PACT RCP-4000A-1A-D190-3M-UV - Current transformer
Set consisting of one 1 A measuring transducer and one UV-resistant Rogowski coil with signal line. Length of Rogowski coil: 600 mm, diameter: 190 mm. Length of signal line: 3 m. The Rogowski coil measures the AC current of busbars and power lines.
Technical Specifications
Insulation characteristics
| Insulation | double insulation |
| Insulation | double insulation |
| Overvoltage category | III (1000 V, to neutral conductor) |
| Overvoltage category | IV (600 V, to neutral conductor) |
| Pollution degree | 2 |
Electrical properties
| Typical measuring error | < 1 % |
| Temperature coefficients | 0.005 %/K (+10 °C ... +70 °C, both components have the same ambient temperature) |
| Temperature coefficients | 0.07 %/K (-20 °C ... +10 °C, both components have the same ambient temperature) |
Measuring coil
| Length of measuring coil | 600 mm |
| Diameter of measuring coil | 8.3 mm ±0.2 mm |
| Length of signal cable | 3 m |
| Conductor structure signal line | 2x 0.22 mm (Signal (tinned)) |
| Conductor structure signal line | 1x 0.22 mm (Shielding (tinned)) |
| Insulation | double insulation |
| Rated Insulation Voltage | 1000 V AC (rms CAT III) |
| Rated Insulation Voltage | 600 V AC (rms CAT IV) |
| Test voltage | 10.45 kV (DC / 1 min.) |
| Basic accuracy | <± 0.21 % |
Measuring transducers
| Linearity error | < 0.5 % (From the range end value) |
| Maximum transmission error | ≤ 0.5 % (From the range end value) |
| Frequency Range | 45 Hz ... 65 Hz |
| Max. detectable harmonics | < 2 kHz |
| Current consumption | < 190 mA (at 19.2 V) |
| Test voltage | 1.5 kV AC (Supply/input and output: 50 Hz, 1 min) |
General
| Can be calibrated | no |
| Class | 1 |
| Accuracy class | 1 |
| Converter type | UV-resistant Rogowski coil and 1 A measuring transducer |
Supply: Measuring transducers
| Nominal Supply Voltage | 24 V DC -20 % ... +25 % |
| Nominal supply voltage range | 19.2 V DC ... 30 V DC |
| Max. current consumption | 190 mA |
| Power consumption | 4 W |
Frequency
| Designation | Measuring coil |
| Frequency measuring range | 40 Hz ... 20000 Hz |
| Position error | < 1 % |
| Linearity error | 0.1 % |
Signal
| Input signal (at 50 Hz) | 100 mV (1000 A) |
| Curve type | Sine |
| Input Impedance | 27 kΩ (smallest measuring range) |
Current transformers
| Configurable/programmable | Via DIP switches |
| Rated power | 1.5 VA |
| Primary rated current Ipn | 0 A AC ... 100 A AC |
| Primary rated current Ipn | 0 A AC ... 250 A AC |
| Primary rated current Ipn | 0 A AC ... 400 A AC |
| Primary rated current Ipn | 0 A AC ... 630 A AC |
| Primary rated current Ipn | 0 A AC ... 1000 A AC |
| Primary rated current Ipn | 0 A AC ... 1500 A AC |
| Primary rated current Ipn | 0 A AC ... 2000 A AC |
| Primary rated current Ipn | 0 A AC ... 4000 A AC |
| Phase angle | < 1 ° |
| Can be calibrated | no |
| Class | 1 |
| Accuracy class | 1 |
| Converter type | UV-resistant Rogowski coil and 1 A measuring transducer |
Signal
| Designation | Measuring coil |
| Output signal (at 50 Hz) | 100 mV (no load, at 1,000 A) |
| Output voltage (in no-load operation) | VOUT = M * dI/dt |
| Output voltage (sinusoidal, in no-load operation) | 100 mV (VOUT = 2 * π * M * f * I (M = 0.318 μH; example: At 50 Hz; I = 1,000 A)) |
| Accuracy class | < 1 |
| Designation | Measuring transducer |
| Current Output Signal | 0 A AC ... 1 A AC |
| Load | 0 Ω ... 1.5 Ω |
| Max. distances for copper cables at PN max | 32 m (0.75 mm² (AWG 20)) |
| Max. distances for copper cables at PN max | 64 m (1.5 mm² (AWG 16)) |
| Max. distances for copper cables at PN max | 107 m (2.5 mm² (AWG 14)) |
Measuring transducer side
| Connection Method | Screw connection |
| Stripping length | 7 mm |
| Screw thread | M3 |
| Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section AWG | 24 ... 14 |
| Tightening torque | 0.5 Nm ... 0.6 Nm |
Signaling
| Operating voltage display | Green LED |
Measuring coil
| Length | 600 mm |
| Diameter | 8.3 mm ±0.2 mm |
Measuring coil when installed
| Diameter | 190 mm |
Signal line
| Length | 3 m |
Material specifications
| Housing Material | PC |
| Housing Material | Polyamide |
| Coil material | Elastollan |
Ambient conditions
| Measuring coil degree of protection | IP67 (not assessed by UL) |
| Measuring transducer degree of protection | IP20 |
| Ambient Temperature (Operation) | -30 °C ... 80 °C (Measuring coil) |
| Ambient Temperature (Operation) | -20 °C ... 70 °C (Measuring transducer) |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C (Measuring coil) |
| Ambient temperature (storage/transport) | -25 °C ... 85 °C (Measuring transducer) |
| Altitude | < 2000 m |
| Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
UKCA
| Certificate | UKCA-compliant |
CMIM
| Certificate | CMIM-compliant |
UL, USA/Canada
| Identification | UL 508 Listed |
| Note | Measuring transducer |
Standards and Regulations
| Standards/regulations | IEC 61010-1 |
| Standards/regulations | IEC 61010-2-032 |
Mounting
| Mounting Type | DIN rail mounting |
Accessories
Why Proax for Phoenix Contact 1033485?
Proax is an authorized distributor of Phoenix Contact 1033485 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
| Pack Size | 1 |
Recommended
PACT RCP-4000A-UIRO-D140 - Set consisting of a 4-way signal conditioner with screw connection technology and a Rogowski coil 450 mm in length/140 mm in diameter for AC current measurement on busbars and power lines.The signal conditioner outputs 8 different standard signals on the output side and has one switching output.
PACT RCP-4000A-UIRO-D190 - Set consisting of a 4-way signal conditioner with screw connection technology and a Rogowski coil 600 mm in length/190 mm in diameter for AC current measurement on busbars and power lines.The signal conditioner outputs 8 different standard signals on the output side and has one switching output.
PACT RCP-4000A-UIRO-D95 - Set consisting of a 4-way signal conditioner with screw connection technology and a Rogowski coil 300 mm in length/95 mm in diameter for AC current measurement on busbars and power lines.The signal conditioner outputs 8 different standard signals on the output side and has one switching output.
PACT RCP-4000A-UIRO-PT-D140 - Set consisting of a 4-way signal conditioner with push-in connection technology and a Rogowski coil 450 mm in length/140 mm in diameter for AC current measurement on busbars and power lines.The signal conditioner outputs 8 different standard signals on the output side and has one switching output.
PACT RCP-4000A-UIRO-PT-D190 - Set consisting of a 4-way signal conditioner with push-in connection technology and a Rogowski coil 600 mm in length/190 mm in diameter for AC current measurement on busbars and power lines.The signal conditioner outputs 8 different standard signals on the output side and has one switching output.
PACT RCP-4000A-UIRO-PT-D95 - Set consisting of a 4-way signal conditioner with push-in connection technology and a Rogowski coil 300 mm in length/95 mm in diameter for AC current measurement on busbars and power lines.The signal conditioner outputs 8 different standard signals on the output side and has one switching output.