SKU
MPN
AXL F EX IS DO4 SD 21-60 XC 1F
Weight
0.39 kg
Series AXL-F-EX-IS-DO
AXL F EX IS DO4 SD 21-60 XC 1F - Digital module
Axioline F, Digital output module, Digital outputs: 4, 21 V, connection technology: 2-conductor, Extreme conditions version, Intrinsically safe, Solenoid drive, transmission speed in the local bus: 100 Mbps, degree of protection: IP20, including bus base module and Axioline F connectors
- Four 21 V DC - 60 mA digital output-powered control signals for solenoid drives
- Intrinsically safe digital outputs with connection to Zone 1, Zone 0 or Division 1
- Can be used under extreme ambient conditions
- Extended temperature range of -40 °C ... +70 °C (see “Tested successfully: use under extreme ambient conditions” in the data sheet)
Technical Specifications
Dimensions
Width | 53.6 mm |
Height | 129.9 mm |
Depth | 77.14 mm |
Note on dimensions | The depth applies when a TH 35-7.5 DIN rail is used (in accordance with EN 60715). |
Utilization restriction
EMC note | EMC: class A product, see manufacturer's declaration in the download area |
CCCex note | Use in potentially explosive areas is not permitted in China. |
Material specifications
Color | traffic grey A RAL 7042 |
Axioline F local bus
No. of channels | 2 |
Connection Method | Bus base module |
Transmission Speed | 100 Mbps |
Module
Input address area | 0 Byte |
Output address area | 1 Byte |
Required parameter data | 12 Byte |
Required configuration data | 6 Byte |
Digital:
Output name | Digital outputs |
Connection Method | Push-in connection |
Connection technology | 2-conductor |
Number of Outputs | 4 |
Output Voltage | 21 V |
Maximum Output Current per channel | 60 mA |
Nominal Output Voltage | 21 V |
Product properties
Product family | Axioline F |
Type | block modular |
Scope of delivery | including bus base module and Axioline F connectors |
Special Properties | Solenoid drive |
Special Properties | Extreme conditions version |
Special Properties | Intrinsically safe |
Potentials: Axioline F local bus supply (UBus)
Supply Voltage | 5 V DC (via bus base module) |
Current draw | max. 60 mA |
Current draw | typ. 40 mA |
Potentials: Supply for digital output modules (UO)
Supply Voltage | 24 V DC |
Supply Voltage Range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
Current draw | max. 420 mA |
Electrical isolation/isolation of the voltage ranges
Test voltage: 5 V supply of the local bus (UBus) / 24 V supply (I/Os) | 500 V AC, 50 Hz, 1 min. |
Test voltage: 5 V supply of the local bus (UBus) / functional ground | 500 V AC, 50 Hz, 1 min. |
Test voltage: 24 V supply (I/O) / functional ground | 500 V AC, 50 Hz, 1 min. |
Test voltage: Field to functional earth | 500 V AC, 50 Hz, 1 min. |
Test voltage: Field to 5V or 24V supplies | 1500 V AC, 50 Hz, 1 min. |
Connection technology
Connection name | Axioline F connector |
Note on the connection method | Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual. |
Conductor connection
Connection Method | Push-in connection |
Conductor cross section rigid | 0.2 mm² ... 1.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 1.5 mm² |
Conductor cross section AWG | 24 ... 16 |
Stripping length | 8 mm |
Axioline F connector
Connection Method | Push-in connection |
Note on the connection method | Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual. |
Conductor cross section, rigid | 0.2 mm² ... 1.5 mm² |
Conductor cross section, flexible | 0.2 mm² ... 1.5 mm² |
Conductor cross section AWG | 24 ... 16 |
Stripping length | 8 mm |
Ambient conditions
Ambient Temperature (Operation) | -25 °C ... 60 °C (Standard) |
Ambient Temperature (Operation) | -40 °C ... 70 °C (Extended, see section “Tested successfully: use under extreme ambient conditions” in the data sheet.) |
Degree of Protection | IP20 |
Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
Permissible humidity (storage/transport) | 5 % ... 95 % (non-condensing) |
Standards and Regulations
Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
ATEX
Identification | II 3(1) G Ex ec [ia IIB Ga] IIC T4 GcII (1) D [Ex ia Da] IIIC |
Certificate | DEMKO 20 ATEX 2370X |
IECEx
Identification | Ex ec [ia IIB Ga] IIC T4 Gc[Ex ia Da] IIIC |
Certificate | IECEx UL 20.0044X |
UKCA Ex (UKEX)
Identification | II 3(1) G Ex ec [ia IIB Ga] IIC T4 GcII (1) D [Ex ia Da] IIIC |
Certificate | UL22UKEX2508X |
Ex data
UL, USA / Canada | Ind. Cont. Eq. (E238705) also ListedInd. Cont. Eq. for haz. loc. E196811Install in: Class I, Div. 2, Groups A, B, C, D T4Intrinsically safe outputs for: Class I, Groups C, D; Class II, Groups E, F, G; Class III; [Ex ia] Haz locClass I, Zone 2, AEx ec [ia IIB Ga] IIC T4 Gc[AEx ia Da] IIICEx ec [ia IIB Ga] IIC T4 Gc[Ex ia Da] IIIC |
Mounting
Mounting Type | DIN rail mounting |
Safety data
Max. output voltage Uo | 24.8 V |
Max. output current Io | 180 mA |
Max. output power Po | 1116 mW |
Safety-related maximum voltage Um | 250 V |
C/IIB, IIIC: Max. external inductivity Lo / Max. external capacitance Co | / 0.86 µF |
D/IIA, E, F, G, Class III: Max. external inductivity Lo / Max. external capacitance Co | / 3.05 µF |
C/IIB, IIIC: Max. external inductivity Lo / Max. external capacitance Co | 2.779 mH |
D/IIA, E, F, G, Class III: Max. external inductivity Lo / Max. external capacitance Co | 7.168 mH |
Why Proax for Phoenix Contact 1086902?
Proax is an authorized distributor of Phoenix Contact 1086902 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended
- AXL F EX IS DI16 NAM XC 1F - Axioline F, Digital input module, Digital inputs: 16 (NAMUR), 8 V DC, connection technology: 2-conductor, Extreme conditions version, Intrinsically safe, transmission speed in the local bus: 100 Mbps, degree of protection: IP20, including bus base module and Axioline F connectors
- Axioline F, Analog output module, Analog outputs: 4 (HART), 0 mA ... 20 mA, 4 mA ... 20 mA, connection technology: 2-conductor, transmission speed in the local bus: 100 Mbps, Extreme conditions version, intrinsically safe, HART functionality, degree of protection: IP20, including bus base module and Axioline F connectors
- Axioline F, Analog input module, Active analog inputs: 8 (HART), 4 mA ... 20 mA, connection technology: 2-conductor, transmission speed in the local bus: 100 Mbps, Extreme conditions version, intrinsically safe, HART functionality, degree of protection: IP20, including bus base module and Axioline F connectors