3245066
UTN 35 - N disconnect terminal block
N disconnect terminal block, Assembly instructions:For secure fastening of the neutral busbar, supports must be set at the beginning and end of each terminal strip as well as every 20 cm on longer terminal strips., for neutral conductor disconnection, nom. voltage: 400 V, nominal current: 110 A, Special and hybrid connection, 1st level connection right, Rated cross section: 35 mm2, cross section: 0.75 mm2 - 35 mm2, mounting type: NS 35/7,5, NS 35/15, color: blue
- Same shape as UT standard terminal blocks
General
| Note | Assembly instructions:For secure fastening of the neutral busbar, supports must be set at the beginning and end of each terminal strip as well as every 20 cm on longer terminal strips. |
| Number of rows | 1 |
| Number of Connections | 2 |
| Potentials | 1 |
| Nominal cross section | 35 mm² |
| Color | blue |
| Insulating material | PA |
| Flammability rating according to UL 94 | V2 |
| Mounting Type | NS 35/7,5 |
| Rated surge voltage | 6 kV |
| Degree of pollution | 3 |
| Overvoltage category | III |
| Insulating material group | I |
| Maximum power dissipation for nominal condition | 4.06 W |
| Maximum Load Current | 110 A (with 35 mm² conductor cross section) |
| Nominal current IN | 110 A |
| Nominal voltage UN | 400 V |
| Open side panel | No |
| General information | The max. load current must not be exceeded by the total current of all connected conductors. |
| Shock protection test specification | DIN EN 50274 (VDE 0660-514):2002-11 |
| Back of the hand protection | guaranteed |
| Result of surge voltage test | Test passed |
| Surge voltage test setpoint | 7.2 kV |
| Result of power-frequency withstand voltage test | Test passed |
| Power frequency withstand voltage setpoint | 1.89 kV |
| Result of the test for mechanical stability of terminal points (5 x conductor connection) | Test passed |
| Result of flexion and pull-out test | Test passed |
| Bending test rotation speed | 10 (+/- 2) rpm |
| Bending test turns | 135 |
| Bending test conductor cross section/weight | 0.75 mm² / 0.4 kg |
| Bending test conductor cross section/weight | 10 mm² / 2 kg |
| Bending test conductor cross section/weight | 35 mm² / 6.8 kg |
| Tensile test result | Test passed |
| Conductor cross section tensile test | 0.75 mm² |
| Tractive force setpoint | 30 N |
| Conductor cross section tensile test | 10 mm² |
| Tractive force setpoint | 90 N |
| Conductor cross section tensile test | 35 mm² |
| Tractive force setpoint | 190 N |
| Result of voltage-drop test | Test passed |
| Requirements, voltage drop | U1 ≤ 4.8 mV (1.6 mV x number of conductor clamping units or disconnect unit contact points) U2 ≤ 1.5 x U1 |
| Result of temperature-rise test | Test passed |
| Requirement temperature-rise test | Increase in temperature ≤ 45 K |
| Short circuit stability result | Test passed |
| Conductor cross section short circuit testing | 35 mm² |
| Short-time current | 4.2 kA |
| Result of thermal test | Test passed |
| Proof of thermal characteristics (needle flame) effective duration | 30 s |
| Oscillation, broadband noise test result | Test passed |
| Test specification, oscillation, broadband noise | DIN EN 50155 (VDE 0115-200):2018-05 |
| Test spectrum | Service life test category 2, bogie-mounted |
| Test frequency | f1 = 5 Hz to f2 = 250 Hz |
| ASD level | 6.12 (m/s²)²/Hz |
| Acceleration | 3.12g |
| Test duration per axis | 5 h |
| Test directions | X-, Y- and Z-axis |
| Shock test result | Test passed |
| Shock form | Semi-sinusoidal |
| Acceleration | 5g |
| Shock duration | 30 ms |
| Number of shocks per direction | 3 |
| Test directions | X-, Y- and Z-axis (pos. and neg.) |
| Relative insulation material temperature index (Elec., UL 746 B) | 125 °C |
| Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) | 125 °C |
| Static insulating material application in cold | -40 °C |
Dimensions
| Width | 15 mm |
| Length | 55 mm |
| Height | 49.8 mm |
| Height NS 35/7,5 | 51 mm |
| Height NS 32 | 56 mm |
Connection data
| Connection | 1st level connection right |
| Connection Method | Special and hybrid connection |
| Screw thread | M6 |
| Stripping length | 16 mm |
| Tightening torque, min | 3.2 Nm |
| Tightening torque max | 3.7 Nm |
| Connection in acc. with standard | IEC 60947-7-1 |
| Conductor cross section solid min. | 0.75 mm² |
| Conductor cross section solid max. | 35 mm² |
| Conductor cross section AWG min. | 18 |
| Conductor cross section AWG max. | 2 |
| Conductor cross section flexible min. | 0.75 mm² |
| Conductor cross section flexible max. | 35 mm² |
| Min. AWG conductor cross section, flexible | 18 |
| Max. AWG conductor cross section, flexible | 2 |
| Conductor cross section flexible, with ferrule without plastic sleeve min. | 0.75 mm² |
| Conductor cross section flexible, with ferrule without plastic sleeve max. | 35 mm² |
| Conductor cross section flexible, with ferrule with plastic sleeve min. | 0.75 mm² |
| Conductor cross section flexible, with ferrule with plastic sleeve max. | 35 mm² |
| 2 conductors with same cross section, solid min. | 0.75 mm² |
| 2 conductors with same cross section, solid max. | 10 mm² |
| 2 conductors with same cross section, stranded min. | 0.75 mm² |
| 2 conductors with same cross section, stranded max. | 10 mm² |
| Two conductors with the same cross section, flexible, with TWIN ferrules, with plastic sleeve, minimum | 0.75 mm² |
| Two conductors with the same cross section, flexible, with TWIN ferrules, with plastic sleeve, maximum | 6 mm² |
| Two conductors with the same cross section stranded, with ferrule and without plastic sleeve, minimum | 0.75 mm² |
| Two conductors with the same cross section stranded, with ferrule and without plastic sleeve, maximum | 10 mm² |
Ambient conditions
| Operating Temperature | -60 °C ... 105 °C (max. short-term operating temperature RTI Elec.) |
| Ambient temperature (storage/transport) | -25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C) |
| Permissible humidity (storage/transport) | 30 % ... 70 % |
| Ambient temperature (assembly) | -5 °C ... 70 °C |
Standards and Regulations
| Connection in acc. with standard | IEC 60947-7-1 |
Environmental Product Compliance
| China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
| China RoHS | No hazardous substances above threshold values |
Why Proax for Phoenix Contact 3245066?
Proax is an authorized distributor of Phoenix Contact 3245066 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
| Pack Size | 50 |
UT 4-HESILED 24 (5X20) - Fuse modular terminal block, fuse type: Glass / ceramics / ..., fuse type: G / 5 x 20, nom. voltage: 24 V, nominal current: 6.3 A, connection method: Screw connection, Rated cross section: 4 mm2, cross section: 0.14 mm2- 6 mm2, mounting type: NS 35/7,5, NS 35/15, color: black
UK 6,3-HESI - Fuse modular terminal block, fuse type: Glass / ceramics / ..., fuse type: G / 6,3 x 32, nom. voltage: 500 V, nominal current: 10 A, number of positions: 1, connection method: Screw connection, Rated cross section: 1.5 mm2, cross section: 0.5 mm2- 16 mm2, mounting type: NS 35/7,5, NS 35/15, NS 32, color: black
Fuse modular terminal block, fuse type: Glass / ceramics / ..., fuse type: G / 6,3 x 32, nom. voltage: 24 V, nominal current: 10 A, number of positions: 1, connection method: Screw connection, Rated cross section: 1.5 mm2, cross section: 0.5 mm2- 16 mm2, mounting type: NS 35/7,5, NS 35/15, NS 32, color: black