Official Distributor
SKU
MPN
IB IL TEMP 8 UTH/RTD-PAC
Weight
0.234 kg
This product is Not Cancellable/Not Returnable
Series IB-IL-TEMP
IB IL TEMP 8 UTH/RTD-PAC - Temperature module
Inline analog input terminal, complete with accessories (connector and marking field), 8 channels, TC (thermocouple), RTD (resistance temperature detector), 2 and 3-conductor connection technology
- 8 temperature sensor inputs
- 3-conductor connection for resistance temperature detectors (Pt 100, Ni 100, Pt 1000, Ni 1000, and others)
- 2-conductor connection for thermocouples
- Internal and external detection and compensation of cold junction temperature (configurable)
- Individual current input, 1 A for total current transformer for heating current monitoring
- Scan time: 20 ms (for all channels)
- Maximum 50 Hz/60 Hz suppression
- High precision and noise immunity
- Temperature stability
- High-resolution temperature, voltage, and resistance measurement
- Resistance values (R0) can be preset separately by means of parameterization
- Channels are parameterized independently of one another
- Diagnostic and status indicators
- Channel scout functionality, for optical channel identification during startup
Technical Specifications
Dimensions
Width | 48.8 mm |
Height | 119.8 mm |
Depth | 71.5 mm |
Inline local bus
Connection Method | Inline data jumper |
Transmission Speed | 500 kbps |
Transmission physics | Copper |
Module
ID code (dec.) | 220 |
ID code (hex) | DC |
Length code (hex) | 0A |
Length code (dec) | 10 |
Process data channel | 160 bit |
Input address area | 20 Byte |
Output address area | 20 Byte |
Register length | 192 bit |
Required parameter data | 25 Byte |
Required configuration data | 5 Byte |
Analog
Input name | Analog RTD inputs |
Description of the input | Temperature sensor inputs |
Number of Inputs | 8 |
Connection Method | Spring-cage connection |
Connection technology | 2-, 3-conductor |
A/D converter resolution | 16 bit |
Sensor types (RTD) that can be used | Pt, Ni sensors, linear resistors |
Sensor types that can be used (TC) | B, C, E, J, K, L, N, R, S, T, U, mV input |
Data formats | IB IL, S7-compatible |
Measuring Principle | Successive approximation |
Measured value representation | 16 bits (15 bits + sign bit) |
Process data update | 20 ms (with filter time of 20 ms or 100 ms) |
Process data update | 100 ms (with filter time of 400 ms or 1600 ms) |
Product properties
Product family | Inline |
Type | modular |
Scope of delivery | including Inline connectors and marking fields |
Operating mode | Process data mode with 10 words, PCP with 2 words |
Insulation characteristics
Overvoltage category | II (IEC 60664-1, EN 60664-1) |
Pollution degree | 2 (IEC 60664-1, EN 60664-1) |
Potentials
Power consumption | typ. 1.15 W |
Potentials: Communications power (UL)
Supply Voltage | 7.5 V DC (via voltage jumper) |
Current draw | max. 100 mA |
Current draw | typ. 90 mA |
Potentials: Supply of analog modules (UANA)
Supply Voltage | 24 V DC (via voltage jumper) |
Supply Voltage Range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
Current draw | typ. 24 mA |
Electrical isolation/isolation of the voltage ranges
Test voltage: 5 V supply, incoming remote bus/7.5 V supply (bus logics) | 500 V AC, 50 Hz, 1 min. |
Test voltage: 5 V supply, outgoing remote bus/7.5 V supply (bus logics) | 500 V AC, 50 Hz, 1 min. |
Test voltage: 7.5 V supply (bus logic), 24 V supply UANA / I/O | 500 V AC, 50 Hz, 1 min. |
Connection technology
Connection name | Inline connector |
Conductor connection
Connection Method | Spring-cage connection |
Conductor cross section rigid | 0.08 mm² ... 1.5 mm² |
Conductor cross section flexible | 0.08 mm² ... 1.5 mm² |
Conductor cross section AWG | 28 ... 16 |
Stripping length | 8 mm |
Inline connector
Connection Method | Spring-cage connection |
Conductor cross section, rigid | 0.08 mm² ... 1.5 mm² |
Conductor cross section, flexible | 0.08 mm² ... 1.5 mm² |
Conductor cross section AWG | 28 ... 16 |
Stripping length | 8 mm |
Ambient conditions
Ambient Temperature (Operation) | -25 °C ... 60 °C |
Degree of Protection | IP20 |
Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Ambient temperature (storage/transport) | -25 °C ... 85 °C |
Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
Permissible humidity (storage/transport) | 10 % ... 95 % (non-condensing) |
Standards and Regulations
Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
Mounting
Mounting Type | DIN rail mounting |
Accessories
Why Proax for Phoenix Contact 2701000?
Proax is an authorized distributor of Phoenix Contact 2701000 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended