2861328
SKU
PHX2861328
MPN
IB IL TEMP 2 RTD-PAC
Weight
0.096 kg
Series IB-IL-TEMP
IB IL TEMP 2 RTD-PAC - Temperature module
Inline, Temperature measurement terminal, Analog RTD inputs: 2, connection technology: 2-, 3-, 4-conductor, transmission speed in the local bus: 500 kbps, degree of protection: IP20, including Inline connector and labeling field
- 2 inputs for resistive temperature sensors
- Pt, Ni, Cu, KTY sensor types according to DIN and SAMA
- Connection of sensors in 2-, 3-, and 4-conductor technology
- The channels are parameterized independently of one another via the bus system
- Measured values can be represented in three different formats
- Measured value acquisition with a resolution of 16 bits
Technical Specifications
Dimensions
| Width | 12.2 mm |
| Height | 136.8 mm |
| Depth | 71.5 mm |
Utilization restriction
| CCCex note | Use in potentially explosive areas is not permitted in China. |
Inline local bus
| Number of interfaces | 2 |
| Connection Method | Inline data jumper |
| Transmission Speed | 500 kbps |
Module
| ID code (dec.) | 127 |
| ID code (hex) | 7F |
| Length code (hex) | 02 |
| Length code (dec) | 02 |
| Process data channel | 32 bit |
| Input address area | 4 Byte |
| Output address area | 4 Byte |
| Register length | 32 bit |
| Required parameter data | 6 Byte |
| Required configuration data | 4 Byte |
Analog
| Input name | Analog RTD inputs |
| Description of the input | Input for resistive temperature sensors |
| Number of Inputs | 2 |
| Connection Method | Spring-cage connection |
| Connection technology | 2-, 3-, 4-conductor |
| Note regarding the connection technology | shielded |
| A/D conversion time | typ. 120 µs (per channel) |
| A/D converter resolution | 16 bit |
| Sensor types (RTD) that can be used | Pt, Ni, KTY, Cu sensors, linear resistors |
| Measuring Principle | Successive approximation |
| Measured value representation | 16 bit two's complement |
| Linear resistance measuring range | 0 Ω ... 400 Ω |
| Linear resistance measuring range | 0 Ω ... 4 kΩ |
| Process data update | 32 ms (both channels use 3-conductor technology) |
| Process data update | 20 ms (one channel in 2-conductor technology and one channel in 4-conductor technology) |
| Process data update | 20 ms (both channels in 2-conductor technology) |
Product properties
| Product family | Inline |
| Type | modular |
| Scope of delivery | including Inline connector and labeling field |
| Operating mode | Process data operation with 2 words |
| Diagnostics messages | Failure of the internal I/O supply I/O error message sent to the bus coupler |
| Diagnostics messages | Failure of or insufficient communications power UL I/O error message sent to the bus coupler |
| Diagnostics messages | I/O error Error message in the process data |
| Diagnostics messages | User error Error message in the process data |
Insulation characteristics
| Overvoltage category | II (IEC 60664-1, EN 60664-1) |
| Pollution degree | 2 (IEC 60664-1, EN 60664-1) |
Electrical properties
| Maximum power dissipation for nominal condition | 0.59 W |
Potentials
| Power consumption | typ. 587 mW |
| Power consumption | max. 882 mW |
Potentials: Communications power (UL)
| Supply Voltage | 7.5 V DC (via voltage jumper) |
| Current draw | max. 60 mA |
| Current draw | typ. 43 mA |
Potentials: Supply of analog modules (UANA)
| Supply Voltage | 24 V DC (via voltage jumper) |
| Supply Voltage Range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Current draw | max. 18 mA |
| Current draw | typ. 11 mA |
Electrical isolation/isolation of the voltage ranges
| Test voltage: 7.5 V supply (bus logics)/24 V analog supply (analog I/O) | 500 V AC, 50 Hz, 1 min. |
| Test voltage: 7.5 V supply (bus logic)/functional ground | 500 V AC, 50 Hz, 1 min. |
| Test voltage: 24 V analog supply (analog I/O)/functional ground | 500 V AC, 50 Hz, 1 min. |
Connection technology
| Connection name | Inline connector |
Conductor connection
| Connection Method | Spring-cage connection |
| Conductor cross section rigid | 0.08 mm² ... 1.5 mm² |
| Conductor cross section flexible | 0.08 mm² ... 1.5 mm² |
| Conductor cross section AWG | 28 ... 16 |
| Stripping length | 8 mm |
Inline connector
| Connection Method | Spring-cage connection |
| Conductor cross section, rigid | 0.08 mm² ... 1.5 mm² |
| Conductor cross section, flexible | 0.08 mm² ... 1.5 mm² |
| Conductor cross section AWG | 28 ... 16 |
| Stripping length | 8 mm |
Ambient conditions
| Ambient Temperature (Operation) | -25 °C ... 55 °C |
| Degree of Protection | IP20 |
| Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Ambient temperature (storage/transport) | -25 °C ... 85 °C |
| Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
| Permissible humidity (storage/transport) | 10 % ... 95 % (non-condensing) |
Standards and Regulations
| Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
Mounting
| Mounting Type | DIN rail mounting |
Accessories
Why Proax for Phoenix Contact 2861328?
Proax is an authorized distributor of Phoenix Contact 2861328 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
| Pack Size | 1 |
Recommended
IB IL TEMP 2 UTH-XC-PAC - Inline, Temperature measurement terminal, Analog UTH inputs: 2 (Thermocouples or linear voltage), connection technology: 2-conductor, transmission speed in the local bus: 500 kbps, Extreme conditions version, degree of protection: IP20, including Inline connector and labeling field