IB IL 24 LPSDO 8-PAC - Safety module
Safety-related digital output module, IP20 protection, for the SafetyBridge system. The module has four safe digital outputs with two-channel occupancy or 8 safe digital outputs with single-channel occupancy
- Generation and monitoring of the SafetyBridge protocol
- Processing of the parameterized safety logic
- SIL 3 according to IEC/EN 61508
- SIL 3 in accordance with EN IEC 62061
- PL e in accordance with EN ISO 13849-1
Technical Specifications
Dimensions
Width | 48.8 mm |
Height | 119.8 mm |
Depth | 71.5 mm |
Note on dimensions | Housing dimensions |
Material specifications
Color | yellow |
Inline local bus
No. of channels | 2 |
Connection Method | Inline data jumper |
Transmission Speed | 500 kbps / 2 Mbps |
SafetyBridge properties
Connection to I/O modules | max. 3 (safe digital input modules) |
Logic memory | 6 kByte |
Module
ID code (dec.) | 199 |
ID code (hex) | C7 |
Length code (hex) | 12 |
Length code (dec) | 18 |
Process data channel | 30 Byte |
Input address area | max. 30 Byte ((Operating mode: SafetyBridge)) |
Output address area | max. 30 Byte ((Operating mode: SafetyBridge)) |
Register length | 32 Byte |
Required parameter data | 1 Byte ((Operating mode: SafetyBridge)) |
Required configuration data | 5 Byte ((Operating mode: SafetyBridge)) |
Digital:
Output name | Digital outputs |
Connection Method | Spring-cage connection |
Connection technology | 2-, 3-, 4-conductor |
Number of Outputs | 4 (for 2-channel assignment) |
Number of Outputs | 8 (for 1-channel assignment) |
Number of Outputs | 8 |
Protective circuit | Overload protection, short-circuit protection of outputs |
Output Voltage | 24 V DC (US - 1 V) |
Output Current | max. 6 A (Total current of all outputs, -25 °C ... 50 °C) |
Output Current | max. 4 A (Total current of all outputs, >50 °C ... 55 °C) |
Maximum output current per group | 3 A |
Maximum Output Current per channel | 2 A |
Nominal Output Voltage | 24 V DC |
Nominal load, inductive | see safety data |
Nominal load, lamp | see safety data |
Nominal load, ohmic | see safety data |
Behavior with inductive overload | Output can be destroyed |
Product properties
Product family | Inline |
Application | Functional safety |
Type | modular |
Diagnostics messages | Short-circuit or overload of the digital outputs Error message in diagnostics code (bus) and display by means of the LED on the motor |
Electrical properties
Maximum power dissipation for nominal condition | 150 W |
Transmission medium | Copper |
Potentials: Communications power (UL)
Supply Voltage | 7.5 V DC (see safety data) |
Current draw | max. 230 mA (see safety data) |
Potentials: Main circuit supply (UM)
Supply Voltage | 24 V DC (see safety data) |
Supply Voltage Range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
Current draw | max. 6.03 A |
Current draw | typ. 30 mA (all outputs set including actuator current) |
Potentials: Segment circuit supply (US)
Supply Voltage | 24 V (see safety data) |
Supply: Module electronics
Supply Voltage | 24 V DC (via voltage jumper) |
Supply Voltage Range | 19.2 V DC ... 30 V DC |
Electrical isolation/isolation of the voltage ranges
Test voltage: 5 V supply, incoming remote bus/7.5 V supply (bus logics) | 500 V AC, 50 Hz, 1 min. |
Test voltage: 5 V supply, outgoing remote bus/7.5 V supply (bus logics) | 500 V AC, 50 Hz, 1 min. |
Test voltage: 7.5 V supply (bus logics)/24 V supply (I/O) | 500 V AC, 50 Hz, 1 min. |
Test voltage: 24 V supply (I/O) / functional ground | 500 V AC, 50 Hz, 1 min. |
Connection technology
Connection name | Inline connector |
pluggable | yes |
Conductor connection
Connection Method | Spring-cage connection |
Conductor cross section rigid | 0.2 mm² ... 1.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 1.5 mm² |
Conductor cross section AWG | 24 ... 16 |
Inline connector
Connection Method | Spring-cage connection |
Conductor cross section, rigid | 0.2 mm² ... 1.5 mm² |
Conductor cross section, flexible | 0.2 mm² ... 1.5 mm² |
Conductor cross section AWG | 24 ... 16 |
Ambient conditions
Ambient Temperature (Operation) | -25 °C ... 55 °C |
Degree of Protection | IP20 |
Air pressure (operation) | 80 hPa ... 108 kPa (up to 2000 m above sea level) |
Air pressure (storage/transport) | 66 hPa ... 108 kPa (up to 3500 m above sea level) |
Ambient temperature (storage/transport) | -25 °C ... 70 °C |
Permissible humidity (operation) | 10 % ... 85 % (Take suitable measures against increased air humidity within the permitted temperature range.) |
Permissible humidity (storage/transport) | 10 % ... 85 % (Take suitable measures against increased air humidity within the permitted temperature range.) |
Standards and Regulations
Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
Mounting
Mounting Type | DIN rail mounting |
Accessories
Why Proax for Phoenix Contact 2916024?
Proax is an authorized distributor of Phoenix Contact 2916024 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended