Official Distributor
SKU
MPN
FL COMSERVER UNI 232/422/485-T
Weight
0.291 kg
This product is Not Cancellable/Not Returnable
Series FL-COMSERVER-UNI
Interface converters FL COMSERVER UNI 232/422/485-T
FL COMSERVER UNI...-T, version with extended temperature range (-40°C to +70°C). For converting a serial RS-232/RS-422/RS-485 interface to Ethernet, supports TCP, UDP, Modbus gateway, and PPP applications, including COM port redirector software.
- Extended temperature range, -40 °C ... +70 °C
- Modbus gateway between Modbus RTU / ASCII and Modbus/TCP
- All connections can be plugged in using a COMBICON screw terminal block
- Configuration via web-based management
- Software for virtual COM ports supplied as standard
Technical Specifications
Note
Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
Dimensions
Width | 45 mm |
Height | 99 mm |
Depth | 116 mm |
Ambient conditions
Ambient Temperature (Operation) | -40 °C ... 70 °C (free-standing, 40mm space on all sides) |
Ambient Temperature (Operation) | -40 °C ... 60 °C (Mounted in rows with zero spacing) |
Ambient temperature (storage/transport) | -40 °C ... 70 °C |
Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
Permissible humidity (storage/transport) | 5 % ... 95 % (non-condensing) |
Altitude | 5000 m (For restrictions see manufacturer's declaration) |
Degree of Protection | IP20 |
Noise immunity | EN 61000-6-2:2005 |
General
Electrical isolation | DIN EN 50178 (VCC // Ethernet // Serial) |
Test voltage data interface/data interface | 1.5 kVrms (50 Hz, 1 min.) |
Test voltage data interface/power supply | 1.5 kVrms |
Test voltage data interface/power supply | 1.5 kVrms (50 Hz, 1 min.) |
Standards/regulations | EN 50121-4 |
Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
Noise emission | EN 61000-6-4 |
Net weight | 188.888 g |
Color | green |
MTBF | 666 Years (Telcordia standard, 25°C temperature, 21% operating cycle (5 days a week, 8 hours a day)) |
MTBF | 179 Years (Telcordia standard, 40°C temperature, 34.25% operating cycle (5 days a week, 12 hours a day)) |
MTTF | 1973 Years (SN 29500 standard, temperature 25 °C, operating cycle 21 % (5 days a week, 8 hours a day)) |
MTTF | 854 Years (SN 29500 standard, temperature 40 °C, operating cycle 34.25 % (5 days a week, 12 hours a day)) |
MTTF | 348 Years (SN 29500 standard, temperature 40 °C, operating cycle 100 % (7 days a week, 24 hours a day)) |
Conformance | CE-compliant |
ATEX | II 3G Ex nA IIC T4 Gc X (Please follow the special installation instructions in the documentation!) |
Power supply
Supply Voltage Range | 12 V AC/DC ... 30 V AC/DC (observe derating) |
Typical current consumption | 100 mA (24 V DC) |
Serial interface
Interface 1 | Ethernet interface, 10/100Base-T(X) in acc. with IEEE 802.3u |
Interface | Ethernet |
No. of ports | 1 |
Connection Method | RJ45 socket, shielded |
Transmission length | ≤ 100 m (shielded twisted pair) |
Protocols Supported | TCP/IP, UDP, Modbus (TCP, RTU/ASCII), PPP |
Auxiliary protocols | ARP, DHCP, BOOTP, SNMP, RIP, RARP, HTTP, TFTP |
Data flow control/protocols | Modbus/TCP |
Serial transmission speed | 10/100 Mbps, auto negotiation |
Interface 2 | V.24 (RS-232) interface in acc. with ITU-T V.28, EIA/TIA-232, DIN 66259-1 |
Interface | RS-232 |
Connection Method | D-SUB 9 plug |
File format/coding | UART/NRZ: 7/8 Bit Data, 1/2 Bit Stopp, None/Even/Odd Parity |
Transmission length | 15 m |
Pin assignment | DTE/DCE switchover via web-based management |
Data flow control/protocols | Software handshake, Xon/Xoff, or hardware handshake RTS/CTS // 3964 R compatible, Modbus RTU/ASCII |
Serial transmission speed | 0.3; 0.6; 1.2; 2.4; 4.8; 7.2; 9.6; 19.2; 38.4; 57.6; 115.2; 187.5; 230.4 kbps |
Interface 3 | RS-422 interface in acc. with ITU-T V.11, EIA/TIA-422, DIN 66348-1 |
Interface | RS-422 |
Connection Method | Plug-in/screw connection via COMBICON |
File format/coding | UART/NRZ: 7/8 Bit Data, 1/2 Bit Stopp, None/Even/Odd Parity |
Transmission length | ≤ 1200 m |
Termination resistor | 390 Ω (configurable) |
Termination resistor | 180 Ω |
Termination resistor | 390 Ω |
Data flow control/protocols | Automatic control |
Serial transmission speed | 0.3; 0.6; 1.2; 2.4; 4.8; 7.2; 9.6; 19.2; 38.4; 57.6; 115.2; 187.5; 230.4; 500; 1000 kbps |
Interface 4 | RS-485 interface, in acc. with EIA/TIA-485, DIN 66259-4/RS-485 2-wire |
Interface | RS-485 |
Connection Method | Plug-in/screw connection via COMBICON |
File format/coding | UART/NRZ: 7/8 Bit Data, 1/2 Bit Stopp, None/Even/Odd Parity |
Termination resistor | 390 Ω |
Termination resistor | 180 Ω |
Termination resistor | 390 Ω (configurable) |
Data flow control/protocols | Automatic control |
Serial transmission speed | 0.3; 0.6; 1.2; 2.4; 4.8; 7.2; 9.6; 19.2; 38.4; 57.6; 115.2; 187.5; 230.4; 500; 1000 kbps |
Function
Web-based management | yes |
Management | Web-based management, SNMP, emergency exit with Telnet and serial |
Status and diagnostic indicators | LEDs: UL (logic voltage), TD + RD (data activity serial), FD (full duplex), 100 (100 Mbps mode), Link (Ethernet), Activity (Ethernet), ERR (error) |
Standards and Regulations
Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
Type of test | Free fall in acc. with IEC 60068-2-32 |
Test result | 1 m |
Type of test | Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 |
Test result | 5g, 10...150 Hz, 2.5 h, in XYZ direction |
Type of test | Shock in acc. with EN 60068-2-27/IEC 60068-2-27 |
Test result | 15g, 11 ms period, half-sine shock pulse |
Type of test | Shock in acc. with EN 60068-2-27/IEC 60068-2-27 |
Test result | 30g, 11 ms period, half-sine shock pulse |
Noise emission | EN 61000-6-4 |
Noise immunity | EN 61000-6-2:2005 |
Free from substances that could impair the application of coating | according to P-VW 3.10.7 57 65 0 VW-AUDI-Seat central standard |
Standards/regulations | EN 50121-4 |
Conformance | CE-compliant |
ATEX | II 3G Ex nA IIC T4 Gc X |
Noxious gas test | ISA-S71.04-1985 G3 Harsh Group A |
Environmental Product Compliance
REACh SVHC | Lead 7439-92-1 |
China RoHS | Environmentally Friendly Use Period = 50 |
China RoHS | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
Accessories
- 2881007 - Surge protection in accordance with Class EA (CAT6A), for Gigabit Ethernet (up to 10 Gbps), token ring, FDDI/CDDI, ISDN, and DS1. Suitable for Power over Ethernet (PoE++ / 4PPoE) “Mode A” and “Mode B”. RJ45 attachment plug with separate grounding cable and ground connection snap-on foot for NS 35 DIN rails.
Why Proax for Phoenix Contact 2904817?
Proax is an authorized distributor of Phoenix Contact 2904817 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended