PACT RCP-4000A-UIRO-D140 - Current transformer
Set consisting of a 4-way signal conditioner with screw connection technology and a Rogowski coil 450 mm in length/140 mm in diameter for AC current measurement on busbars and power lines.The signal conditioner outputs 8 different standard signals on the output side and has one switching output.
Technical Specifications
Insulation characteristics
Overvoltage category | II |
Pollution degree | 2 |
Electrical properties
Electrical isolation | Reinforced insulation in accordance with IEC 61010-1 |
Typical measuring error | < 1 % |
Protective circuit | Surge protection; 33 V suppressor diode |
Step response (0–99%) | 110 ms |
Rated Insulation Voltage | 300 V |
Measuring coil
Conductor structure signal line | 2x 0.22 mm (Signal (tinned)) |
Conductor structure signal line | 1x 0.22 mm (Shielding (tinned)) |
Insulation | double insulation |
Rated Insulation Voltage | 1000 V AC (rms CAT III) |
Rated Insulation Voltage | 600 V AC (rms CAT IV) |
Test voltage | 10.45 kV DC (60 s) |
Basic accuracy | <± 0.2 % |
Measuring transducers
Maximum transmission error | ≤ 0.5 % (From the range end value) |
Frequency Range | 16 Hz ... 1000 Hz |
Test voltage | 3 kV (50 Hz, 1 min.) |
General
Can be calibrated | no |
Class | 1 |
Accuracy class | 1 |
Converter type | Rogowski coil and 4-way signal conditioner |
Supply: Measuring transducers
Nominal Supply Voltage | 24 V DC |
Nominal supply voltage range | 9.6 V DC ... 30 V DC |
Power consumption | ≤ 1 W (at IOUT = 20 mA, 9.6 V DC, 600 Ω load) |
Frequency
Designation | Measuring coil |
Frequency measuring range | 40 Hz ... 20000 Hz |
Position error | <± 0.1 % (typical) |
Linearity error | < 0.1 % |
Signal
Input signal (at 50 Hz) | 100 mV (1000 A) |
Curve type | Sine |
Input Impedance | > 100 kΩ |
Current transformers
Configurable/programmable | Via DIP switches |
Rated frequency: Standard converter | 40 Hz ... 20000 Hz |
Primary rated current Ipn | 0 A AC ... 100 A AC |
Primary rated current Ipn | 0 A AC ... 250 A AC |
Primary rated current Ipn | 0 A AC ... 400 A AC |
Primary rated current Ipn | 0 A AC ... 630 A AC |
Primary rated current Ipn | 0 A AC ... 1000 A AC |
Primary rated current Ipn | 0 A AC ... 1500 A AC |
Primary rated current Ipn | 0 A AC ... 2000 A AC |
Primary rated current Ipn | 0 A AC ... 4000 A AC |
Can be calibrated | no |
Class | 1 |
Accuracy class | 1 |
Converter type | Rogowski coil and 4-way signal conditioner |
Switching: Transistor
Number of Outputs | 1 |
Contact switching type | 1 N/O contact |
Minimum Switching Voltage | 1 V |
Maximum Switching Voltage | 30 V DC |
Min. switching current | 100 µA |
Max. switching current | 100 mA (at 30 V) |
Signal
Designation | Measuring coil |
Output signal (at 50 Hz) | 100 mV (no load, at 1,000 A) |
Output voltage (in no-load operation) | VOUT = M * dI/dt |
Output voltage (sinusoidal, in no-load operation) | 100 mV (VOUT = 2 * π * M * f * I (M = 0.318 μH; example: At 50 Hz; I = 1,000 A)) |
Accuracy class | 1 |
Designation | Measuring transducer |
Configurable/programmable | Yes |
Voltage output signal | 0 V ... 10 V (via DIP switch) |
Voltage output signal | 2 V ... 10 V (via DIP switch) |
Voltage output signal | 0 V ... 5 V (via DIP switch) |
Voltage output signal | 1 V ... 5 V (via DIP switch) |
Voltage output signal | 0 V ... 10.5 V (can be set via software) |
Max. voltage output signal | 12.3 V |
Current Output Signal | 0 mA ... 20 mA (via DIP switch) |
Current Output Signal | 4 mA ... 20 mA (via DIP switch) |
Current Output Signal | 0 mA ... 10 mA (via DIP switch) |
Current Output Signal | 2 mA ... 10 mA (via DIP switch) |
Current Output Signal | 0 mA ... 21 mA (can be set via software) |
Max. current output signal | 24.6 mA |
Load/output load voltage output | ≥ 10 kΩ |
Load/Output Load Current Output | ≤ 600 Ω (20 mA) |
Ripple | < 20 mVPP |
Ripple | < 20 mVPP |
Measuring transducer side
Connection Method | Screw connection |
Stripping length | 10 mm |
Screw thread | M3 |
Conductor cross section rigid | 0.2 mm² ... 1.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 1.5 mm² |
Conductor cross section AWG | 26 ... 16 |
Tightening torque | 0.5 Nm ... 0.6 Nm |
Item dimensions
Width | 6.2 mm |
Height | 110.5 mm |
Depth | 120.5 mm |
Measuring coil
Length | 450 mm |
Diameter | 8.3 mm ±0.2 mm |
Measuring coil when installed
Diameter | 140 mm |
Signal line
Length | 3 m |
Width | 6.2 mm |
Height | 110.5 mm |
Depth | 120.5 mm |
Material specifications
Housing Material | PC |
Housing Material | PBT |
Coil material | Elastollan |
Ambient conditions
Measuring coil degree of protection | IP67 (not assessed by UL) |
Measuring transducer degree of protection | IP20 |
Ambient Temperature (Operation) | -30 °C ... 80 °C (Measuring coil) |
Ambient Temperature (Operation) | -40 °C ... 70 °C (Measuring transducer) |
Ambient temperature (storage/transport) | -40 °C ... 80 °C (Measuring coil) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C (Measuring transducer) |
Altitude | < 2000 m |
Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
CE
Certificate | CE-compliant |
UKCA
Certificate | UKCA-compliant |
CMIM
Certificate | CMIM-compliant |
UL, USA/Canada
Identification | UL 61010 Recognized |
Note | Measuring coil |
Identification | UL 508 Listed |
Note | Measuring transducer |
EMC data
Noise immunity | EN 61000-6-2 |
Note | When being exposed to interference, there may be minimal deviations. |
Electromagnetic compatibility | Conformance with EMC directive |
Noise emission | EN 61000-6-4 |
Standards and Regulations
Electrical isolation | Reinforced insulation in accordance with IEC 61010-1 |
Standards/regulations | IEC 61010-1 |
Standards/regulations | IEC 61010-2-032 |
Mounting
Mounting Type | DIN rail mounting |
Accessories
Why Proax for Phoenix Contact 2906232?
Proax is an authorized distributor of Phoenix Contact 2906232 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended
- 2906233 - Set consisting of a 4-way signal conditioner with screw connection technology and a Rogowski coil 600 mm in length/190 mm in diameter for AC current measurement on busbars and power lines.The signal conditioner outputs 8 different standard signals on the output side and has one switching output.
- 2906231 - Set consisting of a 4-way signal conditioner with screw connection technology and a Rogowski coil 300 mm in length/95 mm in diameter for AC current measurement on busbars and power lines.The signal conditioner outputs 8 different standard signals on the output side and has one switching output.
- 2906235 - Set consisting of a 4-way signal conditioner with push-in connection technology and a Rogowski coil 450 mm in length/140 mm in diameter for AC current measurement on busbars and power lines.The signal conditioner outputs 8 different standard signals on the output side and has one switching output.
- 2906236 - Set consisting of a 4-way signal conditioner with push-in connection technology and a Rogowski coil 600 mm in length/190 mm in diameter for AC current measurement on busbars and power lines.The signal conditioner outputs 8 different standard signals on the output side and has one switching output.
- 2906234 - Set consisting of a 4-way signal conditioner with push-in connection technology and a Rogowski coil 300 mm in length/95 mm in diameter for AC current measurement on busbars and power lines.The signal conditioner outputs 8 different standard signals on the output side and has one switching output.