Proax

Currency
0 Items
proax logo
Cart
Phoenix ContactOfficial Distributor

By Phoenix Contact

SKU
MPN
IB IL 24 LSKIP-PAC
Weight
0.251 kg
This product is Not Cancellable/Not Returnable
Series IB-IL

IB IL 24 LSKIP-PAC - Communication module

Inline, Coupler terminal, for extending the Inline local bus, transmission speed in the local bus: 500 kbps / 2 Mbps, degree of protection: IP20, including Inline connectors and marking fields

  • Supply of all 24 V voltages required for the low-level signal of an Inline station
  • Data transmission between terminals IB IL 24 FLM-PAC and IB IL 24 LSKIP-PAC via the RS-422 protocol
Technical Specifications

Dimensions

Width48.8 mm
Height135 mm
Depth71.5 mm

Inline local bus

Number of interfaces1 (incoming local bus)
Connection MethodInline shield connector
Note on the connection methodStandard INTERBUS cable
Transmission Speed500 kbps / 2 Mbps (Can be used in Inline stations with these transmission speeds)
Transmission physicsCopper
Number of interfaces1
Connection MethodInline data jumper
Transmission Speed500 kbps / 2 Mbps

System limits

Number of local bus devices that can be connectedmax. 63 (without additional power terminal block, observe allowable total current consumption)
Number of devices with parameter channel63

Module

ID code (hex)none
Input address area0 Byte
Output address area0 Byte
Register length0 bit
Required parameter data 0 Byte
Required configuration data 0 Byte

Product properties

Product familyInline
Typemodular
Scope of deliveryincluding Inline connectors and marking fields
Special Propertiesfor extending the Inline local bus

Electrical properties

Protective circuitSurge protection (segment supply, main supply, 24 V supply); Input protective diodes (can be destroyed by permanent overload)Pulse loads up to 1500 W are short circuited by the input protective diode.
Protective circuitProtection against polarity reversal (segment supply/main supply); Parallel diodes for protection against polarity reversal; in the event of an error the high current flowing through the diodes causes the fuse connected upstream to blow.
Protective circuitPolarity reversal (24 V supply); Serial diode in the lead path of the power supply unit; in the event of an error only a low current flows. In the event of an error, no fuse trips within the external power supply unit.
Protective circuitShort-circuit protection of the communications power; electronic
Protective circuitShort-circuit protection of the analog supply; electronic

Potentials: 24 V supply (U24V) for generating UL and UANA

Supply Voltage24 V DC (via Inline connector)
Supply Voltage Range19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current drawmax. 1.25 A (at nominal voltage; consisting of: 0.75 A DC for the communications power and 0.5 A DC for the analog voltage supply)
Current drawmin. 60 mA (without connected Inline I/O terminals)

Potentials: Communications power (UL)

Supply Voltage7.5 V DC

Potentials: Supply of analog modules (UANA)

Supply Voltage24 V DC (via voltage jumper)
Supply Voltage Range19.2 V DC ... 30 V DC (including all tolerances, including ripple)

Potentials: Main circuit supply (UM)

Supply Voltage24 V DC (via Inline connector)
Supply Voltage Range19.2 V DC ... 30 V DC (including all tolerances, including ripple)

Potentials: Segment circuit supply (US)

Supply Voltage24 V DC (via Inline connector)
Supply Voltage Range19.2 V DC ... 30 V DC (including all tolerances, including ripple)

Electrical isolation/isolation of the voltage ranges

Test voltage: 5 V supply incoming local bus / 7.5 V communications power, 24 V analog power supply, 24 V power supply for generating voltages UL and UANA500 V AC, 50 Hz, 1 min.
Test voltage: 5 V supply incoming local bus / 24 V main supply, 24 V segment supply500 V AC, 50 Hz, 1 min.
Test voltage: 7.5 V communications power, 24 V analog power supply, 24 V power supply for generating voltages UL and UANA / functional ground500 V AC, 50 Hz, 1 min.
Test voltage: 7.5 V communications power, 24 V analog power supply, 24 V power supply for generating voltages UL and UANA / 24 V main supply, 24 V segment supply500 V AC, 50 Hz, 1 min.
Test voltage: 24 V main supply, 24 V segment supply, 24 V power supply for generating voltages UL and UANA / functional ground500 V AC, 50 Hz, 1 min.

Connection technology

Connection nameInline connector

Conductor connection

Connection MethodSpring-cage connection
Conductor cross section rigid0.08 mm² ... 1.5 mm²
Conductor cross section flexible0.08 mm² ... 1.5 mm²
Conductor cross section AWG28 ... 16
Stripping length8 mm

Inline connector

Connection MethodSpring-cage connection
Conductor cross section, rigid0.08 mm² ... 1.5 mm²
Conductor cross section, flexible0.08 mm² ... 1.5 mm²
Conductor cross section AWG28 ... 16
Stripping length8 mm

Ambient conditions

Ambient Temperature (Operation)-25 °C ... 55 °C
Degree of ProtectionIP20
Air pressure (operation)70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)70 kPa ... 106 kPa (up to 3000 m above sea level)
Ambient temperature (storage/transport)-25 °C ... 85 °C
Permissible humidity (operation)10 % ... 95 % (non-condensing)
Permissible humidity (storage/transport)10 % ... 95 % (non-condensing)

Standards and Regulations

Protection classIII (IEC 61140, EN 61140, VDE 0140-1)

Mounting

Mounting TypeDIN rail mounting
Accessories

Why Proax for Phoenix Contact 2897457?

Proax is an authorized distributor of Phoenix Contact 2897457 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information

Pack Size1
Recommended

Not in stock

Request lead time or order—we'll ensure quick delivery

Phoenix Contact Availability