PACT RCP-4000A-1A-D190-3M-UV - Current transformer
Set consisting of one 1 A measuring transducer and one UV-resistant Rogowski coil with signal line. Length of Rogowski coil: 600 mm, diameter: 190 mm. Length of signal line: 3 m. The Rogowski coil measures the AC current of busbars and power lines.
Technical Specifications
Insulation characteristics
Insulation | double insulation |
Insulation | double insulation |
Overvoltage category | III (1000 V, to neutral conductor) |
Overvoltage category | IV (600 V, to neutral conductor) |
Pollution degree | 2 |
Electrical properties
Typical measuring error | < 1 % |
Temperature coefficients | 0.005 %/K (+10 °C ... +70 °C, both components have the same ambient temperature) |
Temperature coefficients | 0.07 %/K (-20 °C ... +10 °C, both components have the same ambient temperature) |
Measuring coil
Length of measuring coil | 600 mm |
Diameter of measuring coil | 8.3 mm ±0.2 mm |
Length of signal cable | 3 m |
Conductor structure signal line | 2x 0.22 mm (Signal (tinned)) |
Conductor structure signal line | 1x 0.22 mm (Shielding (tinned)) |
Insulation | double insulation |
Rated Insulation Voltage | 1000 V AC (rms CAT III) |
Rated Insulation Voltage | 600 V AC (rms CAT IV) |
Test voltage | 10.45 kV (DC / 1 min.) |
Basic accuracy | <± 0.21 % |
Measuring transducers
Linearity error | < 0.5 % (From the range end value) |
Maximum transmission error | ≤ 0.5 % (From the range end value) |
Frequency Range | 45 Hz ... 65 Hz |
Max. detectable harmonics | < 2 kHz |
Current consumption | < 190 mA (at 19.2 V) |
Test voltage | 1.5 kV AC (Supply/input and output: 50 Hz, 1 min) |
General
Can be calibrated | no |
Class | 1 |
Accuracy class | 1 |
Converter type | UV-resistant Rogowski coil and 1 A measuring transducer |
Supply: Measuring transducers
Nominal Supply Voltage | 24 V DC -20 % ... +25 % |
Nominal supply voltage range | 19.2 V DC ... 30 V DC |
Max. current consumption | 190 mA |
Power consumption | 4 W |
Frequency
Designation | Measuring coil |
Frequency measuring range | 40 Hz ... 20000 Hz |
Position error | < 1 % |
Linearity error | 0.1 % |
Signal
Input signal (at 50 Hz) | 100 mV (1000 A) |
Curve type | Sine |
Input Impedance | 27 kΩ (smallest measuring range) |
Current transformers
Configurable/programmable | Via DIP switches |
Rated power | 1.5 VA |
Primary rated current Ipn | 0 A AC ... 100 A AC |
Primary rated current Ipn | 0 A AC ... 250 A AC |
Primary rated current Ipn | 0 A AC ... 400 A AC |
Primary rated current Ipn | 0 A AC ... 630 A AC |
Primary rated current Ipn | 0 A AC ... 1000 A AC |
Primary rated current Ipn | 0 A AC ... 1500 A AC |
Primary rated current Ipn | 0 A AC ... 2000 A AC |
Primary rated current Ipn | 0 A AC ... 4000 A AC |
Phase angle | < 1 ° |
Can be calibrated | no |
Class | 1 |
Accuracy class | 1 |
Converter type | UV-resistant Rogowski coil and 1 A measuring transducer |
Signal
Designation | Measuring coil |
Output signal (at 50 Hz) | 100 mV (no load, at 1,000 A) |
Output voltage (in no-load operation) | VOUT = M * dI/dt |
Output voltage (sinusoidal, in no-load operation) | 100 mV (VOUT = 2 * π * M * f * I (M = 0.318 μH; example: At 50 Hz; I = 1,000 A)) |
Accuracy class | < 1 |
Designation | Measuring transducer |
Current Output Signal | 0 A AC ... 1 A AC |
Load | 0 Ω ... 1.5 Ω |
Max. distances for copper cables at PN max | 32 m (0.75 mm² (AWG 20)) |
Max. distances for copper cables at PN max | 64 m (1.5 mm² (AWG 16)) |
Max. distances for copper cables at PN max | 107 m (2.5 mm² (AWG 14)) |
Measuring transducer side
Connection Method | Screw connection |
Stripping length | 7 mm |
Screw thread | M3 |
Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section AWG | 24 ... 14 |
Tightening torque | 0.5 Nm ... 0.6 Nm |
Signaling
Operating voltage display | Green LED |
Measuring coil
Length | 600 mm |
Diameter | 8.3 mm ±0.2 mm |
Measuring coil when installed
Diameter | 190 mm |
Signal line
Length | 3 m |
Material specifications
Housing Material | PC |
Housing Material | Polyamide |
Coil material | Elastollan |
Ambient conditions
Measuring coil degree of protection | IP67 (not assessed by UL) |
Measuring transducer degree of protection | IP20 |
Ambient Temperature (Operation) | -30 °C ... 80 °C (Measuring coil) |
Ambient Temperature (Operation) | -20 °C ... 70 °C (Measuring transducer) |
Ambient temperature (storage/transport) | -40 °C ... 80 °C (Measuring coil) |
Ambient temperature (storage/transport) | -25 °C ... 85 °C (Measuring transducer) |
Altitude | < 2000 m |
Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
UKCA
Certificate | UKCA-compliant |
CMIM
Certificate | CMIM-compliant |
UL, USA/Canada
Identification | UL 508 Listed |
Note | Measuring transducer |
Standards and Regulations
Standards/regulations | IEC 61010-1 |
Standards/regulations | IEC 61010-2-032 |
Mounting
Mounting Type | DIN rail mounting |
Accessories
Why Proax for Phoenix Contact 1033485?
Proax is an authorized distributor of Phoenix Contact 1033485 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended
- 2906232 - Set consisting of a 4-way signal conditioner with screw connection technology and a Rogowski coil 450 mm in length/140 mm in diameter for AC current measurement on busbars and power lines.The signal conditioner outputs 8 different standard signals on the output side and has one switching output.
- 2906233 - Set consisting of a 4-way signal conditioner with screw connection technology and a Rogowski coil 600 mm in length/190 mm in diameter for AC current measurement on busbars and power lines.The signal conditioner outputs 8 different standard signals on the output side and has one switching output.
- 2906231 - Set consisting of a 4-way signal conditioner with screw connection technology and a Rogowski coil 300 mm in length/95 mm in diameter for AC current measurement on busbars and power lines.The signal conditioner outputs 8 different standard signals on the output side and has one switching output.
- 2906235 - Set consisting of a 4-way signal conditioner with push-in connection technology and a Rogowski coil 450 mm in length/140 mm in diameter for AC current measurement on busbars and power lines.The signal conditioner outputs 8 different standard signals on the output side and has one switching output.
- 2906236 - Set consisting of a 4-way signal conditioner with push-in connection technology and a Rogowski coil 600 mm in length/190 mm in diameter for AC current measurement on busbars and power lines.The signal conditioner outputs 8 different standard signals on the output side and has one switching output.
- 2906234 - Set consisting of a 4-way signal conditioner with push-in connection technology and a Rogowski coil 300 mm in length/95 mm in diameter for AC current measurement on busbars and power lines.The signal conditioner outputs 8 different standard signals on the output side and has one switching output.