Series PACT-RCP

PACT RCP-4000A-UIRO-PT-D95 - Current transformer

Set consisting of a 4-way signal conditioner with push-in connection technology and a Rogowski coil 300 mm in length/95 mm in diameter for AC current measurement on busbars and power lines.The signal conditioner outputs 8 different standard signals on the output side and has one switching output.

Technical Specifications

Insulation characteristics

Overvoltage categoryII
Pollution degree2

Electrical properties

Electrical isolationReinforced insulation in accordance with IEC 61010-1
Typical measuring error< 1 %
Protective circuitSurge protection; 33 V suppressor diode
Step response (0–99%)110 ms
Rated Insulation Voltage300 V

Measuring coil

Conductor structure signal line2x 0.22 mm (Signal (tinned))
Conductor structure signal line1x 0.22 mm (Shielding (tinned))
Insulationdouble insulation
Rated Insulation Voltage1000 V AC (rms CAT III)
Rated Insulation Voltage600 V AC (rms CAT IV)
Test voltage10.45 kV DC (60 s)
Basic accuracy<± 0.2 %

Measuring transducers

Maximum transmission error≤ 0.5 % (From the range end value)
Frequency Range16 Hz ... 1000 Hz
Test voltage3 kV (50 Hz, 1 min.)

General

Can be calibratedno
Class1
Accuracy class1
Converter typeRogowski coil and 4-way signal conditioner

Supply: Measuring transducers

Nominal Supply Voltage24 V DC
Nominal supply voltage range9.6 V DC ... 30 V DC
Power consumption≤ 1 W (at IOUT = 20 mA, 9.6 V DC, 600 Ω load)

Frequency

DesignationMeasuring coil
Frequency measuring range40 Hz ... 20000 Hz
Position error<± 0.1 % (typical)
Linearity error< 0.1 %

Signal

Input signal (at 50 Hz)100 mV (1000 A)
Curve typeSine
Input Impedance> 100 kΩ

Current transformers

Configurable/programmableVia DIP switches
Rated frequency: Standard converter40 Hz ... 20000 Hz
Primary rated current Ipn0 A AC ... 100 A AC
Primary rated current Ipn0 A AC ... 250 A AC
Primary rated current Ipn0 A AC ... 400 A AC
Primary rated current Ipn0 A AC ... 630 A AC
Primary rated current Ipn0 A AC ... 1000 A AC
Primary rated current Ipn0 A AC ... 1500 A AC
Primary rated current Ipn0 A AC ... 2000 A AC
Primary rated current Ipn0 A AC ... 4000 A AC
Can be calibratedno
Class1
Accuracy class1
Converter typeRogowski coil and 4-way signal conditioner

Switching: Transistor

Number of Outputs1
Contact switching type1 N/O contact
Minimum Switching Voltage1 V
Maximum Switching Voltage30 V DC
Min. switching current100 µA
Max. switching current100 mA (at 30 V)

Signal

DesignationMeasuring coil
Output signal (at 50 Hz)100 mV (no load, at 1,000 A)
Output voltage (in no-load operation)VOUT = M * dI/dt
Output voltage (sinusoidal, in no-load operation)100 mV (VOUT = 2 * π * M * f * I (M = 0.318 μH; example: At 50 Hz; I = 1,000 A))
Accuracy class1
DesignationMeasuring transducer
Configurable/programmableYes
Voltage output signal0 V ... 10 V (via DIP switch)
Voltage output signal2 V ... 10 V (via DIP switch)
Voltage output signal0 V ... 5 V (via DIP switch)
Voltage output signal1 V ... 5 V (via DIP switch)
Voltage output signal0 V ... 10.5 V (can be set via software)
Max. voltage output signal 12.3 V
Current Output Signal0 mA ... 20 mA (via DIP switch)
Current Output Signal4 mA ... 20 mA (via DIP switch)
Current Output Signal0 mA ... 10 mA (via DIP switch)
Current Output Signal2 mA ... 10 mA (via DIP switch)
Current Output Signal0 mA ... 21 mA (can be set via software)
Max. current output signal24.6 mA
Load/output load voltage output≥ 10 kΩ
Load/Output Load Current Output≤ 600 Ω (20 mA)
Ripple< 20 mVPP
Ripple< 20 mVPP

Measuring transducer side

Connection MethodPush-in connection
Stripping length10 mm
Conductor cross section rigid0.2 mm² ... 2.5 mm²
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section AWG26 ... 12

Item dimensions

Width6.2 mm
Height110.5 mm
Depth120.5 mm

Measuring coil

Length300 mm
Diameter8.3 mm ±0.2 mm

Measuring coil when installed

Diameter95 mm

Signal line

Length3 m
Width6.2 mm
Height110.5 mm
Depth120.5 mm

Material specifications

Housing MaterialPC
Housing MaterialPBT
Coil materialElastollan

Ambient conditions

Measuring coil degree of protectionIP67 (not assessed by UL)
Measuring transducer degree of protectionIP20
Ambient Temperature (Operation)-30 °C ... 80 °C (Measuring coil)
Ambient Temperature (Operation)-40 °C ... 70 °C (Measuring transducer)
Ambient temperature (storage/transport)-40 °C ... 80 °C (Measuring coil)
Ambient temperature (storage/transport)-40 °C ... 85 °C (Measuring transducer)
Altitude< 2000 m
Permissible humidity (operation)5 % ... 95 % (non-condensing)

CE

CertificateCE-compliant

UKCA

CertificateUKCA-compliant

CMIM

CertificateCMIM-compliant

UL, USA/Canada

IdentificationUL 61010 Recognized
NoteMeasuring coil
IdentificationUL 508 Listed
NoteMeasuring transducer

EMC data

Noise immunityEN 61000-6-2
NoteWhen being exposed to interference, there may be minimal deviations.
Electromagnetic compatibilityConformance with EMC directive
Noise emissionEN 61000-6-4

Standards and Regulations

Electrical isolationReinforced insulation in accordance with IEC 61010-1
Standards/regulationsIEC 61010-1
Standards/regulationsIEC 61010-2-032

Mounting

Mounting TypeDIN rail mounting
Accessories

Why Proax for Phoenix Contact PACT RCP-4000A-UIRO-PT-D95?

Proax is an authorized distributor of Phoenix Contact PACT RCP-4000A-UIRO-PT-D95 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information

Alternate NamesPACTRCP4000AUIROPTD95
Pack Size1
Recommended

Available for order