Proax

Currency
0 Items
proax logo
Cart
Phoenix ContactOfficial Distributor

By Phoenix Contact

SKU
MPN
IB IL TEMP 8 UTH/RTD-PAC
Weight
0.234 kg
This product is Not Cancellable/Not Returnable
Series IB-IL-TEMP

IB IL TEMP 8 UTH/RTD-PAC - Temperature module

Inline analog input terminal, complete with accessories (connector and marking field), 8 channels, TC (thermocouple), RTD (resistance temperature detector), 2 and 3-conductor connection technology

  • 8 temperature sensor inputs
  • 3-conductor connection for resistance temperature detectors (Pt 100, Ni 100, Pt 1000, Ni 1000, and others)
  • 2-conductor connection for thermocouples
  • Internal and external detection and compensation of cold junction temperature (configurable)
  • Individual current input, 1 A for total current transformer for heating current monitoring
  • Scan time: 20 ms (for all channels)
  • Maximum 50 Hz/60 Hz suppression
  • High precision and noise immunity
  • Temperature stability
  • High-resolution temperature, voltage, and resistance measurement
  • Resistance values (R0) can be preset separately by means of parameterization
  • Channels are parameterized independently of one another
  • Diagnostic and status indicators
  • Channel scout functionality, for optical channel identification during startup
Technical Specifications

Dimensions

Width48.8 mm
Height119.8 mm
Depth71.5 mm

Inline local bus

Connection MethodInline data jumper
Transmission Speed500 kbps
Transmission physicsCopper

Module

ID code (dec.)220
ID code (hex)DC
Length code (hex)0A
Length code (dec)10
Process data channel160 bit
Input address area20 Byte
Output address area20 Byte
Register length192 bit
Required parameter data 25 Byte
Required configuration data 5 Byte

Analog

Input nameAnalog RTD inputs
Description of the inputTemperature sensor inputs
Number of Inputs8
Connection MethodSpring-cage connection
Connection technology2-, 3-conductor
A/D converter resolution16 bit
Sensor types (RTD) that can be usedPt, Ni sensors, linear resistors
Sensor types that can be used (TC)B, C, E, J, K, L, N, R, S, T, U, mV input
Data formatsIB IL, S7-compatible
Measuring PrincipleSuccessive approximation
Measured value representation16 bits (15 bits + sign bit)
Process data update20 ms (with filter time of 20 ms or 100 ms)
Process data update100 ms (with filter time of 400 ms or 1600 ms)

Product properties

Product familyInline
Typemodular
Scope of deliveryincluding Inline connectors and marking fields
Operating modeProcess data mode with 10 words, PCP with 2 words

Insulation characteristics

Overvoltage categoryII (IEC 60664-1, EN 60664-1)
Pollution degree2 (IEC 60664-1, EN 60664-1)

Potentials

Power consumptiontyp. 1.15 W

Potentials: Communications power (UL)

Supply Voltage7.5 V DC (via voltage jumper)
Current drawmax. 100 mA
Current drawtyp. 90 mA

Potentials: Supply of analog modules (UANA)

Supply Voltage24 V DC (via voltage jumper)
Supply Voltage Range19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current drawtyp. 24 mA

Electrical isolation/isolation of the voltage ranges

Test voltage: 5 V supply, incoming remote bus/7.5 V supply (bus logics)500 V AC, 50 Hz, 1 min.
Test voltage: 5 V supply, outgoing remote bus/7.5 V supply (bus logics)500 V AC, 50 Hz, 1 min.
Test voltage: 7.5 V supply (bus logic), 24 V supply UANA / I/O500 V AC, 50 Hz, 1 min.

Connection technology

Connection nameInline connector

Conductor connection

Connection MethodSpring-cage connection
Conductor cross section rigid0.08 mm² ... 1.5 mm²
Conductor cross section flexible0.08 mm² ... 1.5 mm²
Conductor cross section AWG28 ... 16
Stripping length8 mm

Inline connector

Connection MethodSpring-cage connection
Conductor cross section, rigid0.08 mm² ... 1.5 mm²
Conductor cross section, flexible0.08 mm² ... 1.5 mm²
Conductor cross section AWG28 ... 16
Stripping length8 mm

Ambient conditions

Ambient Temperature (Operation)-25 °C ... 60 °C
Degree of ProtectionIP20
Air pressure (operation)70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)70 kPa ... 106 kPa (up to 3000 m above sea level)
Ambient temperature (storage/transport)-25 °C ... 85 °C
Permissible humidity (operation)10 % ... 95 % (non-condensing)
Permissible humidity (storage/transport)10 % ... 95 % (non-condensing)

Standards and Regulations

Protection classIII (IEC 61140, EN 61140, VDE 0140-1)

Mounting

Mounting TypeDIN rail mounting
Accessories

Why Proax for Phoenix Contact 2701000?

Proax is an authorized distributor of Phoenix Contact 2701000 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information

Pack Size1
Recommended

Available for order

Phoenix Contact Availability