Official Distributor
SKU
MPN
IB IL TEMP 2 UTH-XC-PAC
Weight
0.099 kg
Series IB-IL-TEMP
IB IL TEMP 2 UTH-XC-PAC - Temperature module
Inline, Temperature measurement terminal, Analog UTH inputs: 2 (Thermocouples or linear voltage), connection technology: 2-conductor, transmission speed in the local bus: 500 kbps, Extreme conditions version, degree of protection: IP20, including Inline connector and labeling field
- 2 differential inputs for thermocouples or linear voltage
- 1 input for an external cold junction, Pt 1000 or Ni 1000
- The channels are parameterized independently of one another via the bus system
- Internal detection and compensation of cold junction temperature (can be parameterized)
- Absolute and differential temperature measurement (can be parameterized)
- Pt 1000 sensor in the vicinity of the connection terminal blocks of the thermocouple inputs for internal measurement of the cold junction temperature
- Measured values can be represented in three different formats
- Can be used under extreme ambient conditions
- Extended temperature range of -40 °C ... +70 °C (see “Tested successfully: use under extreme ambient conditions” in the data sheet)
- Coated PCBs
Technical Specifications
Dimensions
Width | 12.2 mm |
Height | 136.8 mm |
Depth | 71.5 mm |
Note on dimensions | Housing dimensions |
Inline local bus
Number of interfaces | 2 |
Connection Method | Inline data jumper |
Transmission Speed | 500 kbps |
Module
ID code (dec.) | 127 |
ID code (hex) | 7F |
Length code (hex) | 02 |
Length code (dec) | 02 |
Process data channel | 32 bit |
Input address area | 4 Byte |
Output address area | 4 Byte |
Register length | 32 bit |
Required parameter data | 6 Byte |
Required configuration data | 4 Byte |
Analog
Input name | Analog UTH inputs |
Description of the input | Inputs for thermocouples or linear voltage |
Number of Inputs | 2 (Thermocouples or linear voltage) |
Connection Method | Inline connector |
Connection technology | 2-conductor |
Note regarding the connection technology | Shielded compensating line for TC with encapsulated sensors |
A/D conversion time | typ. 120 µs (per channel) |
Sensor types that can be used (TC) | U, T, L, J, E, K, N, S, R, B, C, W, HK |
Measuring Principle | Successive approximation |
Measured value representation | 16 bits (15 bits + sign bit) |
Process data update | max. 30 ms (For both channels) |
Protective circuit | Surge protection (TC channels); up to ±40 V |
Product properties
Product family | Inline |
Type | modular |
Scope of delivery | including Inline connector and labeling field |
Operating mode | Process data operation with 2 words |
Special Properties | Extreme conditions version |
Diagnostics messages | Failure of the internal I/O supply I/O error message sent to the bus coupler |
Diagnostics messages | Failure of or insufficient communications power UL I/O error message sent to the bus coupler |
Diagnostics messages | I/O error Error message in the process data |
Diagnostics messages | User error Error message in the process data |
Insulation characteristics
Overvoltage category | II (IEC 60664-1, EN 60664-1) |
Pollution degree | 2 (IEC 60664-1, EN 60664-1) |
Potentials
Power consumption | typ. 587 mW |
Power consumption | max. 882 mW |
Potentials: Communications power (UL)
Supply Voltage | 7.5 V DC (via voltage jumper) |
Current draw | max. 60 mA |
Current draw | typ. 43 mA |
Potentials: Supply of analog modules (UANA)
Supply Voltage | 24 V DC (via voltage jumper) |
Supply Voltage Range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
Current draw | max. 18 mA |
Current draw | typ. 11 mA |
Electrical isolation/isolation of the voltage ranges
Test voltage: 7.5 V supply (bus logics)/24 V analog supply (analog I/O) | 500 V AC, 50 Hz, 1 min. |
Test voltage: 7.5 V supply (bus logic)/functional ground | 500 V AC, 50 Hz, 1 min. |
Test voltage: 24 V analog supply (analog I/O)/functional ground | 500 V AC, 50 Hz, 1 min. |
Connection technology
Connection name | Inline connector |
Conductor connection
Connection Method | Spring-cage connection |
Conductor cross section rigid | 0.08 mm² ... 1.5 mm² |
Conductor cross section flexible | 0.08 mm² ... 1.5 mm² |
Conductor cross section AWG | 28 ... 16 |
Stripping length | 8 mm |
Inline connector
Connection Method | Spring-cage connection |
Conductor cross section, rigid | 0.08 mm² ... 1.5 mm² |
Conductor cross section, flexible | 0.08 mm² ... 1.5 mm² |
Conductor cross section AWG | 28 ... 16 |
Stripping length | 8 mm |
Ambient conditions
Ambient Temperature (Operation) | -25 °C ... 55 °C (Standard) |
Ambient Temperature (Operation) | -40 °C ... 70 °C (Extended, see section “Tested successfully: use under extreme ambient conditions” in the data sheet.) |
Degree of Protection | IP20 |
Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
Permissible humidity (storage/transport) | 10 % ... 95 % (non-condensing) |
Standards and Regulations
Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
Mounting
Mounting Type | DIN rail mounting |
Accessories
- Paire de blocs de jonction pour tension thermoélectrique, TC type E, tension nominale: 400 V, intensité nominale: 1 A, nombre de connexions: 4, nombre de pôles: 2, type de raccordement: Raccordement vissé, 1er étage, section : 0,2 mm2 - 4 mm2, type de montage: NS 35/7,5, NS 35/15, NS 32, coloris: gris
Why Proax for Phoenix Contact 2701216?
Proax is an authorized distributor of Phoenix Contact 2701216 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended