Official Distributor
SKU
MPN
IB IL TEMP 2 RTD-XC-PAC
Weight
0.095 kg
This product is Not Cancellable/Not Returnable
Series IB-IL-TEMP
IB IL TEMP 2 RTD-XC-PAC - Temperature module
Inline, Temperature measurement terminal, Analog RTD inputs: 2, connection technology: 2-, 3-, 4-conductor, transmission speed in the local bus: 500 kbps, Extreme conditions version, degree of protection: IP20, including Inline connector and labeling field
- 2 inputs for resistive temperature sensors
- Pt, Ni, Cu, KTY sensor types according to DIN and SAMA
- Connection of sensors in 2-, 3-, and 4-conductor technology
- The channels are parameterized independently of one another via the bus system
- Measured values can be represented in three different formats
- Measured value acquisition with a resolution of 16 bits
- Channel scout for optical channel identification
- Can be used under extreme ambient conditions
- Extended temperature range of -40 °C ... +70 °C (see “Tested successfully: use under extreme ambient conditions” in the data sheet)
- Coated PCBs
Technical Specifications
Dimensions
Width | 12.2 mm |
Height | 136.8 mm |
Depth | 71.5 mm |
Inline local bus
Number of interfaces | 2 |
Connection Method | Inline data jumper |
Transmission Speed | 500 kbps |
Module
ID code (dec.) | 127 |
ID code (hex) | 7F |
Length code (hex) | 02 |
Length code (dec) | 02 |
Process data channel | 32 bit |
Input address area | 4 Byte |
Output address area | 4 Byte |
Register length | 32 bit |
Required parameter data | 6 Byte |
Required configuration data | 4 Byte |
Analog
Input name | Analog RTD inputs |
Description of the input | Input for resistive temperature sensors |
Number of Inputs | 2 |
Connection Method | Spring-cage connection |
Connection technology | 2-, 3-, 4-conductor |
Note regarding the connection technology | shielded |
A/D conversion time | typ. 120 µs (per channel) |
A/D converter resolution | 16 bit (15 bit + sign bit) |
Sensor types (RTD) that can be used | Pt, Ni, KTY, Cu sensors, linear resistors |
Measuring Principle | Successive approximation |
Measured value representation | 16 bits two's complement and other |
Linear resistance measuring range | 0 Ω ... 400 Ω |
Linear resistance measuring range | 0 Ω ... 4 kΩ |
Process data update | 32 ms (both channels use 3-conductor technology) |
Process data update | 20 ms (one channel in 2-conductor technology and one channel in 4-conductor technology) |
Process data update | 20 ms (both channels in 2-conductor technology) |
Product properties
Product family | Inline |
Type | modular |
Scope of delivery | including Inline connector and labeling field |
Operating mode | Process data operation with 2 words |
Special Properties | Extreme conditions version |
Insulation characteristics
Overvoltage category | II (IEC 60664-1, EN 60664-1) |
Pollution degree | 2 (IEC 60664-1, EN 60664-1) |
Potentials
Power consumption | typ. 587 mW |
Power consumption | max. 882 mW |
Potentials: Communications power (UL)
Supply Voltage | 7.5 V DC (via voltage jumper) |
Current draw | max. 60 mA |
Current draw | typ. 43 mA |
Potentials: Supply of analog modules (UANA)
Supply Voltage | 24 V DC (via voltage jumper) |
Supply Voltage Range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
Current draw | max. 18 mA |
Current draw | typ. 11 mA |
Electrical isolation/isolation of the voltage ranges
Test voltage: 7.5 V supply (bus logics)/24 V analog supply (analog I/O) | 500 V AC, 50 Hz, 1 min. |
Test voltage: 7.5 V supply (bus logic)/functional ground | 500 V AC, 50 Hz, 1 min. |
Test voltage: 24 V analog supply (analog I/O)/functional ground | 500 V AC, 50 Hz, 1 min. |
Connection technology
Connection name | Inline connector |
Conductor connection
Connection Method | Spring-cage connection |
Conductor cross section rigid | 0.08 mm² ... 1.5 mm² |
Conductor cross section flexible | 0.08 mm² ... 1.5 mm² |
Conductor cross section AWG | 28 ... 16 |
Stripping length | 8 mm |
Inline connector
Connection Method | Spring-cage connection |
Conductor cross section, rigid | 0.08 mm² ... 1.5 mm² |
Conductor cross section, flexible | 0.08 mm² ... 1.5 mm² |
Conductor cross section AWG | 28 ... 16 |
Stripping length | 8 mm |
Ambient conditions
Ambient Temperature (Operation) | -25 °C ... 55 °C (Standard) |
Ambient Temperature (Operation) | -40 °C ... 70 °C (Extended, see section “Tested successfully: use under extreme ambient conditions” in the data sheet.) |
Degree of Protection | IP20 |
Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
Permissible humidity (storage/transport) | 10 % ... 95 % (non-condensing) |
Standards and Regulations
Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
Mounting
Mounting Type | DIN rail mounting |
Accessories
Why Proax for Phoenix Contact 2701217?
Proax is an authorized distributor of Phoenix Contact 2701217 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended