Official Distributor
SKU
MPN
IB IL 24 PSDI 8-PAC
Weight
0.351 kg
This product is Not Cancellable/Not Returnable
Series IB-IL
IB IL 24 PSDI 8-PAC - Safety module
Safety-related digital input module, IP20 protection, for the SafetyBridge, INTERBUS-Safety, and PROFIsafe system. The module has 4 safe digital inputs for two-channel assignment or 8 safe digital inputs for single-channel assignment.
- SIL 3 according to IEC/EN 61508
- SIL 3 in accordance with EN IEC 62061
- PL e in accordance with EN ISO 13849-1
Technical Specifications
Dimensions
Width | 48.8 mm |
Height | 119.8 mm |
Depth | 71.5 mm |
Note on dimensions | Housing dimensions |
Inline local bus
No. of channels | 2 |
Connection Method | Inline data jumper |
Transmission Speed | 500 kbps / 2 Mbps (can be switched) |
Module
ID code (dec.) | 163 |
ID code (hex) | A3 |
Length code (hex) | 04 |
Length code (dec) | 04 |
Process data channel | 8 Byte |
Input address area | 8 Byte ((Operating mode: SafetyBridge)) |
Output address area | 8 Byte ((Operating mode: SafetyBridge)) |
Register length | 8 Byte |
Required parameter data | 1 Byte ((Operating mode: SafetyBridge)) |
Required configuration data | 5 Byte ((Operating mode: SafetyBridge)) |
Digital:
Input name | Digital inputs |
Description of the input | IEC 61131-2 type 3 |
Number of Inputs | 4 (for 2-channel assignment) |
Number of Inputs | 8 (for 1-channel assignment) |
Cable Length | max. 200 m (200 m from the clock output to the safe input (total based on forward and return path)) |
Connection Method | Spring-cage connection |
Connection technology | 2-, 3-, 4-conductor |
Input Voltage | 24 V DC (via clock outputs UT1 and UT2 or external supply) |
Input voltage range | -3 V DC ... 30 V DC |
Input voltage range "0" signal | -3 V DC ... 5 V DC |
Input voltage range "1" signal | 11 V DC ... 30 V DC |
Typical input current per channel | 4.2 mA (at 24 V) |
Typical response time | See technical data |
Product properties
Product family | Inline |
Application | Functional safety |
Type | modular |
Electrical properties
Maximum power dissipation for nominal condition | 24.12 W |
Transmission medium | Copper |
Potentials: Communications power (UL)
Supply Voltage | 7.5 V DC (see safety data) |
Current draw | max. 180 mA |
Potentials: Main circuit supply (UM)
Supply Voltage | 24 V DC |
Supply Voltage Range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
Current draw | max. 825 mA (see safety data) |
Current draw | typ. 25 mA (plus current consumption of the inputs when supplied via the clock outputs, plus current consumption of the connected initiators when via through the clock outputs) |
Supply: Module electronics
Supply Voltage | 24 V DC (via voltage jumper) |
Supply Voltage Range | 19.2 V DC ... 30 V DC |
Electrical isolation/isolation of the voltage ranges
Test voltage: 5 V supply, incoming remote bus/7.5 V supply (bus logics) | 500 V AC, 50 Hz, 1 min. |
Test voltage: 5 V supply, outgoing remote bus/7.5 V supply (bus logics) | 500 V AC, 50 Hz, 1 min. |
Test voltage: 7.5 V supply (bus logics)/24 V supply (I/O) | 500 V AC, 50 Hz, 1 min. |
Test voltage: 24 V supply (I/O) / functional ground | 500 V AC, 50 Hz, 1 min. |
Connection technology
Connection name | Inline connector |
pluggable | yes |
Conductor connection
Connection Method | Spring-cage connection |
Conductor cross section rigid | 0.2 mm² ... 1.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 1.5 mm² |
Conductor cross section AWG | 24 ... 16 |
Inline connector
Connection Method | Spring-cage connection |
Conductor cross section, rigid | 0.2 mm² ... 1.5 mm² |
Conductor cross section, flexible | 0.2 mm² ... 1.5 mm² |
Conductor cross section AWG | 24 ... 16 |
Ambient conditions
Ambient Temperature (Operation) | -25 °C ... 55 °C |
Degree of Protection | IP20 |
Air pressure (operation) | 80 kPa ... 108 kPa (up to 2000 m above sea level) |
Air pressure (storage/transport) | 66 kPa ... 108 kPa (up to 3500 m above sea level) |
Ambient temperature (storage/transport) | -25 °C ... 70 °C |
Permissible humidity (operation) | 10 % ... 85 % (Take suitable measures against increased air humidity within the permitted temperature range.) |
Permissible humidity (storage/transport) | 10 % ... 85 % (Take suitable measures against increased air humidity within the permitted temperature range.) |
Standards and Regulations
Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
Mounting
Mounting Type | DIN rail mounting |
Accessories
Why Proax for Phoenix Contact 2985688?
Proax is an authorized distributor of Phoenix Contact 2985688 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended