Series IB-IL-TEMP

IB IL TEMP 4/8 RTD/EF-PAC - Temperature module

Inline, Temperature measurement terminal, Analog RTD inputs: 8 (for resistance temperature detectors), connection technology: 4-conductor, transmission speed in the local bus: 500 kbps, degree of protection: IP20, including Inline connectors and marking fields

  • Connection of 8 RTD temperature sensors and linear resistors in 4-conductor technology
  • Pt, Ni, Cu, KTY sensor types according to DIN and SAMA
  • High precision and noise immunity
  • Temperature stability
  • High-resolution temperature and resistance measurement
  • Resistance values can be preset separately via parameterization bits
  • The channels are parameterized independently of one another via the bus system
  • Parameterization of wire-break detection sensitivity (firmware 1.10 or later)
  • Additional representation in float format according to IEEE754
  • Channel scout functionality, for optical channel identification during startup
Technical Specifications

Dimensions

Width48.8 mm
Height119.8 mm
Depth71.5 mm
Note on dimensionsHousing dimensions

Utilization restriction

CCCex noteUse in potentially explosive areas is not permitted in China.

Inline local bus

Number of interfaces2
Connection MethodInline data jumper
Transmission Speed500 kbps
Transmission physicsCopper

Module

ID code (dec.)223
ID code (hex)DF
Length code (hex)05
Length code (dec)05
Process data channel80 bit
Input address area10 Byte
Output address area10 Byte
Register length96 bit
Required parameter data 31 Byte
Required configuration data 5 Byte

Analog

Input nameAnalog RTD inputs
Description of the inputInput for resistive temperature sensors
Number of Inputs8 (for resistance temperature detectors)
Connection MethodSpring-cage connection
Connection technology4-conductor
Note regarding the connection technologyshielded
A/D converter resolution24 bit
Sensor types (RTD) that can be usedPt, Ni, KTY, Cu sensors, linear resistors
Data formatsIB IL, S7-compatible
Measuring PrincipleSigma/Delta process
Measured value representation16 bits (15 bits + sign bit)
Input filter time100 ms
Input filter time120 ms
Input filter time200 ms
Input filter time480 ms (adjustable)
Differential non-linearitytyp. 1 ppm / ±0.0001 % (in all ranges)
Integral non-linearitytyp. 30 ppm / ±0.003 % (Pt 100)
Integral non-linearitytyp. 20 ppm / ±0.002 % (RLin 500 Ω)
Integral non-linearitytyp. 200 ppm / ±0.02 % (RLin 5000 Ω)
Linear resistance measuring range0 Ω ... 500 Ω
Linear resistance measuring range0 Ω ... 5 kΩ
Linear resistance measuring range0 Ω ... 30 kΩ
Process data update1.8 s (Up to 3.3 s possible depending on operating mode)

Product properties

Product familyInline
Typemodular
Scope of deliveryincluding Inline connectors and marking fields
Operating modeProcess data mode with 5 words/1 word PCP
Diagnostics messagesFailure of the internal I/O supply I/O error message sent to the bus coupler
Diagnostics messagesFailure of or insufficient communications power UL I/O error message sent to the bus coupler
Diagnostics messagesUser error Error message in the process data

Insulation characteristics

Overvoltage categoryII (IEC 60664-1, EN 60664-1)
Pollution degree2 (IEC 60664-1, EN 60664-1)

Electrical properties

Maximum power dissipation for nominal condition0.59 W

Potentials

Power consumptiontyp. 0.85 W (entire device)

Potentials: Communications power (UL)

Supply Voltage7.5 V DC (via voltage jumper)
Current drawmax. 120 mA
Current drawtyp. 95 mA

Potentials: Supply of analog modules (UANA)

Supply Voltage24 V DC (via voltage jumper)
Supply Voltage Range19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current drawmax. 15 mA
Current drawtyp. 6 mA

Electrical isolation/isolation of the voltage ranges

Test voltage: 7.5 V supply (bus logic), 24 V supply UANA / I/O500 V AC, 50 Hz, 1 min.
Test voltage: 7.5 V supply (bus logic), 24 V supply UANA / functional ground500 V AC, 50 Hz, 1 min.
Test voltage: I/O/functional ground500 V AC, 50 Hz, 1 min.

Connection technology

Connection nameInline connector

Conductor connection

Connection MethodSpring-cage connection
Conductor cross section rigid0.08 mm² ... 1.5 mm²
Conductor cross section flexible0.08 mm² ... 1.5 mm²
Conductor cross section AWG28 ... 16
Stripping length8 mm

Inline connector

Connection MethodSpring-cage connection
Conductor cross section, rigid0.08 mm² ... 1.5 mm²
Conductor cross section, flexible0.08 mm² ... 1.5 mm²
Conductor cross section AWG28 ... 16
Stripping length8 mm

Ambient conditions

Ambient Temperature (Operation)-25 °C ... 60 °C
Degree of ProtectionIP20
Air pressure (operation)70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)70 kPa ... 106 kPa (up to 3000 m above sea level)
Ambient temperature (storage/transport)-25 °C ... 85 °C
Permissible humidity (operation)10 % ... 95 % (non-condensing)
Permissible humidity (storage/transport)10 % ... 95 % (non-condensing)

Standards and Regulations

Protection classIII (IEC 61140, EN 61140, VDE 0140-1)

Mounting

Mounting TypeDIN rail mounting
Accessories

Why Proax for Phoenix Contact IB IL TEMP 4/8 RTD/EF-PAC?

Proax is an authorized distributor of Phoenix Contact IB IL TEMP 4/8 RTD/EF-PAC and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information

Alternate NamesIBILTEMP48RTDEFPAC
Pack Size1