IB IL 24 PWR IN/R-PAC
Weight
0.226 kg
This product is Not Cancellable/Not Returnable
Series IB-IL
IB IL 24 PWR IN/R-PAC - Power module
Inline power terminal or boost terminal, complete with accessories (connector and labeling field), 24 V DC, without fuse
- Supply of all 24 V voltages required for the low-level signal of an Inline station
Technical Specifications
Dimensions
Width | 48.8 mm |
Height | 119.8 mm |
Depth | 71.5 mm |
Utilization restriction
CCCex note | Use in potentially explosive areas is not permitted in China. |
Inline local bus
Number of interfaces | 2 |
Connection Method | Inline data jumper |
Transmission Speed | 500 kbps / 2 Mbps (Can be used in Inline stations with these transmission speeds) |
Module
ID code (dec.) | none |
ID code (hex) | none |
Register length | 0 bit |
Required parameter data | 0 Byte |
Required configuration data | 0 Byte |
Product properties
Product family | Inline |
Type | modular |
Number of plugs | 4 |
Special Properties | 24 V DC |
Special Properties | Supply/boost UM, US, UL, UANA |
Insulation characteristics
Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
Electrical properties
Test section | 7.5 V communications power, 24 V analog supply/functional ground 500 V AC 50 Hz 1 min. |
Test section | 7.5 V logics supply, 24 V analog supply / 24 V main supply, 24 V segment supply 500 V AC 50 Hz 1 min. |
Test section | 24 V main supply, 24 V segment supply/functional ground 500 V AC 50 Hz 1 min. |
Protective circuit | Surge protection (segment supply, main supply, 24 V supply); Input protective diodes (can be destroyed by permanent overload)Pulse loads up to 1500 W are short circuited by the input protective diode. |
Protective circuit | Protection against polarity reversal (segment supply/main supply); Parallel diodes for protection against polarity reversal; in the event of an error the high current flowing through the diodes causes the fuse connected upstream to blow. |
Protective circuit | Polarity reversal (24 V supply); Serial diode in the lead path of the power supply unit; in the event of an error only a low current flows. In the event of an error, no fuse trips within the external power supply unit. |
Fuse | electrical/thermal overload protection, included in scope of delivery |
Supply
I/O voltage | 24 V DC |
I/O voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
Residual ripple | ± 1.2 V |
Max. current consumption | 8 A |
Potentials
Power consumption | max. 2.55 W (entire device) |
Potentials: 24 V supply (U24V) for generating UL and UANA
Supply Voltage | 24 V DC (via Inline connector) |
Supply Voltage Range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
Current draw | max. 1.25 A DC (at nominal voltage; consisting of: 0.75 A DC for the communications power and 0.5 A DC for the analog voltage supply) |
Current draw | min. 12 mA DC (at nominal voltage) |
Potentials: Communications power (UL)
Supply Voltage | 7.5 V DC (via voltage jumper) |
Potentials: Supply of analog modules (UANA)
Supply Voltage | 24 V DC |
Supply Voltage Range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
Potentials: Main circuit supply (UM)
Supply Voltage | 24 V DC (via Inline connector) |
Supply Voltage Range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
Potentials: Segment circuit supply (US)
Supply Voltage | 24 V DC (via Inline connector) |
Supply Voltage Range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
Connection technology
Connection name | Inline connector |
Conductor connection
Connection Method | Spring-cage connection |
Conductor cross section rigid | 0.08 mm² ... 1.5 mm² |
Conductor cross section flexible | 0.08 mm² ... 1.5 mm² |
Conductor cross section AWG | 28 ... 16 |
Stripping length | 8 mm |
Inline connector
Connection Method | Spring-cage connection |
Conductor cross section, rigid | 0.08 mm² ... 1.5 mm² |
Conductor cross section, flexible | 0.08 mm² ... 1.5 mm² |
Conductor cross section AWG | 28 ... 16 |
Stripping length | 8 mm |
Ambient conditions
Degree of Protection | IP20 |
Ambient Temperature (Operation) | -25 °C ... 55 °C |
Ambient temperature (storage/transport) | -25 °C ... 85 °C |
Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
Permissible humidity (storage/transport) | 10 % ... 95 % (non-condensing) |
Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Mounting
Mounting Type | DIN rail mounting |
Accessories
Why Proax for Phoenix Contact 2861674?
Proax is an authorized distributor of Phoenix Contact 2861674 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended