-earth) | 2.5 kA |
Total discharge current Itotal (8/20) µs | 20 kA |
Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 450 V (with PT 4-BE) |
Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 600 V (with PT 4+F-BE) |
Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 25 V (with PT 4-BE) |
Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 50 V (with PT 4+F-BE) |
Voltage protection level Up (line-earth) | ≤ 550 V (C1 - 1 kV / 500 A with PT 4-BE) |
Voltage protection level Up (line-earth) | ≤ 950 V (C1 - 1 kV / 500 A with PT 4+F-BE) |
Voltage protection level Up (line-earth) | ≤ 600 V (C2 - 10 kV / 5 kA with PT 4-BE) |
Voltage protection level Up (line-earth) | ≤ 1350 V (C2 - 10 kV / 5 kA with PT 4+F-BE) |
Voltage protection level Up static (line-earth) | ≤ 50 V (C1 - 1 kV / 500 A with PT 4-BE) |
Voltage protection level Up static (line-earth) | ≤ 100 V (C1 - 1 kV / 500 A with PT 4+F-BE) |
Voltage protection level Up static (line-earth) | ≤ 50 V (C2 - 10 kV / 5 kA with PT 4-BE) |
Voltage protection level Up static (line-earth) | ≤ 100 V (C2 - 10 kV / 5 kA with PT 4+F-BE) |
Response time tA (line-line) | ≤ 100 ns |
Response time tA (line-earth) | ≤ 100 ns |
Input attenuation aE, asym. | typ. 0.1 dB (≤ 1 MHz / 50 Ω) |
Cut-off frequency fg (3 dB), asym. (siganl ground) in 50 Ω system | typ. 100 MHz |
Capacity (core-earth) | typ. 2 pF (with PT 4-BE) |
Capacity (core-earth) | typ. 2 pF (with PT 4+F-BE) |
Resistance per path | 0 Ω |
Surge protection fault message | none |
Max. required back-up fuse | 2 A AC (T) |
Max. required back-up fuse | 150 mA DC (T) |
Impulse durability (line-earth) | C2 - 10 kV / 5 kA |
Impulse durability (line-earth) | C1 - 1 kV / 500 A |
Impulse durability (line-earth) | C3 - 100 A |
Impulse durability (line-earth) | D1 - 2.5 kA |
Ambient conditions
Degree of Protection | IP20 |
Ambient Temperature (Operation) | -40 °C ... 85 °C |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Altitude | ≤ 2000 m (amsl) |
Standards and Regulations
Standards/specifications | IEC 61643-21 |
Note | 2000 + corrigendum 2001 + A1:2008, modified + A2:2012 |
Standards/specifications | EN 61643-21 |
Note | 2001 + A1:2009 + A2:2013 |
Mounting
Mounting Type | on base element |
Accessories
Why Proax for Phoenix Contact 2858441?
Proax is an authorized distributor of Phoenix Contact 2858441 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended
- 3211861 - Fuse modular terminal block, fuse type: Glass / ceramics / ..., fuse type: G / 5 x 20, nom. voltage: 500 V, nominal current: 6.3 A, number of positions: 1, connection method: Push-in connection, Rated cross section: 4 mm2, cross section: 0.2 mm2- 6 mm2, mounting type: NS 35/7,5, NS 35/15, color: black
- 3002611 - Fuse modular terminal block, fuse type: Glass / ceramics / ..., fuse type: G / 5 x 20, nom. voltage: 500 V, nominal current: 28 A, connection method: Push-in connection, Rated cross section: 4 mm2, cross section: 0.2 mm2- 6 mm2, connection method: Push-in connection, Rated cross section: 4 mm2, cross section: 0.2 mm2- 6 mm2, mounting type: NS 35/7,5, NS 35/15, color: black
- 3002612 - Fuse modular terminal block, fuse type: Glass / ceramics / ..., fuse type: G / 5 x 20, nom. voltage: 500 V, nominal current: 28 A, connection method: Push-in connection, Rated cross section: 4 mm2, cross section: 0.2 mm2- 6 mm2, connection method: Push-in connection, Rated cross section: 4 mm2, cross section: 0.2 mm2- 6 mm2, mounting type: NS 35/7,5, NS 35/15, color: black
- 3002609 - Fuse modular terminal block, fuse type: Glass / ceramics / ..., fuse type: G / 5 x 20, nom. voltage: 24 V, nominal current: 28 A, connection method: Push-in connection, Rated cross section: 4 mm2, cross section: 0.2 mm2- 6 mm2, connection method: Push-in connection, Rated cross section: 4 mm2, cross section: 0.2 mm2- 6 mm2, mounting type: NS 35/7,5, NS 35/15, color: black
- 3002608 - Fuse modular terminal block, fuse type: Glass / ceramics / ..., fuse type: G / 5 x 20, nom. voltage: 500 V, nominal current: 28 A, connection method: Push-in connection, Rated cross section: 4 mm2, cross section: 0.2 mm2- 6 mm2, connection method: Push-in connection, Rated cross section: 4 mm2, cross section: 0.2 mm2- 6 mm2, mounting type: NS 35/7,5, NS 35/15, color: black